The document provides assumptions and design parameters for structural design of transformer and earthing transformer roofs in Staad Pro software. It includes unit weights of materials, live loads, wind loads, load combinations, and grade of steel. The total weight of structural members for the transformer roof is 38.404 kN and for the earthing transformer roof is 12.4 kN. The total weight of the roof supporting arrangement including purlins but excluding sheeting is 10.21 tons.
The document provides assumptions and design parameters for structural design of transformer and earthing transformer roofs in Staad Pro software. It includes unit weights of materials, live loads, wind loads, load combinations, and grade of steel. The total weight of structural members for the transformer roof is 38.404 kN and for the earthing transformer roof is 12.4 kN. The total weight of the roof supporting arrangement including purlins but excluding sheeting is 10.21 tons.
The document provides assumptions and design parameters for structural design of transformer and earthing transformer roofs in Staad Pro software. It includes unit weights of materials, live loads, wind loads, load combinations, and grade of steel. The total weight of structural members for the transformer roof is 38.404 kN and for the earthing transformer roof is 12.4 kN. The total weight of the roof supporting arrangement including purlins but excluding sheeting is 10.21 tons.
The document provides assumptions and design parameters for structural design of transformer and earthing transformer roofs in Staad Pro software. It includes unit weights of materials, live loads, wind loads, load combinations, and grade of steel. The total weight of structural members for the transformer roof is 38.404 kN and for the earthing transformer roof is 12.4 kN. The total weight of the roof supporting arrangement including purlins but excluding sheeting is 10.21 tons.
1. Unit weight of roof sheet cladding including purlins 30 kg/m2
2. Unit Weight for water proofing and other ancillaries 30 kg/m2 3. Unit Weight for thermal insulation of metal cladding 15 kg/m2 4. Dust Load considered on roof due to dust storm 75kg/m2 5. Live load considered considering accesible roof 150kg/m2 6. Calculated design wind pressure considered for roof 1.48kN/m2 considering wind speed of 45 m/s as per TS 7. Software followed for design Staad-Pro 8. Load combinations as per BS EN 1990:2002 9. Live Load considerations for roof as per BS 6399-3:1988 10. Design of Steel structure as per BS EN 1993-1-1:2005 11. Grade of steel used S275 as per TS.
Structural Summary as per Staad Pro Design Output
Transformer Roof(IBT-1 & IBT-2)
PROFILE LENGTH(METE) WEIGHT(KN ST CH100X50X10 131.34 13.116 ST CH125X65X15 72 10.398 ST UA40X40X5 25.5 0.742 ST UA100X100X10 34.89 5.147 ST UA75X75X8 25.87 2.266 ST UA60X60X6 25.87 1.373 ST UA50X50X6 25.5 1.115 ST UA45X45X5 13.5 0.404 ST UA75X75X6 31.89 2.139 ST UA90X90X8 15.95 1.703 TOTAL = 38.404
Earthing Transformer(ET-1 & ET-2)
PROFILE LENGTH(METE) WEIGHT(KN ST CH100X50X10 58.5 5.842 ST CH125X65X15 15 2.166 ST UA40X40X5 18.53 0.539 ST UA75X75X8 20.64 1.808 ST UA45X45X5 12 0.36 ST UA75X75X6 21.21 1.423 ST UA50X50X6 6 0.262 TOTAL = 12.4
Total Quantity of structural members 50.80
Quantity of purlins CH 150x75 @17.9kg/m 42 Quantity assumed for gussets, plates, bolts etc.@10% 9.28
Total Quantity for Roof Supporting 102.08 kN
Arrangement(including purlins but excluding sheeting Total Quantity for Roof Supporting Arrangement(including purlins but excluding 10.21 ton sheeting PROFILE LENGTH(METE) WEIGHT(KN
ST CH100X50X10 131.34 13.116
ST CH125X65X15 72 10.398 ST UA40X40X5 25.5 0.742 ST UA100X100X10 34.89 5.147 ST UA75X75X8 25.87 2.266 ST UA60X60X6 25.87 1.373 ST UA50X50X6 25.5 1.115 ST UA45X45X5 13.5 0.404 ST UA75X75X6 31.89 2.139 ST UA90X90X8 15.95 1.703 ---------------- TOTAL = 38.404
ST CH100X50X10 58.5 5.842
ST CH125X65X15 15 2.166 ST UA40X40X5 18.53 0.539 ST UA75X75X8 20.64 1.808 ST UA45X45X5 12 0.36 ST UA75X75X6 21.21 1.423 ST UA50X50X6 6 0.262 ---------------- TOTAL = 12.4