Professional Documents
Culture Documents
Hyundai Elevator Planning Guide
Hyundai Elevator Planning Guide
PLANNING GUIDE - We reserve the right to change designs and specifications for the product development without prior notice.
Copyright Ϳ HYUNDAI ELEVATOR CO., LTD. All rights reserved. Printed in Korea.
C-EPG-E1605 / 2012. 09 / Revision 16
Selection of Elevator System
The selection of elevators should be made in consideration of the building type/scale, tenant
characteristics, elevator usage and the anticipated passenger carrying capacity at the
buildingÍ
s traffic peak time.
Hyundai elevators are available from machine-room-less elevators to low-medium and ultra
high-speed elevators, covering the full range of vertical transportation requirements.
ELEVATORS
And a variety of functional and attractive designs per usages, such as passenger, service,
observation, hospital bed, freight and automobile elevators are offered for architectsÍand
customersÍ flexible applications.
MOVING WALKS
Kinds of Building Usage Control Speed Operation
(m/min)
2
PASSENGER ELEVATORS
Gearless Elevatorsǖ60~150m/min
Plan of Hoistway & Machine Room Section of Hoistway Standard Dimensions & Reactions
(Unit : mm)
Height (MH)
(Byothers)
6 450 800 1400Ý 850 1460Ý1005 1800 3700 5600 1430 2000 4000 6000 3200 3600 2000 5400 4500
M/C Room
(By others)
Cinder
(By others) 8 550 800 1400Ý1030 1460Ý1185 1800 3700 5600 1610 2000 4000 6000 3400 4050 2250 6000 4900
Vent
Vent
Vent
Vent Grille
Grille
Grille
VentGrille
9 600 800 1400Ý1130 1460Ý1285 1800 3700 5600 1710 2000 4000 6000 3500 4100 2450 6300 5100
CB
Y
60
B
R2 R1
CA
10 700 800 1400Ý1250 1460Ý1405 1800 3700 5600 1830 2000 4000 6000 3600 4200 2700 6800 5400
MY
Overhead (OH)
11 750 800 1400Ý1350 1460Ý1505 1800 3700 5600 1930 2000 4000 6000 3700 4550 2800 7100 5600
OP 90
R2
13 900 900 1600Ý1350 1660Ý1505 2050 4200 6350 1980 2300 4400 6800 3750 5100 3750 8100 6300
Control
Panel
105 15 1000 900 1600Ý1500 1660Ý1655 2050 4200 6350 2130 2300 4400 6800 3850 5450 4300 8600 6600
1000 1800Ý1500 1900Ý1670 2350 4800 7250 2180 2600 4900 7500 3900
Distribution Board 17 1150 6600 5100 11000 8700
(By others) 120 Note 6
1100 2000Ý1350 2100Ý1520 2550 5200 7850 2030 2800 5250 8300 3800
Machine Room Access Door (By others)
Min. 900 (W)Ý2000 (H)
1000 1800Ý1700 1900Ý1870 2350 4800 7250 2380 2600 4900 7500 4200
1100 2000Ý1500 2100Ý1670 2550 5200 7850 2180 2800 5250 8300 4000
X2
X1 A 2000Ý1750 2100Ý1920 2550 5200 7850 2430 2900 5400 8300 4300
Travel (TR)
R1 R1 24 1600 1100 8500 6800 13600 10400
Vent Fan (By others)
2150Ý1600 2250Ý1770 2700 5500 8300 2280 3000 5650 8700 4200
Beam (By others)
Notes : 1. Above hoistway dimensions are based on 15-storied buildings. For application to over 16-storied buildings,
Vent Grille (By others)
the hoistway dimensions shall be at least 5% larger considering the sloping of the hoistways.
Ent. Height (EH)
2. Above dimensions are based on center opening doors. For applicable dimensions with side opening doors, consult Hyundai.
CB
Y
B
3. When non-standard capacities and dimensions are required to meet the local code, consult Hyundai.
2100
CA 4. The capacity in persons is calculated at 65kg/person. (EN81=75kg/person)
5. Above dimensions are applied in case the door is standard. In case fire protection door that the clear opening is over 1000mm
is applied, hoistway size for 1 car should be applied above X1 dimension plus 100mm.
MY
6. In case of 120m/min and 150m/min, hoistway size is above plus 100mm, the machine room size is above plus 100mm.
OP OP
Vent Grille (By others)
R2 R2
Control Control R3 R4
Panel Panel
Receptacle Ladder Waterproof Finish
Distribution Board (By others) (By others) (By others)
(By others)
Y
B
CA
OP OP OP
MY
Vent Fan (By others)
R2 R2 R2
Vent Grille (By others)
4 5
PASSENGER ELEVATORS
Machine-Room-Less Elevatorsǖ60~150m/min
Plan of Hoistway & Machine Room (8~38 Person) Section of Hoistway Standard Dimensions (8~38 Person) (ۚ : mm)
Clear Control
Speed Capacity Opening Car Hoistway Motor M/C Room Reaction (kg) Pit Reaction (kg)
Persons
Speed Overhead Pit
Panel
(m/min) Persons kg OP CAÝCB AÝB X Y (kW) R1 R2 R3 R4 R5 R6 (m/min) (OH) (PP) (CP)(*)
Lighting 60 3.4 45, 60 3800 1500 530
(By others) X Lighting (By others) 90 8 550 800 1300Ý1100 1360Ý1255 2050 1700 5.1 4000 2100 1500 600 7000 1600 8~17 90 3900 1800 530
A
Hook (By others) 105 5.9 105 4000 2100 530
R4 R1 60 3.7 120 4300 2200 530
13~17
90 9 600 800 1300Ý1190 1360Ý1345 2050 1800 5.6 4100 2300 1600 600 7300 1600 150 4600 2400 530
CA Traction 105 6.5 45, 60 4200 1500 530
Machine
Top floor
(By others) 60 4.3 90 4300 1800 630
20~24 105 4500 2100 630
CB
90 10 700 800 1300Ý1300 1360Ý1455 2050 1800 6.5 4500 2300 1700 650 7800 1600
Y
Travel (TR)
Control
Control
Control
Control
Control
Control
Panel
Panel
Panel 1700Ý1570 2500 6100 3900 2200 900 11800 2500 200mm
Panel
Panel
Panel 150 2250 15.4
CP OP
3. The minimum hoistway dimensions are
Distribution Board
(By others)
60 7.1 shown on the above table. Therefore, some
(*) Receptacle
allowances should be made considering the
(By others) 90 10.6 6300 3400 2100 900 12500 2500
2600 2100 sloping of the hoistways.
Floor with control panel Ladder
105 17 1150 1000 1800Ý1400 1900Ý1570 12.4 4. When face to face arrangement is required,
(By others) 120 14.1 partitioning work for hoistway is required.
6600 4200 2300 900 14200 2700 (EN81)
Notes : 1. The lighting of hoistway should be 150 2650 2250 17.7 5. If the hoistway is glass, consult Hyundai as
installed less than 500mm from above
60 8.3 it needs to finish laminated glass. (EN81)
the ceiling of hoistway and within Lighting 6. When non-standard capacities and
500mm above the bottom of the pit. Pit Depth (PP) 90 2650 12.5 7700 4300 2500 1100 13900 3000
(By others) dimensions are required to meet the local
(By others) 105 20 1350 1000 1800Ý1600 1900Ý1770 2400 14.5
Waterproof Finish code, please consult Hyundai Elevator.
2. Machine room temperature should be
maintained below 40°C with ventilating (By others) 120 16.6
2680 8200 4600 2600 1200 16500 3100
fan and/or air conditioner (if necessary) 150 20.7
and humidity below 90%. R5 R6
60 9.9
90 2850 14.8 7900 4600 2600 1200 15200 3200
105 24 1600 1100 2000Ý1600 2100Ý1770 2450 17.2
120 19.7
2880 8300 4900 2700 1200 17800 3300
150 24.6
60 11.5
90 27 1750 1200 1600Ý2300 1700Ý2507 2480 2850 17.2 8600 4300 2900 1300 16700 2800
105 20.1
60 12.3
90 30 2000 1200 2100Ý1900 2200Ý2107 3000 2550 18.4 9100 4700 3100 1300 19800 3300
105 21.5
60 15.4
90 38 2500 1400 2200Ý2200 2300Ý2407 3300 3050 23 10300 5200 3300 1600 24000 3700
105 26.9
Notes : 1. When non-standard capacities and dimensions (including fire protection doors) are required to meet the local code, please
consult Hyundai.
2. The minimum hoistway dimensions are shown on the above table. Therefore, some allowances should be made considering
the sloping of the hoistways.
3. If the height of floor is over 11m, please consult Hyundai as to the needs for emergency exit.
4. Above dimensions are applied in case the door is standard. In case fire protection door that the clear opening is over
1000mm is applied, hoistway size for 1car should be applied above X1 dimension plus 100mm.
5. In case the emergency stop switch is applied to the counter weight, consult Hyundai.
6. When face to face arrangement is required, partitioning work for hoistway is required. (EN81)
6 7
PASSENGER ELEVATORS
Geared Elevatorsǖ60~105m/min
Plan of Hoistway & Machine Room Section of Hoistway Standard Dimensions & Reactions (Unit : mm)
Height (MH)
X1
M/C Room
(By others)
Cinder Persons kg OP CA Ý CB AÝB X1 X2 X3 Y MX1 MX2 MX3 MY R1 R2 R3 R4
A Concrete Min. 150
R1 (By others) 6 450 800 1400Ý 850 1460Ý1005 1800 3700 5600 1430 2000 4000 6000 3200 3600 2000 5200 4300
Vent Grille (By others)
R2 R1
8 550 800 1400Ý1030 1460Ý1185 1800 3700 5600 1610 2000 4000 6000 3400 4050 2250 5800 4700
9 600 800 1400Ý1130 1460Ý1285 1800 3700 5600 1710 2000 4000 6000 3500 4100 2450 6100 4900
Vent Fan (By others)
Overhead (OH)
CB
10 700 800 1400Ý1250 1460Ý1405 1800 3700 5600 1830 2000 4000 6000 3600 4200 2700 6600 5200
Y
60
B
CA
11 750 800 1400Ý1350 1460Ý1505 1800 3700 5600 1930 2000 4000 6000 3700 4550 2800 6900 5400
MY
13 900 900 1600Ý1350 1660Ý1505 2050 4200 6350 1980 2300 4400 6800 3750 5100 3750 7900 6100
OP
R2
90 15 1000 900 1600Ý1500 1660Ý1655 2050 4200 6350 2130 2300 4400 6800 3850 5450 4300 8400 6400
Control
Panel 1000 1800Ý1500 1900Ý1670 2350 4800 7250 2180 2600 4900 7500 3900
17 1150 6600 5100 10800 8500
1100 2000Ý1350 2100Ý1520 2550 5200 7850 2030 2800 5250 8300 3800
Total Height (TH)
Distribution Board 105 1000 1800Ý1700 1900Ý1870 2350 4800 7250 2380 2600 4900 7500 4200
(By others)
Machine Room Access Door (By others) 20 1350 7800 6000 11800 9100
Min. 900 (W)Ý2000 (H)
1100 2000Ý1500 2100Ý1670 2550 5200 7850 2180 2800 5250 8300 4000
Travel (TR)
2000Ý1750 2100Ý1920 2550 5200 7850 2430 2900 5400 8300 4300
24 1600 1100 8500 6800 13100 9900
2150Ý1600 2250Ý1770 2700 5500 8300 2280 3000 5650 8700 4200
Ent. Height (EH)
Notes : 1. Above hoistway dimensions are based on 15-storied buildings. For application to over 16-storied buildings,
the hoistway dimensions shall be at least 5% larger considering the sloping of the hoistways.
2100
2. Above dimensions are based on center opening doors. For applicable dimensions with side opening doors, consult Hyundai.
3. When non-standard capacities and dimensions are required to meet the local code, consult Hyundai.
4. The capacity in persons is calculated at 65kg/person. (EN81=75kg/person)
Pit Depth (PP)
5. Above dimensions are applied in case the door is standard. In case fire protection door that the clear opening is over 1000mm is applied,
hoistway size for 1 car should be applied above X1 dimension plus 100mm.
Note : Machine room temperature should be maintained below 40°C
with ventilating fan and/or air conditioner (if necessary) and
humidity below 90%.
Receptacle Ladder Waterproof Finish
(By others) (By others) (By others)
MX2 MX3
(Unit : mm)
X2 X3 Speed Overhead Pit M/C Room Height
X1 A X2 (m/min) (OH) (PP) (MH)
R1 R1
Vent Fan (By others)
X1
60 4600 1500 2200
Vent Fan (By others)
Min. 100
A
R1 R1 R1
Beam (By others)
90 4800 1800 2400
Vent Grille (By others)
(By others)
CB
Y
B
CB
Notes : 1. The minimum hoistway dimensions are shown on the above table. Therefore, some allowances
Y
B
OP
OP
OP
OP
OP
OP OP
OP
OP
OP
OP
OP OP
OP
OP
OP
OP
OP 3. The minimum machine room height should be 2800mm in case of the traction machine with double
MY
OP OP isolation pad.
R2 R2 R2
Vent Grille (By others)
R2 R2
Vent Grille (By others)
Control Control
Panel Panel Control Control Control
Panel Panel Panel
Distribution Board Distribution Board
(By others) (By others)
8 9
HIGH-SPEED/ULTRA-HIGH-SPEED ELEVATORS
Gearless Elevatorsǖ180~600m/min
Plan of Hoistway & Machine Room (In-Line Arrangement of 3 Units) Section of Hoistway Standard Dimensions & Reactions (Unit : mm)
Hook or Trolly Beam Clear Car Hoistway M/C Room M/C Room
MX3 (By others) Speed Capacity
X3
Opening Internal External 1Car 2Cars 3Cars Depth 1Car 2Cars 3Cars Depth Reaction (kg)
(m/min)
X2 Suspension
Persons kg OP CA Ý CB AÝB X1 X2 X3 Y MX1 MX2 MX3 MY R1 R2
M/C Room
Cinder Concrete
Height
(MH)
X1 Min. 150
13 900 900 1600Ý1350 1700Ý1520 2300 4550 6900 2150 2800 5500 7900 4500 12030 6630
Min. 200
A (By others)
(By others) 1000 1800Ý1500 1900Ý1670 2500 4950 7500 2350 3000 6100 8800 4700
17 1150 13080 7130
1100 2000Ý1350 2100Ý1520 2700 5350 8100 2200 3200 6250 9100 4500
CB
Overhead (OH)
CA
180
1000 1800Ý1700 1900Ý1870 2500 4950 7500 2550 3000 6100 8900 5000
OP OP OP 20 1350 14360 7650
MY
R2 R2 R2
1100 2000Ý1500 2100Ý1670 2700 5350 8100 2350 3200 6250 9100 4700
2000Ý1750 2100Ý1920 2700 5350 8100 2600 3200 6250 9100 5000
Vent Fan (By others)
Vent Grille (By others)
Travel (TR)
Machine Room Access Door (By others)
900 (W) X 2000 (H) 1000 1800Ý1500 1900Ý1670 5000 7550 2350 6100 8900 4900
17 1150 14100 8000
Entrance
1100 2000Ý1350 2100Ý1520 5400 8150 2200 6200 9000 4900
Height
2100
Note : Temperature should be maintained below 40°C and humidity 210
below 90%, with installation of a ventilating fan, ventilating grille, 240
and air conditioner (if necessary). Toxic gas or dust should not be generated. 1000 1800Ý1700 1900Ý1870 5000 7550 2550 6100 8800 5000
20 1350 15100 8050
1100 2000Ý1500 2100Ý1670 5400 8150 2350 6200 9000 5000
Receptacle Ladder Waterproof Finish 10 00 1800Ý1700 1900Ý1920 5100 7700 2650 6200 9100 6000
(By others) (By others) (By others) 20 1350 17800 13200
1100 2000Ý1500 2100Ý1720 5500 8300 2450 6200 9100 5900
300
Face-to-Face Arrangement 360
2000Ý1750 2100Ý1970 5500 8300 2650 6500 9100 6300
24 1600 1100 18100 13500
MX3 2150Ý1600 2250Ý1820 5800 8750 2500 6500 9400 6200
X3
X2 420 17 1150 1000 1800Ý1500 7800 2500 8900 6000
X1 480
A 20 1350 1100 2000Ý1500 8750 2500 9500 6300
Min. 200
Vent Fan (By others)
R1
540
R1 R1
600 24 1600 1100 2000Ý1750 8750 2750 9500 6300
Beam
Vent Grille (By others)
(By others) Notes : 1. The minimum hoistway dimensions are shown on the above table. Therefore, some allowances should be made considering the sloping of the hoistways.
MX2
X2 2. Above dimensions are based on center opening doors. For applicable dimensions with side opening doors, consult Hyundai.
CB
CA X1 A
Vent Fan (By others)
4. When non-standard capacities and dimensions are required to meet the local code, consult Hyundai.
R1 R1
5. The capacity in persons is calculated at 65kg/person. (EN81=75kg/person)
OP OP OP 6. Above dimensions are applied in case the door is standard. In case fire protection door that the clear opening is over 1000mm is applied, hoistway size for 1 car should be applied
Beam
Vent Grille (By others)
(By others)
Machine Room
R2 R2 R2
Access Door
3600 ~ 4000
OP OP OP CA (Unit : mm)
(By others)
MY
Speed Overhead Top Clearance Pit M/C Room Speed Overhead Top Clearance Pit M/C Room
Vent Grille (By others)
OP OP
(m/min) (OH) (TC) (PP) Height (MH) (m/min) (OH) (TC) (PP) Height (MH)
R2 R2
Y
Control Control
180 6000 2300 2700 2500 420 8500 4200 6000 3200
(By others)
Vent Fan
Panel Panel
Distribution Board (By others) 210 6400 2700 3200 2800 480 9500 5700 6400 3500
240 7100 3350 3850 2800 540 9750 5950 8800 3500
Min. 200
Notes : 1. The above table shows minimum figures. Therefore, some allowances should be made considering errors that may occur during construction.
2. Above dimensions are applied in case car height is 2800mm. In case car height is over 2800mm, overhead should be applied above dimension plus additional height.
10 11
OBSERVATION ELEVATORS
Gearless & Geared Elevatorsǖ60~105m/min
Plan of Hoistway & Machine Room Section of Hoistway Standard Dimensions & Reactions
(Unit : mm)
Height (MH)
(By others)
M/C Room
Glass Wall
(By others) Cinder 6 450 800 1400Ý850 1460Ý1060 2200Ý1400 2600Ý2900 5000 2700 6650 5750
Concrete Min. 150
(By others)
8 550 800 1400Ý1030 1460Ý1240 2200Ý1500 2600Ý3000 5350 3000 7300 6200
Vent Grille (By others) 9 600 800 1400Ý1130 1460Ý1340 2200Ý1600 2600Ý3100 5550 3100 7600 6400
R1
R2
B
Y
CB
60
Overhead (OH)
11 750 800 1400Ý1350 1460Ý1560 2200Ý1850 2600Ý3350 6100 3400 8500 7000
Machine Room
1-Side
MY
90
2100
Control
Panel
Distribution Board
17 1150 1000 1800Ý1500 1900Ý1710 2850Ý2000 3500Ý3500 8900 5300 12800 10500
24 1600 1100 2000Ý1750 2100Ý1960 3050Ý2250 3700Ý3750 9850 7050 15500 12300
8 550 800 1400Ý1030 1460Ý1240 2200Ý1500 2600Ý3000 5400 3050 7500 6400
Glass Enclosure
Min.
500
9 600 800 1400Ý1130 1460Ý1340 2200Ý1600 2600Ý3100 5600 3120 7800 6600
(By others)
10 700 800 1400Ý1250 1460Ý1460 2200Ý1750 2600Ý3200 5950 3350 8400 7000
11 750 800 1400Ý1350 1460Ý1560 2200Ý1850 2600Ý3350 6100 3450 8700 7200
Pit Depth (PP)
60
2-Side 90 13 900 900 1600Ý1350 1660Ý1560 2400Ý1850 3000Ý3350 6850 3750 9750 7950
Note : Machine room temperature should be maintained below 40°C Maintenance Deck Observation
(By others) 105
with ventilating fan and/or air conditioner (if necessary) and 15 1000 900 1600Ý1500 1660Ý1710 2400Ý2000 3000Ý3500 7150 3930 10350 8350
humidity below 90%.
Receptacle Ladder Waterproof Finish
(By others) (By others) (By others) 17 1150 1000 1800Ý1500 1900Ý1710 2850Ý2000 3500Ý3500 9000 5400 13000 10700
20 1350 1000 1800Ý1700 1900Ý1910 2850Ý2200 3500Ý3700 9100 6700 14250 11600
24 1600 1100 2000Ý1750 2100Ý1960 3050Ý2250 3700Ý3750 9950 7100 15700 12500
Notes : 1. Above dimensions are based on center opening doors. For applicable dimensions with side opening doors. Consult Hyundai.
2 Side Type MX 2. When non-standard capacities and dimensions are required to meet the local code, consult Hyundai.
X 3. The capacity in persons is calculated at 65kg/person. (EN81=75kg/person)
A 4. Above dimensions are applied in case the door is standard. In case fire protection door that the clear opening is over
Glass Wall 1000mm is applied, hoistway size for 1 car should be applied above X1 dimension plus 100mm.
(By others)
Vent Grille (By others)
(Unit : mm)
R1
R2
Y
CB
12 13
OBSERVATION ELEVATORS
Gearless & Geared Elevatorsǖ60~105m/min
Plan of Hoistway & Machine Room Section of Hoistway Plan of Hoistway & Machine Room Section of Hoistway
X2, MX2 Suspension Hook X2, MX2 Suspension Hook
(By others) (By others)
550 A 200 A 550
550 A 200 A 550
Glass Enclosure
(By others)
Height (MH)
Height (MH)
M/C Room
M/C Room
Cinder Glass Enclosure (By others) Cinder
Concrete Min. 150
Concrete Min. 150
(By others)
(By others)
R2
CB
Y
B
CB
Y
B
CA
R2
R1
R1
CA
S
R1
R1
Overhead (OH)
Overhead (OH)
MY
OP OP
OP OP
Ent. Height(EH)
2100
2100
Control Control
Vent Fan (By others)
Control Control
Vent Fan (By others)
Travel (TR)
Concrete (Min. 3600) or
Glass Enclosure
Glass Enclosure
Machine Room Access Door (By others) Machine Room Access Door (By others) 500
3 Side Type Min. 900 (W)Ý2100 (H) 500
Semicircle Type Min. 900 (W)Ý2100 (H)
(By others)
(By others)
Pit Depth (PP)
Notes : 1. The minimum hoistway dimensions are shown on the above table. Therefore, some Notes : 1. The minimum hoistway dimensions are shown on the above table. Therefore, some
allowances should be made considering the sloping of the hoistways. Note : Machine room temperature should be maintained allowances should be made considering the sloping of the hoistways. Note : Machine room temperature should be maintained
2. The minimum machine room height should be 2800mm in case of the traction below 40°C with ventilating fan and/or air conditioner 2. The minimum machine room height should be 2800mm in case of the traction below 40°C with ventilating fan and/or air conditioner
machine with double isolation pad. (if necessary) and humidity below 90%. machine with double isolation pad. (if necessary) and humidity below 90%.
3. Above dimentions are changeable according to the car exterior design. 3. Above dimentions are changeable according to the car exterior design.
11 750 800 1400Ý1400 1460Ý1610 2450 5100 2000 1200 2900 5100 3500 6150 3450 6900 8700 7150 11 750 800 1400Ý1480 1460Ý1690 2450 5100 2000 1200 2900 5100 3500 6180 3450 6900 8700 7150
13 900 900 1600Ý1450 1660Ý1660 2650 5500 2050 1350 3300 5500 3550 6900 3750 7500 9700 7900 13 900 900 1600Ý1500 1660Ý1710 2650 5500 2050 1350 3300 5500 3550 6930 3750 7500 9700 7900
60 60
15 1000 900 1600Ý1570 1660Ý1780 2650 5500 2200 1350 3300 5500 3700 7200 3950 7900 10300 8300 15 1000 900 1600Ý1650 1660Ý1860 2650 5500 2200 1350 3300 5500 3700 7220 3950 7900 10300 8300
90 90
17 1150 1000 1800Ý1580 1900Ý1790 2850 6100 2200 1600 3500 6100 3700 9100 5450 10900 13150 10900 17 1150 1000 1800Ý1650 1900Ý1860 2850 6100 2200 1600 3500 6100 3700 9100 5450 10900 13150 10900
105 105
20 1350 1000 1800Ý1800 1900Ý2010 2850 6100 2400 1600 3500 6100 3900 9150 6750 13500 14550 11850 20 1350 1000 1800Ý1900 1900Ý2110 2850 6100 2400 1600 3500 6100 3900 9150 6750 13500 14550 11850
24 1600 1100 1800Ý2000 1900Ý2210 2850 6100 2600 1600 3500 6100 4100 10000 7150 14300 16100 12900 24 1600 1100 1800Ý2130 1900Ý2340 2850 6100 2600 1600 3500 6100 4100 10050 7190 14380 16100 12900
Notes : 1. Above dimensions are based on center opening doors. For applicable dimensions with side opening doors, consult Hyundai. Notes : 1. Above dimensions are based on center opening doors. For applicable dimensions with side opening doors, consult Hyundai.
2. Above dimensions are applied in case the door is standard. In case fire protection door that the clear opening is over 1000mm is applied, 2. Above dimensions are applied in case the door is standard. In case fire protection door that the clear opening is over 1000mm is applied,
hoistway size for 1 car should be applied above X1 dimension plus 100mm. hoistway size for 1 car should be applied above X1 dimension plus 100mm.
3. Consult Hyundai if the capacity is 10 persons and less. 3. Consult Hyundai if the capacity is 10 persons and less.
14 15
OBSERVATION ELEVATORS
Machine-Room-Less Elevaotrsǖ60 ~105m/min
Plan of Hoistway & Machine Room Section of Hoistway Standard Dimensions & Reactions
(Unit : mm)
60
1-Side 900 1500Ý1400 1560Ý1610 2300Ý1900
90 13 900 5050 2250 2100 1000 9750 7950
60
Y
B
Travel (TR)
Lighting 15 1000 900 1600Ý1400 1760Ý1610 2400Ý1950 5750 2400 2500 1100 10550 8550
R3 R2 (By others)
OP
17 1150 1000 1800Ý1400 1960Ý1610 2700Ý2150 6650 3500 3150 1150 13200 10900
Receptacle
(By others) 20 1350 1000 1800Ý1600 1960Ý1810 2700Ý2450 7730 4850 3500 1400 14450 11800
Floor without control panel
Ladder 24 1600 1100 2000Ý1700 2160Ý1910 2900Ý2500 8250 5000 3650 1500 15900 12700
(By others)
Notes : 1. When non-standard capacities and dimensions (including fire protection doors) are required to meet the local code, please consult Hyundai.
2. The minimum hoistway dimensions are shown on the above table. Therefore, some allowances should be made considering the sloping of the hoistways.
3. The capacity in persons is calculated at 65kg / person. (EN81=75kg / person)
Lighting
4. If the height of floor is over 11m, please consult Hyundai as to the needs for emergency exit.
Pit Depth (PP)
(By others) 5. Above dimensions are applied in case the door is standard. In case fire protection door that the clear opening is over 1000mm is applied, hoistway size for
Waterproof Finish 1 car should be applied above X1 dimension plus 100mm.
(By others) 6. In case the emergency stop switch is applied to the counter weight, consult Hyundai.
7. If the car is heavier than 1000kg because of interior decoration in case of elevator for 15 persons (1000kg), consult Hyundai.
R5 R6
Notes : 1. Above dimensions are applied for car height of 2500mm (car internal height is
Distribution Board Speed Overhead Pit Control Panel 2300mm), For other applicable dimensions, consult Hyundai.
Persons
(By others) (m/min) (OH) (PP) (CP)(*) 2. The minimum hoistway dimensions are shown on the above table. Therefore, some
allowances should be made considering the sloping of the hoistways.
60 4250 1750
3. When face to face arrangement is required, partitioning work for hoistway is
Control 8 ~ 15 90 4350 1800 530 required. (EN81)
Panel 4. If the hoistway is glass, consult Hyundai as it needs to finish joining glass. (EN81)
OP CP 105 4400 2000 5. The lighting should be installed at the top and bottom of hoistway.
(*) 6. When non-standard capacities and dimensions are required to meet the local code,
60 4250 1800 please consult Hyundai Elevator.
17 90 4350 1900 530
Floor with control panel
105 4400 2000
60 4850 1800 530
Note : The lighting of hoistway should be installed less than 20 ~24 90 5000 1900 630
500mm from above the ceiling of hoistway and within
500mm above the bottom of the pit. (By others) 105 5000 2100 630
16 17
GLASS WALLED ELEVATORS
Gearless & Geared / MRL Elevatorsǖ45 ~105m/min
Plan of Hoistway & Machine Room Section of Hoistway Standard Dimensions & ReactionsɆGearless & Geared Elevators (Unit : mm)
CA 24 1600 1100 2000Ý1750 2160Ý1960 3090Ý2250 3800Ý3750 10020 7190 16800 13600
R1
R2
CB
Notes : 1. The machine room reactions are changeable according to the size of hoistway and
Speed (m/min) Overhead (OH) Pit (PP) M/C Room Height (MH) center of car weight.
MY
2. The same dimension of passenger elevators apply to the others except the above.
Machine Room
45 4500 1500 2200 3. For NDFL-01 (Frameless Glass-walled elevators) type, consult Hyundai Elevator
since hoistway dimension and machine room reactions for NDFL-01 type are
Travel (TR)
Floor without control panel Standard Dimensions & ReactionsɆMRL Elevators (Machine-Room-Less) (Unit : mm)
Receptacle
Clear Car Pit
(By others) Speed Capacity Hoistway M/C Room Reaction (kg) Reaction (kg)
Type Opening Internal External
Ladder
(m/min)
Persons kg OP CA Ý CB AÝB XÝY R1 R2 R3 R4 R5 R6
(By others)
8 550 800 1300Ý1100 1460Ý1310 2130Ý1750 4295 1870 660 1960 8150 7050
9 600 800 1300Ý1190 1460Ý1400 2130Ý1800 4515 1910 740 2010 8500 7300
MRL Gallery Window Lighting Lighting 10 700 800 1300Ý1300 1460Ý1510 2130Ý1850 4820 2030 840 2100 9050 7650
Pit Depth (PP)
Speed (m/min) Persons Overhead (OH) Pit (PP) Speed (m/min) Persons Overhead (OH) Pit (PP)
CB
Control
Panel
OP CP
Max.15 4200 1500 45 4850
45 / 60 1600
R4 R2
(*) 17 4200 1600 60 4850
20 / 24
OP
Floor with control panel 90 4300 1800 90 5000 1800
Max.17
105 4400 2000 105 5000 2100
Floor without control panel Note : The lighting of hoistway should be installed less than Notes : 1. The machine room reactions are changeable according to the size of hoistway and center of car weight.
500mm from above the ceiling of hoistway and within 2. The same dimension of passenger elevators apply to the others except the above.
500mm above the bottom of the pit. (By others) 3. For NDFL-01 (Frameless Glass-walled elevators) type, consult Hyundai Elevator since hoistway dimension
and machine room reactions for NDFL-01 type are changeable under different conditions.
18 19
FREIGHT ELEVATORS
General Type (2S, 2U, 3U)
Plan of Hoistway & Machine Room Section of Hoistway Standard Dimensions & Reactions (Unit : mm)
MX
Entrance Car Hoistway M/C Room Buffer
Speed Door M/C Room Reaction (kg) Reaction (kg)
Model Internal External
X
(m/min) Opening WidthÝHeight Entrance XÝY
Overhead (MXÝMY)
A (OPÝEH) Type CA Ý CB AÝB (OH) R1 R2 R3 R4
Type
Suspension Hook 30 Standard 1800Ý1857 2500Ý2150
(By others)
F0750-2S 45 2S 1100Ý2100 1700Ý1650 4800 2800Ý3200 6200 4100 5000 4300
Height (MH)
M/C Room
Double
1800Ý1989 2500Ý2320
Cinder
60
Vent Fan
CB
B
Y
Overhead (OH)
CA
Double
60 Entrance 2200Ý2876 3000Ý3250
Min. 900 (W)Ý2000 (H)
Access Door (By others)
Double
60 Entrance 2400Ý3076 3300Ý3450
OP 2300Ý2700
Distribution Board (By others) 30 Standard 2400Ý2898 3300Ý3250
F2000-2U 45 2U 2300Ý2100 4600 3800Ý4200 13300 8800 11400 9400
Double
2400Ý3016 3300Ý3490
Total Height (TH)
60 Entrance
2-PANEL SIDE-OPENING DOORS (2S) 30 Standard 2600Ý3228 3500Ý3600
F2500-2S 45 2S 1800Ý2100 4800 4000Ý4400 15100 10000 13200 10700
Note : Temperatures should be maintained below 40°C with ventilating Double
(60) 2600Ý3376 3500Ý3750
Travel (TR)
fan and/or air conditioner (if necessary) and humidity below 90%. Entrance
2500Ý3000
30 Standard 2600Ý3198 3500Ý3600
F2500-2U 45 2U 2500Ý2100 4600 4000Ý4400 15100 10000 13200 10700
Double
(60) Entrance 2600Ý3316 3500Ý3800
Ent. Height (EH)
45 Double
Entrance 2800Ý3616 3700Ý4100
200
50 50
F3500-2U 2U 2800Ý2500 2800Ý3800 5000 4300Ý5200 21700 14500 19000 15500
Min. 300 Min. 650
45 Double
Entrance 3020Ý4116 4050Ý4600
R3 R4
Receptacle Ladder Waterproof Finish
2-PANEL UP-SLIDING DOORS (2U) (By others) (By others) (By others) 25 Standard 3220Ý4758 4250Ý5250
Minimum floor height : Opening heightÝ3 / 2 + 700mm F4000-3U 3U 3000Ý2800 3000Ý4500 5300 4500Ý5900 32500 21700 28700 23700
30 Double
Minimum entrance height : 2100mm Entrance 3220Ý4936 4250Ý5520
Notes : 1. Please consult Hyundai when the loading capacity is over 5000kg or the car is non-standard size.
2. The loading capacity should be over 250kg/m2 minimally.
30
3. The actual reaction may slightly differ from above dimensions in line with machine beam position.
250
Wall+Finished
50 OP 50
Min. 650 Min. 300 (Unit : mm)
20 21
FREIGHT ELEVATORS AUTOMOBILE ELEVATORS
Hydraulic Type (2S, 2U, 3U) General Type (2U, 3U)
Plan of Hoistway & Machine Room Section of Hoistway Plan of Hoistway & Machine Room Section of Hoistway
Suspension Hook (By others)
X X
Min. 300 A Min. 650 Suspension Hook
Height (MH)
600 A
M/C Room
(By others)
Cinder
Overhead (OH)
Concrete Min. 150
(By others)
OPB
CB
Overhead (OH)
Distribution Board
R2
R1 R2 (Hydraulic hose)
R1
Travel (TR)
Total Height (TH)
Y
Min 900 (W)Ý2000 (H) [By others]
B
Y
B
CB
Power Unit
MY
CA
Control
Machine Room
Panel
Access Door
200 30
[By others]
200
200
200
200
200
Vent Grille
200 30
Travel (TR)
Min. 650 Min. 300
MX
1800
maintained below 40°C with
ventilating fan and/or
30
25
130
are optional.
R2
Wall+Finished
MY
Min. 650 Min. 300
Machine Room
R1
Minimum floor height : Opening Height X 4/3+750mm
Minimum entrance height : 2100mm Control
Panel
30
Distribution Board (By others)
Notes : 1. Consult Hyundai if the actual size is less than the above minimum floor height.
250
2. The left and right minimum size should be 650mm and 300mm respectively for the
installation of driving part. (Unit : mm)
50 OP 50
Wall+Finished
(Unit : mm) Speed Overhead Pit M/C Room Height
Notes : 1. Temperatures should be maintained below 40°Cwith ventilating fan and/
(m/min) (OH) (PP) (MH)
Speed Ent. Height Overhead Pit M/C Room Height Travel 3-PANEL UP-SLIDING DOORS (3U)
(m/min) (EH) (OH) (PP) (MH) (TR)
or air conditioner (if necessary) and humidity below 90%. 30 / 45 4400 1200 2400
2. The above are minimum size. Minimum floor height : Opening heightÝ4 / 3 + 750mm
20 / 30 / 45 2100 4100 1400 2000 20m 3. The overhead height can be varied in line with entrance height and door type. Note : The above are minimum size.
Minimum entrance height : 1800mm
4. Consult Hyundai if the travel height is 20m or more.
Note : Consult Hyundai if the dimensions are less than the minimum.
Notes : 1. Please consult Hyundai when the loading capacity is over 5000kg or the car is non-standard size. A2500-3UD 2750 2750Ý6300 2850Ý6300 3700Ý6800 3850Ý6800 22500 12500
2. The loading capacity should be over 250kg/m2 minimally.
3. The actual reaction may slightly differ from above dimensions in line with machine beam position. Notes : 1. The car external size can be varied in line with entrance type.
4. Above dimensions are based on up-sliding door available for 2-panel side-opening (2S) doors of same capacity. 2. When non-standard capacities and dimensions are required, consult Hyundai.
3. The car door is applied in BS code region.
22 23
HOSPITAL BED ELEVATORS TYPICAL ENTRANCE LAYOUTS
General Type (2S, 2SD) Standard/Optional
Plan of Hoistway & Machine Room Section of Hoistway Entrance Structural Opening of Entrance
MX In case of Boxless Type Buttons and Fire man’s Switch
X
Suspension Hook (By others)
30
Height (MH)
M/C Room
A Wiring Inlet :͚50
Cinder Concrete (By others)
Min. 150 150
700
Concrete Opening : 2200
Steel Bar for
Fixing Jamb
500
͚9Ý6EA (By others)
others)
700
Overhead (OH)
700
R1
1000
͚9Ý6EA (By others)
1050
Clear
700
Opening (OP) Concrete Opening
700
30
OP+140
R2
CA Finished
Floor Level
MY
OP
Travel (TR)
30
Control Wiring Inlet :͚50
Panel
(By others)
Ent. Height (EH)
Distribution Board
(By others)
700
2100
700
Steel Bar for
HB With HPI
700
500
700
Steel Bar for 80
Receptacle Ladder Waterproof Finish Fixing Jamb
(Unit : mm)
1000
(By others) (By others) (By others) Clear ͚9Ý6 EA (By others)
1000
30 Opening (OP)
700
Speed Overhead Pit M/C Room Height
700
Concrete Opening
(m/min) (OH) (PP) (MH) OP+300
Finished
30/45 4400 1200 Notes : 1. Machine Room temperature should be maintained below Floor Level
40°C with ventilating fan and/or air conditioner, if necessary, (By others) Concrete Opening Finished Floor Level
60 4600 1500 and humidity below 90%. OP+300 (By others)
2400 2. In case of special hoistway, machine room height may be JP100 Type (Optional)
90 4800 1800 higher than above size.
105 5000 2100 3. Above is minimum size.
4. The minimum machine room height should be 2800mm in
case of the traction machine with double isolation pad.
30
(Unit : mm)
Clear Car Hitch Beam Transom Panel
Hoistway M/C Room
Type Model Opening Internal External Reaction (kg)
Hall Position Wiring Inlet :͚50
OP CAÝCB AÝB XÝY MXÝMY R1 R2 Steel Bar for
Indicator Fixing Jamb Steel Bar for (By others)
B1350-2S30, 45 Emergency ͚9Ý6EA (By others) Fixing Jamb
250
1100 1300Ý2300 1400Ý2507 2100Ý2850 2300Ý3500 10500 8500 Call Switch ͚9Ý6EA (By others)
B1350-2S60
700
Concrete Opening:JH+50
(For emergency 150
Concrete Opening:JH+50
700
Standard
Jamb Height (JH)
floor is applied)
B1600-2S60 11500 9500
300
B1750-2S30~60 1200 1600Ý2300 1700Ý2507 2400Ý2850 2850Ý4000 HB
700
700
B1350-2SD30, 45
1900
1650
1100 1300Ý2300 1400Ý2634 2300Ý3000 2300Ý3500 10500 8500
B1350-2SD60 80
Double
B1600-2SD30, 45
1000
1000
Entrance Clear
Type 1200 1500Ý2300 1600Ý2634 2500Ý3000 2750Ý4000 30 Opening (OP) Concrete Opening Concrete Opening
700
B1600-2SD60 11500 9500
700
OP+300 OP+300
B1750-2SD30~60 1200 1600Ý2300 1700Ý2634 2600Ý3000 2850Ý4000
Finished Floor Level
Notes : 1. When non-standard capacities and dimensions are required, consult Hyundai.
(By others)
2. Above dimension are applied in case the door is standard. In case fire protection door is applied, hoistway size for 1 car should be applied above X dimension plus 100mm.
3. Consult Hyundai in case the code applied. JP200 Type (Optional)
24 25
TYPICAL ENTRANCE LAYOUTS TYPICAL ENTRANCE LAYOUTS
Only for Floor with Control Panel of the Machine-Room-Less Elevators 2-Panel Up-Sliding Doors (2U) / 4-Panel Center-Opening Doors (2CO)
500
Hall Button 150
with Indicator Indicator lamp
50
250
150
700
Steel Bar for
Fixing Jambs
͚9Ý6EA (By others)
500
Entrance Height (EH) : 2100
500
Entrance Height(EH)
Steel Bar for
Jamb Height (JH)
500
Hall Button
Concrete Opening
with Indicator Fixing Jambs
UP ͚9Ý6EA
EH+100
700
(By others)
500
1100
500
1000
CP Clear Opening (OP) 30 700 Concrete Opening
(*) Clear Opening Clear Opening
+ CP + 100 + 100 Finished
Finished Floor Level 2 2
Floor Level
(By others) (By others)
Clear Opening (OP) Concrete Opening (OP)
OP+200
Transom Panel
- OF CAR
D
Plan of Entrance Section of Entrance
Position
Indicator
200
100
700
(*)
Finished Clear
Clear Opening
Opening
Clear Opening ClearOpening
Clear
Clear
Clear Opening
Opening
Opening
Opening
Floor Level + CP + 100 +100
2 222222
(By others)
35
Plan of Entrance
(Unit : mm)
Width of 200
Persons Speed(m/min)
Control Panel(CP)(*)
8~17 Under 105 530
60 530
20, 24 90 630
105 630
26 27
TYPICAL ENTRANCE LAYOUTS
2-Panel Center-Opening Doors (CO) 2 Pannel Side-Opening Doors (2S)
130
90
Jamb Width
50
Jamb Width
Thickness
Wall
100
100
Wall Finish
Thickness
30 30
Jamb
Jamb
Jamb
Jamb Width
JambWidth
Width
Width
Width
90
130
Jamb Width
Thickness
Wall
Wall Finish
Thickness
50
50
30 (180)
Hall 150 Clear Opening (OP) 150
150 Clear Opening (OP) 150
Button
Note : The above layout is for left side opening. Right side opening doors are available, if requested.
50
50
50
50
50
50
Ceiling Line
Upper Upper Ceiling
100
100
10 10 10 10
Jamb Height (JH)
Jamb Width Jamb Width Jamb Width Jamb Width Jamb Width Jamb Width
50
50
50
50
50
50
JP100 Type JP200 Type JP200 Type JP100 Type JP200 Type JP200 Type
(with upper frame) (without upper frame) (with upper frame) (without upper frame)
28 29
NEW WORLD CLASS ESCALATORS(30Á
) NEW WORLD CLASS ESCALATORS (35Á
)
NW-BT, NW-BB NW-BT, NW-BB
C 1.732H (note 2) B
(note 1) Floor Opening AA
D (note 4) Min. 2500
50 Soffit Guard 50
Floor Opening Enclosures (By Others)
1070
(By Others)
793
Working R1
Head ROOM
Min. 2300
Point
908
Wiring Inlet 50 Soffit Guard
950
1070
793
(note 2) F (By Others) (By Others) R1
Working
HEAD ROOM
R4 Point
Min. 2300
(note 4) Min. 2500
H = Rise
E
968
Wiring Inlet
950
(note 4) Min. 2500 1490 (note 3) 2522 (By Others)
H = Rise
R3 Intermediate
Support
937
1070
937
R2 Working
Point 35°
L3 L1
Min. 1170
G
1070
R2 Working
J Point
L2 2358
Model QÍty of
B C D E F G J
(Inclination) Flat Step Min. 4500
Notes : 1. AA = 1.732 Ý H + B + C + 100
When maximum floor opening exceeds AA=14,962mm, intermediate NW-BT 2 2560 2230 1820 1490 2511 2118 4500
support(s) are required. Consult Hyundai for the intermediate support data. NW-BB 3 2967 2637 2227 1897 2918 2525 4910 Notes : 1. AA = 1.428 Ý H + 2650 + 2230 + 100
2. In case inverter system is applied, dimension B, F shall increase 500mm. When maximum floor opening exceeds AA=14,230mm, intermediate support(s) are
(800Type, 1000Type : increase 700mm) required. Consult Hyundai for the intermediate support data.
3. When vertical rise is over 6000mm, 3-flat step is applied.
4. Dimension between the end of handrail to the wall ; Min. 2500mm
Section Dimensions (Unit : mm)
2. Q’ty of flat step : 2
3. In case inverter system is applied, dimension 2650, 2522 shall increase 500mm.
5. Dimensions are based on EN115. (800Type, 1000Type : increase 700mm)
6. Vertical Rise H 10.5m. Type NW800 NW1000 NW1200 4. Dimension between the end of handrail to the wall ; Min. 2500mm
W1 612 813 1014 5. Dimensions are based on EN115.
6. Vertical Rise H 6m.
W2 855 1056 1257
W3 1150 1350 1550
W4 1100 1300 1500
W5 1250 1450 1650
11(Shim)
Enclosure
11 (Shim)
Intermediate Support
W2 855 1056 1257
90
90
(By Others)
R1 0.65H + 2300 0.36L1 + 900 0.36L1 + 1100 0.36L1 + 1100
150
150
935
R2 0.65H + 1600 0.36L2 + 300 0.36L2 + 400 0.36L2 + 450 W3 1150 1350 1550
L200×200×20 R3 - 0.36(L1 + L2) + 450 0.36(L1 + L2) + 700 0.36(L2 + L3) + 250 L200×200×20 W4 1100 1300 1500
R4 - - - 0.36(L1 + L3) + 600 W5 1250 1450 1650
50 50 Type NW1000 50 50
w3
Rise H (mm) H 6000 5000 H 7600 7600 H 10500
w2 Number of
w1 Intermediate Support - 1 1 2
R1 0.72H + 2600 0.41L1 + 900 0.41L1 + 1100 0.41L1 + 1100 w4 Reactions (Unit : kg)
Typical Steel Support Floor Opening
Enclosure R2 0.72H + 1900 0.41L2 + 300 0.41L2 + 400 0.41L2 + 450
Typical Steel Support W5 Vertical Rise
(By Others) R3 - 0.41(L1 + L2) + 450 0.41(L1 + L2) + 700 0.41(L2 + L3) + 250
Reactions ML800 ML1000 ML1200
Top of Finish Floor
Min. 200
Top of Finish Floor
Min. 200 H(mm)
935
3000
11(Shim)
Type NW1200
150
90
90
150
30 31
MILLENNIUM ESCALATORS(30Á
) MILLENNIUM ESCALATORS (35Á
)
ML-BT, ML-BB ML-BT, ML-BB
C 1.732H (note 2) B
(note 1) Floor Opening AA
D (note 4) Min. 2500
50 Soffit Guard 50
R1 Floor Opening Enclosures (By Others)
(By Others)
793
1000
Head Room Working
Min. 2300 Point
908
Wiring Inlet 50 Soffit Guard
950
1000
793
(note 2) F (By Others) (By Others) R1
Working
Min. 2100
R4 Point
(note 4) Min. 2500
H = Rise
E
968
Wiring Inlet
950
(note 4) Min. 2500 1498 (note 3) 2139 (By Others)
H = Rise
R3 Intermediate
Support
937
1000
937
R2 Working
Point 35°
L3 L1
Min. 1100
G
1000
R2 Working
J Point
L2 Model QÍty of Vertical Rise H Speed B C D E F G J
(Inclination) Flat Step (mm) 2316
2 H 6000 2286 2080 1695 1490 2116 2250 4230 Min. 4000
Notes : 1. AA = 1.732H + B + C + 100 ML-BT 6000ƖH 7600 30 2693 2487 2102 1897 2523 2657 4640 Notes : 1. AA = 1.428Ý H + 2367 (2767) + 2088 + 100
2. In case inverter system is applied, B, F shall increase 500mm. 2. Q'ty of flat step : 2
ML-BB 3 7600ƖH 10500 2876 2606 2237 1967 2707 2777 4750
(800Type, 1000Type : increase 700mm) 3. In case inverter system is applied, 2367, 2139 shall increase 500mm.
3. When vertical rise is over 6000mm, 3-flat step is applied. (30°) 3476 2556 2236 1966 3306 2727 4720 (800Type, 1000Type : increase 700mm)
H 6000 30 ~ 40
4. Dimension between the end of handrail to the wall ; Min. 2500mm 4 3882 2962 2642 2372 3712 3133 5120 4. Dimension between the end of handrail to the wall ; Min. 2500mm
5. If EN115 is applied, consult Hyundai. 5. If EN115 is applied, consult Hyundai.
6. Vertical Rise H 10.5m. 6. Vertical Rise H 6m.
11(Shim)
(By Others)
W2 855 1056 1257
90
Reactions
Min. 150
936
90
(Unit : kg) W3 1148 1349 1550
L200×200×20
Type ML800 W4 1098 1299 1500
Base Plate Rise H (mm) H 6000 5000 H 7600 7600 H 10500 L200Ý200Ý20 W5 1248 1449 1650
150Ý19 Number of Base Plate
Intermediate Support 1 1 2 150Ý19
50 50
w3 R1 0.66H + 2600 0.37L1 + 900 0.37L1 + 1200 0.37L1 + 1250
w2 50 50
R2 0.66H + 2000 0.37L2 + 350 0.37L2 + 500 0.37L2 + 450
w1
R3 0.37(L1 + L2) + 600 0.37(L1 + L2) + 850 0.37(L2 + L3) + 400 w4 Reactions (Unit : kg)
Typical Steel Support Floor Opening
Enclosure R4 0.37(L1 + L3) + 700
w5
Vertical Rise
Top of Finish Floor
Min. 200 (By Others) Type ML1000 Typical Steel Support H(mm)
Reactions ML800 ML1000 ML1200
936
R2
Min. 150
90
L200×200×20 R3 0.42(L1 + L2) + 600 0.42(L1 + L2) + 850 0.42(L2 + L3) + 400 Note : When vertical rise is over 6000mm or AA is over 14835mm, consult
Hyundai for reactions data.
50 50 R4 0.42(L1 + L3) + 700
L200Ý200Ý20
Reinforced Plate
w4 Type ML1200
(By Others) 50 50
W5 Rise H (mm) H 6000 5000 H 7600 7600 H 10500 Reinforced Plate
Number of
Intermediate Support - 1 1 2 (By Others)
Notes : 1. When maximum floor opening exceeds
AA=14,835mm, intermediate support(s) R1 0.79H + 3200 0.47L1 + 1000 0.47L1 + 1300 0.47L1 + 1350
are required. Consult Hyundai for the R2 0.79H + 2600 0.47L2 + 350 0.47L2 + 500 0.47L2 + 500 Notes : 1. When maximum floor opening exceeds AA=14,835mm,
intermediate support data. intermediate support(s) are required, Consult Hyundai
2. Consult Hyundai if the isolation pad is R3 0.47(L1 + L2) + 650 0.47(L1 + L2) + 900 0.47(L2 + L3) + 400 for the intermediate support data.
applied. R4 0.47(L1 + L3) + 750 2. Consult Hyundai if the isolation pad is applied.
32 33
H-SERIES ESCALATORS H-SERIES ESCALATORS
HA-BT, HA-BB HD-BT, HD-BB
937
"A"
Floor Opening Enclosures (By Others)
937
1280
Head Room Working
Soffit Guard Point
Min. 2300
843
1400
(By Others) Working R1 R1
"B"
Min. 2300
Point Wiring Inlet
0
100
(By Others)
(note 5) H = Rise
(note 2) Min. 2500 2150 (note 3) 4342 Intermediate Support
793
(By Other)
Min. 290
R4
908
"B"
0
110 Wiring Inlet
H = Rise
2241
(By Others)
(note 1)
Intermediate
R3 Support
937
"A" "B"
937
30°
(By Others)
30°
Min. 1400
1300
1210
Working
1200
R2 Working Point R3 R4 R5
Point
L3 L1 R2 Min. 5100
3065
L 2 (Max.12000) L 3 (Max.12000) L 4 (Max.12000) L 1 (Max.12000)
Min. 5700
L2
Notes : 1. N : Number of intermediate supports
Max. distance between intermediate supports is 12000mm
AA = 1.732Ý H + 4014 + 2884 + 100
Notes : 1. N : Number of intermediate supports
2. Dimension between the end of handrail to the wall : Min. 2500mm
Max. distance between intermediate supports is 12000mm
AA = 1.732 Ý H + 4464 + 4342 + 100 3. 4014 is a dimension of inverter applied system.
2. Dimension between the end of handrail to the wall : Min. 2500mm 4. Dimensions are based on EN115.
3. 4464, 4342 are dimensions of inverter applied system. 5. Vertical Rise 15m < H 20m.
(800Type : 4664, 4542)
4. If EN115 is applied, consult Hyundai.
5. Vertical Rise 10.5m < H 15m.
w5
Typical Concrete Support
w5 Section Dimensions (Unit : mm) Typical Concrete Support w3
Section Dimensions (Unit : mm)
w3
w2 Type HA800 HA1000 HA1200 Min. 200
w2 Type HD800 HD1000 HD1200
Min. 200 Floor Opening Top of Finish Floor
Top of Finish Floor w1 w1
(By Others) Enclosure W1 594 813 1014 (By Others) W1 612 813 1014
11 (Shim)
(By Others)
11(Shim)
Min. 210
Min. 210
936
90
90
50 50 50 50
w4
w 4 + 200
Reactions (Unit : kg)
Typical Steel Support Typical Steel Support
Type HA800 HA1000 HA1200
Min. 200 Min. 200
Top of Finish Floor Vertical Rise Top of Finish Floor
(By Others) 10500 H 15000 (By Others)
H (mm)
11 (Shim)
11(Shim)
Min. 210
90
90
34 35
MODULAR ESCALATORS MOVING WALKS
M-BB HORIZONTAL TYPENPM-BT
5FOTJPOTUBUJPO %SJWFTUBUJPO
Floor Opening AA = (L)
(note 1) Floor Opening AA
937
937
"A"
"A"
719
"B" "B" "B"
1100
Floor Opening Enclosures (By Others)
1200
1200
1100
Working Working
R2 Point Point R1
Intermediate Support Beam
Soffit Guard R3 R4~R(n-1) Rn
Wiring Inlet (By Other)
(By Others)
1073
Working Min. 3000 (note 1) Min. 4000
R1
Min. 2300
Point
(note 3) 3427
699
Wiring Inlet
H=Rise
0
803
(By Others)
106
L 2 (Max.7000) L 3 ~L (n-1) (Max.8000) L n (Max.8000) L 1 (Max.7000)
(note 2) Min. 2500 2074
(note 1) Notes : 1. In case inverter system is applied, dim. 2190, 4000 shall increase 500mm.
400R Intermediate (1000Type : increase 700mm)
933
Support
30Á (By Others) 2. Dimension between the end of handrail to the wall : Min. 2500mm
3. Dimensions are based on EN115.
Min. 1173
Working
1073
R2 Point
w5 w5
Typical Concrete Support w3 Section Dimensions (Unit : mm) Typical Concrete Support w3 Section Dimensions (Unit : mm)
w2 w2
Min. 200 Floor Opening Type M800 M1200 Type NPM1000 NPM1200
Top of Finish Floor w1 Min. 200
(By Others)
Enclosure Top of Finish Floor w1
(By Others)
(By Others) W1 594 1014 W1 814 1014
11(Shim)
11(Shim)
933
Min. 150
Min. 150
90
90
W3 1275 1695 W3 1350 1550
W4 1244 1664 W4 1300 1500
L200Ý200Ý20 L200×200×20
Base Plate W5 1375 1795 Base Plate W5 1500 1700
150Ý19 150Ý19
w4 w4
50 50 50 50
w 4 + 200
w5
Reactions (Unit : kg)
11 (Shim)
Min. 150
90
AA+0.1 AA+0.1
L200Ý200Ý20
L200×200×20
50 50
50 50
Reinforced Plate
(By Others) Reinforced Plate
(By Others)
Note : Consult Hyundai if the isolation pad is applied. Note : Consult Hyundai if the isolation pad is applied.
36 37
MOVING WALKS
HORIZONTAL & INCLINED TYPENPM-BT WORKS TO BE DONE BY OTHER CONTRACTORS
The following works are not included in the elevator contract, and shall be done by other contractors
Floor Opening AA (L) = 4.70465 × H + 5187
in accordance with the Hyundai Elevator's drawings and the applicable codes and regulations.
50 1787 4.70465H (note 1) 3300 50
2643
The reference rules shown are from Code ANSI.
Floor Opening Enclosures (By Others)
"A"
940
Head Room
Building Work Electrical Work
1100
Working
Min. 2300
Point
1129
Hoistway Hoistway
790
Height (H)
"B" R1
Wiring Inlet
719
(By Others) 1. Clear, plumb hoistway with fire resistant hatch walls as required by the applicable 1. Light outlet for each elevator, in center of hoistway (or in machine room) as
"A" Intermediate Support code. (Rule 100.1a) indicated by Hyundai Elevator Company.
940
"B"
12°
(By Others)
2. 75° bevel guards on all projections, recesses, or setbacks over 50mm except on 2. Convenience outlet and light fixture in pit with switch located adjacent to the
1200
1100
Working side used for loading or unloading. (Rule 100.6) access door. (Rule 106.1e)
Point
3. Venting of the hoistway as required by the applicable code or responsible 3. Wiring and piping work of emergency bell, interphone, etc. Outside the hoistway
R2
authority. (Rule 100.4) and the machine room.
Min. 6000 R3 R4
4. Supports for rail brackets at each floor, roof, and machine room. (Rule 200.9)
Maximum allowable vertical spacing of rail supports without backing. (Rule 200.4
L 2 (Max.10000) L 3 (Max.10000) L 1 (Max.10000)
and 301.1) Divider beams 100mm between hoistway at each floor and roof, for Machine Room
Notes : 1. In case inverter system is applied, dim. 3300 shall increase 500mm. guide rail bracket supports. (Rule 200.4, 200.9 and 301.1) 4. Lighting, convenience outlets, ventilation, heating of machine room, and
(1000Type : increase 700mm) 5. Recesses supports and patching as required to accommodate hall button boxes, machinery space. (Rule 101.5)
2. Dimension between the end of handrail to the wall : Min. 2500mm
3. Dimensions are based on EN115. signal fixtures, etc. 5. Temperature should be maintained below 40 ° by a ventilating fan and/or air
6. All barricades either outside elevator hoistways or between inside hoistways as conditioner, if necessary, and humidity below 90%.
required. 6. A fused disconnect switch or circuit breaker for each elevator and light switch
Reactions (L1 ~ Ln Unit : m) 7. Dry pit reinforced to sustain normal vertical forces from rails and buffers. (Rule located per the applicable code and where practicable located adjacent to the
NPM1000 NPM1200 106.1b and 109) Consult Hyundai Elevator Company for rail forces and buffer door of the machine room. (Rule 210.5 and 306.7)
Incli- Vertical intermediate
Number of
nation H Rise
(mm) Support
impacts. Where there is space below the pit floor that can be occupied, consult 7. Feeder and branch wiring to the controller, including main-line switch and
R1 (kg) R2 (kg) R3 (kg
R4 (kg) R5 (kg) R1 (kg) R2 (kg) R3 (kg) R4 (kg) R5 (kg)
Hyundai Elevator Company for special requirements. (Rule 300.4) Cylinder hole, convenience outlets.
10° 1430 1 453 × L1 + 700 439 × L2 + 45 449 × (L1 + L2) - - 503 × L1 + 780 487 × L2 + 50 498 × (L1 + L2) - - 8. Suitable power feeder and branch wiring circuits as required for elevators with
casings under the pit as required, and backfilling around the cylinder casings when
& ~ 2 453 × L1 + 700 439 × L2 + 45 440 × (L2 + L3) 449 × (L1 + L3) - 503 × L1 + 780 487 × L2 + 50 489 × (L2 + L3) 498 × (L1 + L3) - direct plunger type is to be installed. power-operated doors, including disconnect switch or circuit breaker.
12° 7000 3 453 × L1 + 700 439 × L2 + 45 440 × (L2 + L3) 440 × (L3 + L4) 449 × (L1 + L4) 503 × L1 + 780 487 × L2 + 50 489 × (L2 + L3) 489 × (L3 + L4) 498 × (L1 + L4) 8. Where access to the pit is by means of the lowest hoistway entrance, vertical iron
ladder extending 1060mm minimum above sill of access door. (Rule 106.1d)
9. Entrance walls and finished floor are not to be constructed until after door frames
Emergency Provisions
and sills are in place. Door frames are to be anchored to walls and properly 9. Elevator fireman’s and other emergency services wiring and interconnections to
W3 1350 1550 11. Elevator fireman’s and other emergency service requirements may differ from
W4 1300 1500
Machine Room each country. Consult Hyundai Elevator Company or local distributor for other
L200×200×20 local requirements.
Base Plate W5 1500 1700 11. Enclosed and protected machine room. (Rule 101.1)
150×19 12. Access to the machine room and machinery space as required by the applicable 12. When provisions for earthquake protection are required, consult Hyundai Elevator
50 50 code or responsible authority. (Rule 101.3) Company for special requirements.
13. Reinforced concrete machine room floor slab or grating, as specified, which must
not be placed over the hoistway until elevator machinery is set in position. (Rule
Typical Steel Support w4
w5
100.3 for Traction Elevator) Heat Emission of Machine Room
Min. 200 Clear access above ceiling or trench in floor, for oil line and wiring duct from
Top of Finish Floor
(By Others) Q (Kcal/H) = WÝVÝFÝN
machine room, if machine room is remote from elevator hoistway. (For Hydraulic
11(Shim)
Elevator) Cutout through machine room wall, for oil line and wiring duct as
90
required by Hyundai Elevator’s shop drawings. (For Hydraulic Elevator) F : Factor ; 1/40 (VVVF) N : Number of cars
14. Hoisting beams, trap doors, and other means of access to machine room for
L200×200×20 maintenance and equipment removal purposes. (Rule 101.3d)
50 50
15. Cable guards in the machine room or secondary level. (Rule 104.1)
Reinforced Plate
(By Others) 16. Supports for machine and sheave beams and reactions including wall pockets and
patching after beams are set in place. (Rule 105.1 to 105.5)
Note : Consult Hyundai if the isolation pad is applied.
38 39
ELECTRIC POWER REQUIREMENTS (By others)
(50/60Hz, 380V)
AC-Gearlessǖ180~600m/min (50/60Hz, 380V)
Speed N.F.B. Rated Transformer Power Feeder Earth Wire Speed N.F.B. Rated Transformer Power Feeder Earth Wire
Speed Motor MCCB (A) Power (KVA) Cable (mm2) Earth (mm2) Persons Motor Current (A) Capacity (kVA) (mm2) (mm2) Persons Motor Current (A) Capacity (kVA) (mm2) (mm2)
Persons / Kg / kg
(m/
(kW) / kg
(m/
(kW)
(m/min) (kW) min) min)
1Car 2Cars 1Car 2Cars 1Car 2Cars 1Car 2Cars 1Car 2Cars 1Car 2Cars 1Car 2Cars 1Car 2Cars 1Car 2Cars 1Car 2Cars 1Car 2Cars 1Car 2Cars
60 5.5 (2.8) 20 (20) 30 (20) 4 (3) 7 (5) 4 (4) 6 (4) 4 (6) 4 (6) 13 / 180 25 75 150 28 50 16 50 10 35
180 16.6 50 100 18 33 10 25 6 16
900 210 30 100 175 33 60 25 50 16 35
6 / 450 90 7.5 (4.2) 20 (20) 30 (40) 6 (4) 10 (8) 4 (4) 6 (10) 4 (6) 6 (6)
180 18.4 60 100 20 37 10 25 6 16 240 35 125 200 39 70 35 70 25 50
105 7.5 (4.9) 20 (20) 40 (40) 7 (5) 12 (9) 4 (4) 10 (10) 4 (6) 6 (6) 15 /
210 23 75 125 26 46 16 35 10 25 300 42 125 225 47 84 35 70 25 50
1000 20 /
60 5.5 (3.4) 20 (20) 30 (20) 5 (4) 9 (6) 4 (4) 6 (4) 4 (6) 4 (6) 240 26 100 150 29 52 25 50 16 35 360 50 150 300 56 100 50 120 35 95
1350
180 21.2 75 125 24 42 16 35 10 25 420 58 150 300 64 116 50 120 35 95
8 / 550 90 7.5 (5.1) 20 (20) 30 (40) 7 (5) 13 (10) 4 (4) 6 (10) 4 (6) 4 (6)
210 25 75 150 28 50 16 50 10 35 480 67 175 300 74 134 50 120 35 95
105 11 (5.9) 30 (20) 50 (40) 8 (6) 15 (11) 6 (4) 16 (10) 4 (6) 6 (6) 240 30 100 175 33 60 25 50 16 35 540 75 200 350 83 150 70 150 50 120
60 5.5 (3.7) 20 (20) 30 (30) 5 (4) 9(7) 4 (4) 6 (6) 4 (6) 4 (6) 300 36 125 200 40 72 35 70 25 50 600 83 225 400 92 166 70 185 70 150
17 /
360 43 125 200 48 86 35 70 25 50 180 30 100 175 33 60 25 50 16 35
9 / 600 90 11 (5.6) 30 (20) 50 (40) 8 (6) 14 (11) 6 (4) 16 (10) 4 (6) 6 (10) 1150
420 50 125 225 56 100 35 70 25 50 210 35 125 200 39 70 35 70 25 50
105 11 (6.5) 30 (20) 50 (40) 9 (7) 16 (12) 6 (4) 16 (10) 4 (6) 6 (10) 480 57 150 300 63 114 50 120 35 95 240 40 125 225 44 80 35 70 25 50
60 7.5 (4.3) 20 (20) 40 (30) 6 (5) 11 (8) 4 (4) 10 (6) 4 (6) 6 (6) 540 64 175 300 71 128 50 120 35 95 300 50 150 300 56 100 50 120 35 95
24 /
600 71 175 350 79 142 50 150 35 120 360 60 175 350 67 120 50 150 35 120
10 / 700 90 11 (6.5) 30 (20) 50 (40) 9 (7) 16 (12) 6 (4) 16 (10) 4 (6) 6 (6) 1600
420 69 175 350 77 138 50 150 35 120
105 11 (7.6) 30 (20) 60 (40) 11 (9) 19 (14) 6 (4) 16 (10) 4 (6) 10 (6) 480 79 200 350 88 158 70 150 50 120
60 7.5 (4.6) 20 (20) 40 (30) 6 (5) 12 (9) 4 (4) 10 (6) 4 (6) 6 (6) 540 89 225 400 99 178 70 185 70 150
600 98 250 500 109 196 95 240 95 185
90 11 (6.9) 30 (20) 50 (40) 10 (7) 17 (13) 6 (4) 16 (10) 4 (6) 6 (10)
11 / 750 Notes : 1. The above power sizes are for lengths of electric wire up to 50m from the elevator 2. Above power feeder sizes are for copper wires inside electro-metallic tubing.
105 11 (8.1) 30 (30) 60 (50) 11 (9) 20 (15) 10 (6) 16 (16) 4 (6) 10 (10)
machine room to the transformer. 3. It is recommended a larger diameter earth wire be used.
120 (9.2) (30) (50) (10) (18) (6) (16) (6) (10) For lengths of 50m or more, the following formula should be applied : 4. For installing several elevators, apply the following formula.
Power feeder length (m) Transformer Capacity (kVA) = Number of elevator X Diversity factor
60 11 (5.6) 30 (20) 50 (30) 8 (6) 14 (11) 6 (4) 10 (6) 4 (6) 6 (6) Power feeder size (mm2) =
50
Ý size in the above (mm2)
5. Consult Hyundai if you need electric power requirements for 220V.
90 15 (8.3) 40 (30) 60 (50) 12 (9) 21 (16) 10 (6) 16 (16) 6 (6) 10 (10) Number of elevator (N) 1 2 3 4 5 6. For AC-Geared elevators, consult Hyundai.
Diversity factor 1.00 0.91 0.85 0.80 0.76 7. For AC-Gearless elevators(300m/min ~ 1080m/min), consult Hyundai.
13 / 900 105 15 (9.7) 40 (30) 75 (50) 14 (10) 24 (18) 10 (6) 25 (16) 6 (6) 10 (10)
120 (11.1) (30) (60) (12) (21) (6) (16) (6) (10)
150 (13.8) (50) (100) (15) (28) (10) (25) (6) (16)
60 11 (6.2) 30 (20) 50 (40) 9 (7) 15 (12) 6 (4) 16 (10) 4 (6) 6 (10) Hydraulicǖ30~45m/min (50/60Hz, 380v)
90 15 (9.2) 40 (30) 75 (50) 13 (10) 23 (18) 10 (6) 25 (16) 6 (6) 10 (10) N.F.B. Rated Transformer Power Feeder Earth Wire Heat Emission of Machine Ventilation of
Speed
15 / 1000 105 15 (10.8) 40 (30) 75 (60) 15 (11) 27 (20) 10 (6) 25 (16) 6 (6) 10 (10) Persons / kg Motor (kW) Current (A) Capacity (kVA) (mm2) (mm2) Room (kcal/h) Machine Room (m2/h)
(m/min)
120 (12.3) (40) (75) (13) (23) (10) (25) (6) (16) 1Car 2Cars 1Car 2Cars 1Car 2Cars 1Car 2Cars 1Car 2Cars 1Cars 2Cars
30 15 50 100 25 45 10 25 6 6 3000 6000 1000 2000
150 (15.4) (50) (100) (17) (31) (10) (25) (6) (16) 6 / 450
45 22 75 150 38 70 16 50 6 10 3900 7800 1300 2600
60 11 (7.1) 30 (20) 50 (40) 10 (8) 18 (13) 6 (4) 16 (10) 4 (6) 6 (10) 30 18.5 75 125 30 56 16 35 6 6 3500 7000 1100 2200
8 / 550
90 15 (10.6) 40 (30) 75 (60) 15 (11) 27 (20) 10 (6) 25 (16) 6 (6) 10 (10) 45 30 100 175 49 90 25 70 6 10 5500 11000 1900 3800
17 / 1150 105 18.5 (12.4) 50 (30) 100 (60) 17 (13) 31 (23) 16 (6) 35 (16) 6 (6) 10 (16) 30 18.5 75 125 30 56 16 35 6 6 3500 7000 1100 2200
9 / 600
45 30 100 175 49 90 25 70 6 10 5500 11000 1900 3800
120 (14.1) (40) (75) (15) (27) (10) (25) (6) (16)
30 18.5 75 125 30 56 16 35 6 6 3500 7000 1100 2200
150 (17.7) (60) (100) (20) (35) (10) (25) (6) (16) 10 / 680
45 30 100 175 49 90 25 70 6 10 5500 11000 1900 3800
60 15 (8.3) 30 (20) 60 (40) 12 (9) 21 (16) 10 (4) 16 (10) 6 (6) 6 (6) 30 18.5 75 125 30 56 16 35 6 6 3500 7000 1100 2200
11 / 750
90 18.5 (12.5) 50 (40) 100 (75) 17 (13) 31 (24) 16 (10) 25 (25) 6 (6) 10 (10) 45 30 100 175 49 90 25 70 6 10 5500 11000 1900 3800
30 30 100 175 49 90 25 70 6 10 5500 11000 1900 3800
20 / 1350 105 22 (14.5) 50 (40) 100 (75) 20 (15) 37 (28) 16 (10) 35 (25) 6 (6) 10 (10) 13 / 900
45 37 125 225 62 113 35 95 6 10 6900 13800 2300 4600
120 (16.6) (40) (100) (17) (31) (10) (25) (6) (10) 30 30 100 175 49 90 25 70 6 10 5500 11000 1900 3800
15 / 1000
150 (20.7) (75) (125) (23) (41) (16) (35) (10) (25) 45 37 125 225 62 113 35 95 6 16 6900 13800 2300 4600
60 15 (9.9) 40 (30) 75 (50) 14 (10) 25 (19) 10 (6) 25 (16) 6 (6) 10 (6) 30 37 125 225 62 113 35 95 6 16 6900 13800 2300 4600
17 / 1150
45 52 175 300 81 148 50 150 10 25 9700 19400 3500 7000
90 22 (14.8) 50 (50) 100 (75) 21 (16) 37 (28) 16 (10) 35 (25) 6 (6) 10 (10)
30 37 125 225 62 113 35 95 6 16 6900 13800 2300 4600
105 22 (17.2) 60 (50) 125 (100) 24 (18) 43 (33) 16 (16) 35 (25) 10 (6) 16 (10) 20 / 1350
24 / 1600 45 52 175 300 81 148 50 150 10 25 9700 19400 3500 7000
120 (19.7) (50) (100) (21) (37) (16) (25) (6) (10) 30 37 125 225 62 113 35 95 6 16 6900 13800 2300 4600
24 / 1600
150 (24.5) (75) (150) (27) (49) (16) (50) (10) (35) 45 52 175 300 81 148 50 150 10 25 9700 19400 3500 7000
Notes : 1. Above power feeder sizes are for the length of electric wire up to 50m from elevator machine room to transformer.
Notes : 1. Above power feeder sizes are for the length of electric wire up to 50m from 4. Machine room temperature should be maintained below 40°C with ventilating fan For the length being 50m or more, the following formular should be applied:
elevator machine room to power. and air conditioner, and humidity below 90%. 2. Above power feeder sizes are for copper wires inside electrometallic tubings. Power feeder sizes (mm2) = Power feeder length (m) ÝSize in the above (mm2)
For the length being 50m or more, the following formular should be applied. 5. Data shown in ( ) is applied to the Machine-Room-Less elevators and gearless elevators. 3. For power requirement of 3 cars or more, consult Hyundai. 50
2. Above cable sizes are for copper wires inside electrometallic tubings. 4. Machine room temperature should be maintained below 40°C with ventilating fan and air conditioner, and humidity below 90%.
Cable length (m)
Cable sizes (mm 2) = ÝSize in the above (mm2) 5. The heat emission and ventilation of machine room on above dimensions may vary slightly with the machine room size and
50
peripheral environment.
3. For power requirement of 3 cars or more, consult Hyundai.
6. Consult Hyundai if you need electric power requirements for 220V.
40 41
ELECTRIC POWER REQUIREMENTS (By others)
There are some building and electrical work which is necessary for a normal escalator
installation, but is not done by the escalator contractor. Please consult Hyundai for it.
Electric Power
Motor Power Supply Power Supply Voltage C.B. Rated Power Feeder (mm2) (from power room to escalator controller)
Type
(kW) Capacity (kVA) (AC-3Phase) Current (A) 20m 40m 60m 80m 100m 120m
Ɇ 50 10 16 25 35 35 35
5.5 12 ɇ 30 6 6 10 16 16 16
Ɉ 30 6 6 6 10 10 16
Ɇ 60 10 25 35 35 50 50
7.5 14 ɇ 40 6 6 10 16 16 25
Ɉ 30 6 6 6 10 16 16
Ɇ 75 16 25 35 35 50 70
5.5Ý2/11 19 ɇ 50 6 10 16 25 25 25
Ɉ 40 6 6 10 16 16 25
New World Ɇ 125 25 35 50 95 95 120
Class 7.5Ý2 27 ɇ 75 6 16 25 25 35 35
/ Ɉ 60 6 10 16 25 25 25
Millennium Ɇ 175 35 50 50 120 120 150
/ 7.5Ý3 40 ɇ 100 10 25 35 35 50 50
Modular Ɉ 100 6 16 25 25 35 35
Ɇ 225 35 95 120 120 185 185
7.5Ý4 52 ɇ 150 16 25 35 50 70 95
Ɉ 125 10 25 25 35 35 50
Ɇ 300 50 95 120 185 185 240
7.5Ý5 65 ɇ 175 16 35 50 70 95 95
Ɉ 150 16 25 35 35 50 70
Ɇ 350 50 120 150 185 240 300
7.5Ý6 78 ɇ 200 25 35 50 95 95 120
Ɉ 175 16 25 35 50 70 95
Ɇ 100 16 25 35 50 50 95
11 19 ɇ 50 6 10 16 25 25 25
Ɉ 40 6 6 10 16 16 25
Ɇ 125 25 35 50 70 95 120
16 25 ɇ 60 6 16 25 25 35 35
Ɉ 50 6 10 16 16 25 25
Ɇ 150 25 35 50 95 120 120
18.5 31 ɇ 75 10 16 25 35 35 35
Ɉ 75 6 16 16 25 25 35
Ɇ 175 25 50 95 120 120 150
H-Series 22 36 ɇ 100 10 16 25 35 35 50
Ɉ 75 6 16 25 25 35 35
Ɇ 175 35 50 95 120 120 150
26 46 ɇ 125 16 25 35 35 50 50
Ɉ 100 6 16 25 25 35 35
Ɇ 200 35 95 120 120 185 185
30 52 ɇ 125 16 25 35 50 70 95
Ɉ 100 10 25 25 35 35 50
Ɇ 300 50 95 120 185 185 240
37 60 ɇ 150 16 35 50 70 95 95
Ɉ 125 16 25 35 35 50 70
Lighting Power
Balustrade Vertical Power Supply Power Supply C.B. Rated Power Feeder (mm2)
Voltage
Type Rise (m) Capacity (kVA) (AC-1phase) Current (A) 20m 40m 60m 80m 100m 120m
1.83-4.27 1.4(3) 30(40) 6 10 16
With Handrail 4.28-7.6 100-110
2(6) 40(70) 6 10 16 25
Lighting
(BTL Type) 1.83-4.27 1.4(3)
200-265
20 4 6 10
4.28-7.6 2(6) 20(40) 4 6 10 Ɇ 3Ø, 200V, 50Hz 3Ø, 220V, 60Hz
100-110 2.5 4 6 10 ɇ 3Ø, 346V, 50Hz 3Ø, 380V, 60Hz
Without Handrail - 1.2 20
Lighting 200-265 2.5 4 6 10 Ɉ 3Ø, 415V, 50Hz 3Ø, 460V, 60Hz
Notes : 1. Consult Hyundai when the rise over 7600mm.
2. The capacity shown by ( ) mark shall be applied to moving walks.
42