Grid1 - calculo1.GR1S - Complete
Grid1 - calculo1.GR1S - Complete
Contract: SN:
Frequency: 60.0
Contract: SN:
System Data
Total Sf Cp Tf Tc Ts
Ambient Fault Division Projection for for Sizing for
Freq. Weight Temp. Current Factor Factor Total Fault Ground Available
Hz kg °C kA X/R % % Duration Conductors Body Current
60.0 70 30.00 6.800 20.00 100.0 100.0 0.60 0.60 0.60
Soil Data
Crushed rock 4267.2 0.200 Moist soil 302.6 7.27 Moist soil 67.5
Material Constants
Resistivity of Thermal
r Factor Fusing Ground Conductor Capacity
Conductivity @ 20 °C K0 @ Temperature @ 20°C Per Unit Volume
Conductor/Rod Type % 1/°C 0 °C °C micro ohm.cm J/(cm³.°C)
Conductor Copper, commercial hard-drawn 97.0 0.00381 242.0 1084.0 1.78 3.42
Rod Copper-clad steel wire 1 40.0 0.00378 245.0 1084.0 4.40 3.85
Rod Data
Grid Configuration
Contract: SN:
Cost
Conductor Rod
Total Total Length Cost Total Total Length Cost Total Cost
No. m $ No. m $ $
34 2080 93600.00 60 600 12000.00 105600.00
Project: ETAP Page: 4
Contract: SN:
Rg GPR
Touch Potential Step Potential
Ground Ground
Resistance Potential Rise Tolerable Calculated Tolerable Calculated
Maximum Grid Current: 7.094 kA Surface Layer Derating Factor (Cs): 0.829