Bay Controller SIPROTEC 6MD85

Properties

Properties – SIPROTEC 6MD85


Brief description Bay controller for medium-voltage and
1
high- to extra-high-voltage switchgear with
integrated operation and extensive protec-
1.1
tion functions. Powerful automation, simple
configuration with DIGSI 5. 1.2
Inputs and outputs • 5 predefined standard variants with
4 current transformers and
1.3
4 voltage transformers,
11 to 75 binary inputs, 1.4
9 to 41 binary outputs or
Hardware flexibility • flexibly adjusted and expandable I/O 1.5
quantity structure within the scope of the
SIPROTEC 5 modular system. The device 1.6
can be expanded into the second tier if a
large number of inputs and outputs are 1.7
needed. For example, 240 (and more)
binary inputs are possible with the IO230 1.8
(see Section Hardware).
Housing width 1/3 × 19" to 2/1 × 19" 1.9
• Integrated bay controller with versatile protection functions 2
for applications from medium to extra high voltage
• Control of up to 20 switching devices
2.1
• Synchrocheck and switchgear interlocking system
Fig. 2.9 / 2 Bay controller SIPROTEC 6MD85 (1/3 device with
2.2
• Integrated electrical Ethernet port J for DIGSI 1/6 expansion module and operation panel for key-operated
switch) 2.3
• IEC 61850 (Reporting) via integrated port J
• Up to 4 pluggable communication modules usable for different 2.4
and redundant protocols (IEC 61850, IEC 60870-5-103, as selective protection equipment for overheadlines and cables
IEC 60870-5-104, DNP3 (serial+TCP), Modbus RTU Slave) with single- and multi-ended infeeds. The device supports all
• Ethernet redundancy protocols PRP and HSR SIPROTEC 5 system characteristics. It enables future-oriented
system solutions with high investment security and low operat-
• Cyber Security in accordance with NERC CIP and BDEW ing costs.
whitepaper
• Powerful automation with CFC (Continuous Function Chart) Functions 2.5
• Optional overcurrent protection for all voltage levels with Table 2.9 / 2 on page 2.9 / 5 shows all functions that are available
3-pole tripping in the SIPROTEC 6MD85. Basically, all functions can be con-
• Also used in switchgear with breaker-and-a-half scheme figured freely with DIGSI 5. For the application of some of the
• Selective protection of overhead lines and cables with functions, you require the appropriate number of free function
single- and multi-ended infeeds for use with protection data points within the device. The function point calculator in the
communication online configurator provides support in determining the required
number of function points for your device. 2.6
• Overcurrent protection also configurable as backup
function Application templates 2.7
• Secure serial protection data communication, also over
Application templates are available in DIGSI for standard
great distances and all available physical media (fiber-optic
applications. They comprise all basic configurations and default
2.8
cable, 2-wire connections and communication networks)
settings. Table 2.9 / 2 on page 2.9 / 5 shows the functional scope 2.9
• Measurement of operational values and the function point requirement for the application templates
• Synchrophasor measured values and IEEE C37.118 protocol described. The following application templates are available: 2.10
integrated (PMU)
SIPROTEC 6MD85 standard
• Powerful fault recording 3
• Auxiliary functions for simple tests and commissioning. • Double-busbar feeder with switchgear interlocking.
3.1
Applications SIPROTEC 6MD85 extended control
• Additionally to 6MD85 standard, this includes the CFC blocks 3.2
The bay controller 6MD85 is a universal, control and automation
for switching sequences and arithmetic
device with protection functions on the basis of the SIPROTEC 3.3
5 system. It is especially designed for the protection of lines • Switching sequence for automatic busbar transfer precon-
and therefore it is optimally suitable for reserve or emergency figured (started by function key). 3.4
protection for the line protection devices. Due to its high flex-
ibility in using of protection data communication it is suitable 3.5
3.6
3.7
SIPROTEC 5 – Devices · Protection, Automation and Monitoring · Siemens SIPROTEC 5.01 · Edition 2 2.9 / 3
Bay Controller SIPROTEC 6MD85
Application example

1
1.1
1.2 QB1 QB2

1.3
)* 9,BSK )* &LUFXLWEUHDNHU4$
1.4 
QA1 MP I-3ph V-1ph 
V4
1.5 V-1ph 1 V-3ph V-3ph

1.6 QB9 I1
I2 MP
1.7 I3 I-3ph 1 2SHUDWLRQDOPHDVXUHG
Display, Ctrl
YDOXHV
I4 Commu- BI
1.8 (QHUJ\PHWHUHG
YDOXHV
nication, CB
BO
CFC
V1
1.9 V2
MP
V-3ph 1

Fig_3_6_Visio_Bsp-Application-1-us.pdf
&)&
V3 )* 'LVFRQQHFWRU4%
2 6ZLWFKLQJVHTXHQFH
IRUEXVEDUWUDQVIHU

2.1 /LQH Ctrl


BI
2.2 Dco
BO
2.3
2.4 )* )XQFWLRQJURXS  6\QFKURFKHFNV\QFKURQL]LQJIXQFWLRQ
03 0HDVXULQJSRLQW &WUO &RQWURO
(QA) &% &LUFXLWEUHDNHU &)& &RQWLQXRXV)XQFWLRQ&KDUW
(QB) 'FR 'LVFRQQHFWRU
%, %LQDU\LQSXW
%2 %LQDU\RXWSXW

2.5 Fig. 2.9 / 3 Application example: Bay controller SIPROTEC 6MD85 for double busbar with switching sequence for busbar transfer

2.6
2.7
2.8
2.9
2.10
3
3.1
3.2
3.3
3.4
3.5
3.6
3.7
2.9 / 4 SIPROTEC 5 – Devices · Protection, Automation and Monitoring · Siemens SIPROTEC 5.01 · Edition 2
Bay Controller SIPROTEC 6MD85
Functions, application templates

Application templates 1

Available in 6MD85
1.1

6MD85 expanded
6MD85 standard
1.2
1.3
ANSI Functions Abbr. 1.4
25 Synchrocheck, synchronizing function Sync Q
50BF Circuit-breaker failure protection CBFP – 1.5
79 Automatic reclosing AR –
PMU Synchrophasor measurement PMU Q
1.6
Operational measured values, standard Q Q Q
1.7
Measured values, extended: Min, Max, Avg Q 6x
Switching-statistic counters Q Q Q 1.8
CFC standard Q Q Q
CFC arithmetic Q
1.9
CFC switching sequences Q Q
Control for 4 switching devices Q Q Q
2
Q
Control for more than 4 switching devices 2.1
Protection interface Q
50/51 Overcurrent protection, phases I>, IP> Q 2.2
50N/51N Overcurrent protection, ground IN>, INP Q
50HS High speed instantaneous overcurrent protection I>>> Q
2.3
Q
59 Overvoltage protection, 3-phase V> 2.4
59 Overvoltage protection, positive-sequence system V1> Q
59N Overvoltage protection, zero-sequence system V0> Q
27 Undervoltage protection, 3-phase V< Q
27 Undervoltage protection, positive-sequence system V1< Q
81O Overfrequency protection f> Q
81U Underfrequency protection f< Q
Inrush-current detection Q
2.5
Monitoring and supervision Q Q Q
46 Negative-sequence system overcurrent protection I2>, I2/I1> Q
49 Thermal overload protection θ, I2t Q
External trip initiation Q
74TC Trip-circuit supervision TCS Q
Function points 0 75 2.6
The configuration and function points for your application can be ascertained in the
SIPROTEC 5 order configurator under: www.siemens.com/siprotec
2.7
Table 2.9 / 2 SIPROTEC 6MD85 – Functions and application templates
2.8
2.9
2.10
3
3.1
3.2
3.3
3.4
3.5
3.6
3.7
SIPROTEC 5 – Devices · Protection, Automation and Monitoring · Siemens SIPROTEC 5.01 · Edition 2 2.9 / 5