May 2008 — Approval Guide Page 1


Automatic Sprinkler Systems
CHAPTER 1
AUTOMATIC SPRINKLER SYSTEMS

Automatic sprinkler protection is recommended for industrial and other buildings having combustible construction or combustible occupancies. There are many
FM Approved types of automatic sprinklers. Typical examples include: upright, pendent, flush, recessed, concealed, sidewall, dry-pendent and dry-upright, Early
Suppression Fast Response (ESFR), Quick Response (QR), extended coverage, corrosion resistant, large drop, rack storage and decorative coated. A sprinkler
operates automatically when the heat-actuated element is heated to, or above, its thermal rating. Selection of the proper temperature rating for automatic
sprinklers is important. The proper rating provides a factor of safety designed to prevent premature operation. The rating should be selected from the following
table:

TEMPERATURE RATINGS OF SPRINKLERS

Max Temperature at Rated Temperature of


Rating Sprinkler Level Sprinkler Frame Color

Ordinary 100°F 135° through 170°F Unpainted


*
(38°C) (57° through 77°C)
150°F 175° through 225°F

Intermediate (66°C) (79° through 107°C) White


225°F 250° through 300°F

High (107°C) (121° through 149°C) Blue


300°F 325° through 375°F

Extra High (149°C) (163° through 191°C) Red


365°F 400° through 475°F

Very Extra High (185°C) (204° through 246°C) Green


465°F 500° through 650°F

Ultra High (241°C) (260° through 343°C) Orange

*Frame arms of 135°F (57°C) sprinklers of some manufacturers are painted black.

Sprinklers of ‘‘very extra high’’ and ‘‘ultra high’’ ratings are primarily used for internal protection of chambers such as ovens and dryers having working
temperatures above 300°F (149°C). When the sprinklers are normally heated to the working temperature of the oven or dryer, under accidental fire conditions they
will operate fast enough for safe protection. However, when the sprinklers are initially at the same temperature as a cold oven or dryer, operation may be so
severely retarded that the oven or dryer is virtually without internal sprinkler protection.

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide Page 2
Automatic Sprinkler Systems
Specially coated or plated sprinklers are available for use where corrosion resistance is desired and decorative coated sprinklers are available for areas where
improved appearance is desired. For corrosion resistance, wax is satisfactory except in extreme atmospheres. Wax has too low a melting point for high-degree
heads, whereas a bituminous coating affords some protection. A lead coating protects against certain mild corrosive atmospheres. Wax-over-lead provides good
sprinkler protection. Corrosion resistant sprinklers such as those manufactured from stainless steel or other corrosion resistant materials currently afford the
best available protection. Common decorative finishes are bright brass, chrome, paint, or polyester coating. These finishes are for decorative purposes only and
are not FM Approved for corrosion resistance.

Only sprinklers supplied by the listed manufacturers are FM Approved. .Any change in the device after it leaves the manufacturer voids the Approval. Coated,
plated and painted sprinklers rated above 165°F (74°C) have the standard temperature color code either on the frame arms or on the compression screws, except
in the case of bulb type decorative coated sprinklers in which the bulb fluid color indicates the temperature rating per the following table:
Temperature Rating Bulb Color
°F (°C) Code
135°
Orange
(57°)
155°
Red
(68°)
175°
Yellow
(79°)
200°
Green
(93°)
250°, 286°
Blue
(121°, 141°)
325°, 360°
Mauve
(162°, 182°)
400°–650°
Black
(204°–343°)

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide Page 3
Automatic Sprinkler Systems

When selecting a specific type of sprinkler, refer to the FM Global Property Loss Prevention Data Sheets to ensure that the sprinkler selected is capable of
providing adequate fire protection for the intended occupancy. In addition, working plans of proposed layouts, showing all details with respect to location of
sprinklers and piping, description of the occupancy and details of construction, should be sent to your insurance company for review before the materials are
fabricated. The plans will be accepted or changes will be recommended to assure that the work will be done according to the best practice and to avoid the
possibility of later requests for changes.
Unless otherwise noted, automatic sprinkler system components, which are subjected to system water pressure, have a rated working pressure of 175 psi (1205
kPa).

In this section, FM Approved sprinklers are listed in a tabular format.

Because this format limits the space in which the information can be provided, the following conventions are used:

The sprinkler nominal discharge coefficient (K-factor) is expressed in US customary units of gal/min/(psi) ½.
Sprinkler response categories are abbreviated as follows:

SR Standard Response
QR Quick Response
FR Suppression Mode Fast Response

Heat responsive elements are identified as either Fusible or, in the case of bulb type elements, with the nominal bulb diameter in millimeters (e.g., 2.5 mm, 3 mm,
etc.). Nominal thread sizes are expressed using American National Standard Taper Pipe Threads (NPT). Sprinklers intended for sale outside the United States
shall have threads which are in compliance with other national or international standards as permitted at the sole discretion of FM Approvals.

Sprinkler finishes are identified as follows:

Finish Description
Brass Unfinished, Plain Brass or Bronze
Chrome Chrome Plated
Black Plated Black Plated
Bright Brass Bright Brass Plated
Lead Lead Coated (for extra corrosion protection in some atmospheres)
Wax Wax Coated (for extra corrosion protection in some atmospheres)
Wax Over Lead Wax Over Lead Coated (for extra corrosion protection in some atmospheres)
Polyester Polyester Coated (any color)
Painted Painted (any color)

Sprinkler nominal temperature ratings are expressed in degrees Fahrenheit (°F) followed by the equivalent in degrees Celsius (°C).

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide Page 4
Automatic Sprinkler Systems
Control Mode Sprinklers

K2.8 Standard Spray Sprinklers


Control mode standard spray sprinklers have deflectors specially designed to discharge water in all directions below the plane of the deflector. Thus, the spray pattern is roughly that of a half sphere
filled with water spray. Little or no water is discharged upward to wet the ceiling. Upright control mode sprinklers are not intended for use in the pendent position; FM Approved pendent control mode
½
sprinklers are required. Control mode automatic sprinklers with a nominal discharge coefficient of 2.8 gal/min/(psi) have cross sectional3 dimensions of the water passageway less than 8 in. and may
require the use of individual or system strainers per the appropriate FM Global Property Loss Prevention Data Sheets.

K2.8 Upright (Class 2002)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V2701 2.8 Upright SR 5 mm 12 Polyester, Lead, NICOTEF 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Victaulic V2701 2.8 Upright SR 5 mm 1 Wax, Wax Over Lead 155°, 200°F (68°, 93°C)
2

K2.8 Upright, Quick Response (Class 2020)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V2702 2.8 Upright QR 3 mm 12 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)

K5.6 Upright (Class 2002


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V2703 5.6 Upright SR 5 mm 12 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°F (57°,68°,79°,93°, 141°, 182°C)
Polyester, Lead, NICOTEF
Victaulic V2703 5.6 Upright SR 5 mm 1 Wax, Lead, Wax Over Lead 155°, 200°F (68°,93°C)
2

K5.6 Upright, Quick Response (Class 2020)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V2704 5.6 Upright QR 3 mm 12 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°,68°,79°,93°, 141°C)
Polyester, Lead, NICOTEF
Victaulic V2704 5.6 Upright QR 3 mm 1 Wax, Lead, Wax Over Lead 155°, 200°F (68°,93°C)
2

K5.6 Pendent (Class 2017)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V2707 5.6 Pendent SR 5 mm 12 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°F (57°,68°,79°,93°, 141°, 182°C)
Polyester, Lead, NICOTEF
Victaulic V2707 5.6 Pendent SR 5 mm 1 Wax, Wax Over Lead 155°, 200°F (68°,93°C)
2

K5.6 Pendent, Quick Response (Class 2020)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V2708 5.6 Pendent QR 3 mm 12 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°,68°,79°,93°, 141°C)
Polyester, Lead, NICOTEF
Victaulic V2708 5.6 Pendent QR 3 mm 1 Wax, Wax Over Lead 135°, 155°, 175°, 200°, 286°F (57°,68°,79°,93°, 141°C)
2

K5.6 Dry Upright (Class 2013)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V3601 5.6 Dry Upright SR 5 mm 1 Brass, NICOTEF Coated, 135°, 155°, 200°, 286°F (57°,68°,93°, 141°C)

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide Page 5
Automatic Sprinkler Systems
Chrome Polyester
* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).

K5.6 Dry Upright Quick Response (Class 2020)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V3602 5.6 Dry Upright QR 3 mm 1 Brass, NICOTEF Coated, 135°, 155°, 200°, 286°F (57°,68°,93°, 141°C)
Chrome Polyester
* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).

K5.6 Dry Pendent (Class 2013)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V3605 5.6 Dry Pendent SR 5 mm 1 Brass, NICOTEF Coated 135°, 155°, 200°, 286°F (57°,68°,93°, 141°C)
* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).

K5.6 Dry Pendent, Quick Response (Class 2020)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V3606 5.6 Dry Pendent QR 3 mm 1 Brass, NICOTEF Coated 155°, 286°F (68°, 141°C)
* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).

K5.6 H (Class 2020)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V2709 5.6 Horizontal Sidewall SR 5 mm 1 Polyester, Lead, NICOTEF 135°, 155°, 175°, 200°, 286°F (57°,68°,79°,93°, 141°C)
2

Victaulic V2709 5.6 Horizontal Sidewall SR 5 mm 1 Wax, Wax Over Lead 155°, 200°F (68°,93°C)
2

K5.6 Sidewall, Quick Response (Class 2020)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V2710 5.6 Horizontal Sidewall QR 3 mm 12 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°,68°,79°,93°, 141°C)
Polyester, Lead, NICOTEF

K5.6 Dry Sidewall (Class 2013)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V3609 5.6 Dry Horizontal Sidewall SR 5 mm 1 Brass, NICOTEF Coated, 135°, 155°, 200°, 286°F (57°, 68°, 93°, 141°C)
Chrome Polyester
* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).

K5.6 Dry Sidewall, Quick Response (Class 2020)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V3610 5.6 Dry Horizontal Sidewall QR 3 mm 1 Brass, NICOTEF Coated, 135°, 155°, 200°, 286°F (57°,68°,93°, 141°C)
Chrome Polyester
* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).

K5.6 Pendent
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V2707 5.6 Recessed Pendent SR 5 mm 12 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°F (57°,68°,79°,93°C)
Polyester, NICOTEF
Victaulic V3802 5.6 Concealed Pendent SR 3 mm 1 Brass 155°, 175°, 200°F (68°, 79°, 93°C)
2

* This sprinkler is FM Approved with a die cast frame only.

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide Page 6
Automatic Sprinkler Systems
K5.6 Flush, Recessed and Concealed, Quick Response (Class 2020)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V2708 5.6 Recessed Pendent QR 3 mm 12 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°F (57°, 68°, 79, 93°C)
Polyester, NICOTEF

K5.6 Sidewall Flush, Recessed and Concealed (Class 2015)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V2709 5.6 Recessed Horizontal Sidewall SR 5 mm 12 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°F (57°,68°,79°,93°C)
Polyester, NICOTEF

K5.6 Sidewall Flush, Recessed and Concealed, Quick Response (Class 2020)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V2710 5.6 Recessed Horizontal Sidewall QR 3 mm 12 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°F (57°,68°,79°,93°C)
Polyester, Lead, NICOTEF

K5.6 Dry Flush, Recessed and Concealed (Class 2015)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V3605 5.6 Dry Recessed Pendent SR 5 mm 1 Brass, NICOTEF Coated 135°, 155°, 200°F (57°,68°,93°C)
Victaulic V3609 5.6 Dry Recessed Horizontal Sidewall SR 5 mm 1 Brass, NICOTEF Coated, Chrome 135°, 155°, 200°F (57°,68°,93°C)
Polyester

K5.6 Dry Flush, Recessed and Concealed, Quick Response (Class 2020)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F (°C)
Victaulic V3606 5.6 Dry Recessed Pendent QR 3 mm 1 Brass, NICOTEF Coated 135°, 155°, 200°F (57°,68°,93°C)
Victaulic V3610 5.6 Dry Recessed Horizontal Sidewall QR 3 mm 1 Brass, NICOTEF Coated, Chrome 135°, 155°, 200°F (57°,68°,93°C)
Polyester
* Approval of these dry sprinklers is limited to a maximum nominal length of 36 in. (0.91 m).

K5.6 Rack Storage


Rack storage sprinklers (also called intermediate level sprinklers) provide in-rack protection for rack storage arrays. These sprinklers are similar to the basic sprinkler types from which they are derived
½½
except that they are equipped with a disc mounted above the thermal-sensitive element which protects it from delayed operation as a result of water discharge ½ from nearby sprinklers at higher
elevations. Rack storage sprinklers are available with nominal discharge coefficients of 5.6 gal/min/(psi) , 8.0 gal/min/(psi) and 11.2 gal/min/(psi) and in both upright and pendent configurations. When
using quick response rack storage sprinklers, standard response sprinklers will continue to be required at the ceiling level in accordance with the FM Global Property Loss Prevention Data Sheets.
Reference should be made to the FM Global Property Loss Prevention Data Sheets with regard to selection of type and temperature rating for a given installation.

K5.6 Rack Storage, Upright (Class 2005)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V2721 5.6 Rack Storage Upright SR 5 mm ½ Brass, NICOTEF 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
182°C)

K5.6 Rack Storage, Upright, Quick Response (Class 2020)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V2722 5.6 Rack Storage Upright QR 3 mm 1 Brass, NICOTEF 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,
2
182°C)

K5.6 Rack Storage, Pendent (Class 2005)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V2723 5.6 Rack Storage Pendent SR 5 mm ½ Brass, NICOTEF 135°, 155°, 175°, 200°, 286°, 360°F (57°, 68°, 79°, 93°, 141°,

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide Page 7
Automatic Sprinkler Systems
182°C)

K5.6 Rack Storage, Pendent, Quick Response (Class 2020)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V2724 5.6 Rack Storage Pendent QR 3 mm 1 Brass, NICOTEF 135°, 155°, 175°, 200°, 286°F (57°,68°,79°,93°, 141°C)
2

K5.6 Wax Coated High Temperature


There are instances where high temperature sprinklers, rated 250-300°F (121-149°C), are installed for purposes other than expected ambient temperatures above 225°F (107°C) and where the
environment is corrosive. The sprinklers listed below have been coated with a wax normally intended for intermediate temperature sprinklers, 175-225°F (79-107°C) These sprinklers are not
recommended for installation in areas where the ambient temperature may exceed 150°F (66°C).

K5.6 Wax Coated, High Temperature, Upright (Class 2043)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V2703 5.6 Upright SR 5 mm 1 Wax, Wax Over Lead 286°F (141°C)
2

K5.6 Wax Coated, High Temperature, Pendent (Class 2043)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V2707 5.6 Pendent SR 5 mm 1 Wax, Wax Over Lead 286°F (141°C)
2

Wax Coated, High Temperature, Sidewall (Class 2043)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V2709 5.6 Horizontal Sidewall SR 5 mm 1 Wax, Wax Over Lead 286°F (141°C)
2

K5.6 High Temperature Oven


Automatic sprinklers listed in this category are for use in high temperature ovens only. These sprinklers are not to be used in other occupancies.

K5.6 High Temperature Oven, Pendent (Class 2017)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3401 8.0 Upright SR 5 mm 34 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°, 360°F (57°,68°,79°,93°, 141°, 182°C)
Polyester, NICOTEF
Victaulic V3401 8.0 Upright SR 5 mm 3 Wax, Lead, Wax Over Lead 155°, 200°F (68°,93°C)
4

K8.0 Upright, Quick Response (Class 2020)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3402 8.0 Upright QR 3 mm 34 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°,68°,79°,93°, 141°C)
Polyester, Lead, NICOTEF

K8.0 Dry Upright (Class 2013)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3603* 8.0 Dry Upright SR 5 mm 1 Brass, NICOTEF Coated, 135°, 155°, 200°, 286°F (57°,68°,93°, 141°C)
Chrome Polyester
*Approval of these dry sprinklers is limited to a maximum nominal length of 30 in. (0.76 m).

K8.0 Dry Upright Quick Response (Class 2020)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide Page 8
Automatic Sprinkler Systems
Victaulic V3604* 8.0 Dry Upright QR 3 mm 1 Brass, NICOTEF Coated, 155°, 286°F (68°, 141°C)
Chrome Polyester
*Approval of these dry sprinklers is limited to a maximum nominal length of 30 in. (0.76 m).

K8.0 Dry Pendent (Class 2013)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3607* 8.0 Dry Pendent SR 5 mm 1 Brass, NICOTEF Coated 135°, 155°, 200°, 286°F (57°,68°,93°, 141°C)
*Approval of these dry sprinklers is limited to a maximum nominal length of 30 in. (0.76 m).

K8.0 Dry Pendent, Quick Response (Class 2020)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3608* 8.0 Dry Pendent QR 3 mm 1 Brass, NICOTEF Coated 135°, 155°, 200°, 286°F (57°,68°,93°, 141°C)
*Approval of these dry sprinklers is limited to a maximum nominal length of 30 in. (0.76 m).

K8.0 Pendent (Class 2001)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3405 8.0 Pendent SR 5 mm 3 Polyester, Lead, NICOTEF, Wax, 135°, 155°, 175°, 200°, 286°, 360°F (57°,68°,79°,93°, 141°, 182°C)
4
Wax Over Lead

K8.0 Pendent, Quick Response (Class 2020)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3406 8.0 Pendent QR 3 mm 34 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°, 286°F (57°,68°,79°,93°, 141°C)
Polyester, Lead, NICOTEF

K8.0 Flush, Recessed and Concealed (Pendent)

½ ½
Pendent flush, recessed and concealed sprinklers with a nominal discharge coefficient of 8.0 gal/min/(psi) are similar to those with a nominal discharge coefficient of 5.6 gal/min/(psi) except that they
discharge 40% more water at the same discharge pressure. These sprinklers are intended for use with a concealed piping system. Flush types are constructed with an operating element which extends a
short distance below the ceiling. Upon actuation, the sprinkler deflector drops below the ceiling level to provide a proper water distribution. Recessed types consist of a sprinkler installed in a decorative
recessed cup which reduces the protrusion of the sprinkler from the ceiling. Concealed types incorporate a cover plate which is heat activated and can be manually removed to prevent over-painting of the
cover plate. All of these sprinkler types are intended for use where attractive appearance under a ceiling is desired, in such occupancies as offices, hotel lobbies, dining rooms, clubs and similar
properties.

FM Approved flush, recessed and concealed sprinklers are limited to a maximum temperature rating of 225°F (107°C) and to protection of hazard occupancies described in the FM Global Property Loss
Prevention Data Sheets. Quick response flush recessed and concealed sprinklers are FM Approved for use in Wet Systems and Pre-action Systems qualifying as Wet Systems only.

K8.0 Flush, Recessed and Concealed (Class 2015)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3405 8.0 Recessed Pendent SR 5 mm 34 Brass, Chrome, Bright Brass, 135°, 155°, 175°, 200°F (57°, 68°, 79°, 93°C)
Polyester, NICOTEF

K8.0 Dry Flush, Recessed and Concealed (Class 2015)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3607* 8.0 Dry Recessed Pendent SR 5 mm 1 Brass, NICOTEF Coated 135°, 155°, 200°F (57°,68°,93°C)
*Approval of these dry sprinklers is limited to a maximum nominal length of 30 in. (0.76 m).

K8.0 Dry Flush, Recessed and Concealed, Quick Response (Class 2020)
© 2008 FM Approvals LLC. All rights reserved.
May 2008 — Approval Guide Page 9
Automatic Sprinkler Systems
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3608* 8.0 Dry Recessed Pendent QR 3 mm 1 Brass, NICOTEF Coated 135°, 155°, 200°F (57°,68°,93°C)

*Approval of these dry sprinklers is limited to a maximum nominal length of 30 in. (0.76 m).

K8.0 Rack Storage

Rack storage sprinklers (also called intermediate level sprinklers) provide in-rack protection for rack storage arrays. These sprinklers are similar to the basic sprinkler types from which they are derived
except that they are equipped with a disc mounted above the thermal-sensitive element which protects it from delayed operation as a result of water discharge ½ from nearby sprinklers at higher
elevations. Rack storage sprinklers are available with nominal discharge coefficients of 5.6 gal/min/(psi) , 8.0 gal/min/(psi) and 11.2 gal/min/(psi) and in both upright and pendent configurations. When
using quick response rack storage sprinklers, standard response sprinklers will continue to be required at the ceiling level in accordance with the FM Global Property Loss Prevention Data Sheets.
Reference should be made to the FM Global Property Loss Prevention Data Sheets with regard to selection of type and temperature rating for a given installation.

K8.0 Rack Storage, Upright (Class 2005)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3417 8.0 Rack Storage Upright SR 5 mm 34 Brass, NICOTEF 135°, 155°, 175°, 200°, 286°, 360°F (57°,68°,79°,93°,141°,
182°C)

K8.0 Rack Storage, Upright, Quick Response (Class 2020)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3418 8.0 Rack Storage Upright QR 3 mm 3 Brass, NICOTEF 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
4

K8.0 Rack Storage, Pendent (Class 2005)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, ° °C)
Victaulic V3419 8.0 Rack Storage Pendent SR 5 mm 34 Brass, NICOTEF 135°, 155°, 175°, 200°, 286°, 360°F (57°,68°,79°,93°,141°,
182°C)

K8.0 Rack Storage, Pendent, Quick Response (Class 2020)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3420 8.0 Rack Storage Pendent QR 3 mm 3 Brass, NICOTEF 135°, 155°, 175°, 200°, 286°F (57°, 68°, 79°, 93°, 141°C)
4

K8.0 Wax Coated, High Temperature

There are instances where high temperature sprinklers, rated 250-300°F (121-149°C), are installed for purposes other than expected ambient temperatures above 225°F (107°C) and where the
environment is corrosive. The sprinklers listed below have been coated with a wax normally intended for intermediate temperature sprinklers, 175-225°F (79-107°C) These sprinklers are not
recommended for installation in areas where the ambient temperature may exceed 150°F (66°C).

K8.0 Upright, Wax Coated, High Temperature (Class 2043)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3401 8.0 Upright SR 5 mm 3 Wax, Wax Over Lead 286°F (141°C)
4

K8.0 Pendent, Wax Coated, High Temperature (Class 2043)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3405 8 Pendent SR 5 mm 3 Wax, Wax Over Lead 286°F (141°C)
4

K8.0 Extended Coverage Light Hazard (ECLH)

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide Page 10
Automatic Sprinkler Systems
Control mode, Extended Coverage-Light Hazard (ECLH) sprinklers are designed to be installed at spacing and coverage areas greater than the standard spacing of 15 ft by 15 ft (4.6 m by 4.6 m) for
upright and pendent standard sprinklers and 14 ft by 14 ft (4.3 m by 4.3 m) for vertical and horizontal sidewall sprinklers. Upright and pendent ECLH sprinklers, regardless of nominal discharge coefficient,
½
have a maximum spacing (width by length) of 20 ft by 20 ft (6.1 m by 6.1 m). Horizontal sidewall ECLH sprinklers with a nominal discharge coefficient of 5.6 gal/min/(psi) have a maximum spacing (width
½
by length) of 16 ft by 20 ft (4.9 m by 6.1 m). Horizontal sidewall ECLH sprinklers with a nominal discharge coefficient of 8.0 gal/min/(psi) have a maximum spacing (width by length) of 16 ft by 24 ft (4.9 m
by 7.3 m). The FM Global Property Loss Prevention Data Sheets should be closely followed when designing and installing automatic fire protection systems utilizing these sprinklers. FMApproved ECLH
sprinklers are limited to a maximum temperature rating of 175°F (79°C).

K8.0 Extended Coverage Light Hazard (ECLH), Sidewall (Class 2022)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3415 8.0 Horizontal Sidewall SR 5 mm 34 Brass, Chrome, Polyester, 135°F (57°C)
NICOTEF

K8.0 Extended Coverage Light Hazard (ECLH), Sidewall, Quick Response (Class 2020)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3416 8.0 Horizontal Sidewall QR 3 mm 34 Brass, Chrome, Polyester, 135°, 155°F (57°,68°C)
NICOTEF

K8.0 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed (Pendent or Sidewall)

Control mode, Extended Coverage-Light Hazard (ECLH) flush, recessed and concealed sprinklers are ECLH sprinklers intended for use with a concealed piping system. Flush pendent types are
constructed with an operating element which extends a short distance below the ceiling. Upon actuation, the sprinkler deflector drops below the ceiling level to provide a proper water distribution.
Recessed pendent types consist of a sprinkler installed in a decorative recessed cup which reduces the protrusion of the sprinkler from the ceiling. Concealed pendent types incorporate a cover plate
which is heat activated and can be manually removed to prevent over-painting of the cover plate. Sidewall flush, recessed and concealed sprinklers are similar to pendent flush recessed and concealed
sprinklers except that they are designed to be installed in a wall near the junction of the ceiling and wall. They are equipped with a special deflector which discharges most of the water in a forward
direction. All of these sprinkler types are intended for use in light hazard occupancies where attractive appearance under a ceiling is desired. The FM Global Property Loss Prevention Data Sheets should
be closely followed when designing and installing automatic fire protection systems utilizing these sprinklers. Quick response ECLH flush recessed and concealed sprinklers are FM Approved for use in
Wet Systems and Pre-action Systems qualifying as Wet Systems only.

K8.0 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed (Class 2022)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3416 8.0 Recessed Horizontal Sidewall SR 3 mm 34 Brass, Chrome, Polyester, 155°F (68°C)
NICOTEF

K8.0 Extended Coverage Light Hazard (ECLH), Flush Recessed and Concealed, Quick Response (Class 2020)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3416 8.0 Recessed Horizontal Sidewall QR 3 mm 34 Brass, Chrome, Polyester, 135°F (57°C)
NICOTEF
Victaulic V3403 11.2 Upright SR 5 mm 3 Wax, Wax Over Lead 155°, 200°F (68°,93°C)
4

K11.2 Upright, Quick Response (Class 2020)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3404 11.2 Upright QR 3 mm 34 Brass, Chrome, Polyester, Lead, 135°, 155°, 175°, 200°, 286°F (57°,68°,79°,93°, 141°C)
NICOTEF

K11.2 Pendent (Class 2009)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3407 11.2 Pendent SR 5 mm 34 Brass, Lead, Chrome, NICOTEF 135°, 155°, 175°, 200°, 286°F (57°,68°,79°,93°, 141°C)
Victaulic V3407 11.2 Pendent SR 5 mm 3 Wax, Wax Over Lead 155°, 200°F (68°,93°C)
4

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide Page 11
Automatic Sprinkler Systems
K11.2 Pendent, Quick Response (Class 2020)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3408 11.2 Pendent QR 3 mm 34 Brass, Chrome, Lead, NICOTEF 135°, 155°, 175°, 200°, 286°F (57°,68°,79°,93°, 141°C)

K11.2 Extended Coverage Light Hazard (ECLH) Pendent (Class 2022)

Control mode, Extended Coverage-Light Hazard (ECLH) sprinklers are designed to be installed at spacing and coverage areas greater than the standard spacing of 15 ft by 15 ft (4.6 m by 4.6 m) for
upright and pendent standard sprinklers and 14 ft by 14 ft (4.3 m by 4.3 m) for vertical and horizontal sidewall sprinklers. Upright and pendent ECLH sprinklers, regardless of nominal discharge coefficient,
have a maximum spacing (width by length) of 20 ft by 20 ft (6.1 m by 6.1 m). The FM Global Property Loss Prevention Data Sheets should be closely followed when designing and installing automatic fire
protection systems utilizing these sprinklers. FM Approved ECLH sprinklers are limited to a maximum temperature rating of 175°F (79°C).

Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3411 11.2 Pendent SR 5 mm 34 Brass, Chrome, Bright Brass, 135°, 155°, 175°F (57°,68°,79°C)
Polyester, NICOTEF

K11.2 Extended Coverage Light Hazard (ECLH) Pendent, Quick Response (Class 2020)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3412 11.2 Pendent QR 3 mm 34 Brass, Chrome, Bright Brass, 135°, 155°F. (57°, 68°C)
Polyester, NICOTEF

K11.2 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed (Pendent)

Control mode, Extended Coverage-Light Hazard (ECLH) flush, recessed and concealed sprinklers are ECLH sprinklers intended for use with a concealed piping system. Flush pendent types are
constructed with an operating element which extends a short distance below the ceiling. Upon actuation, the sprinkler deflector drops below the ceiling level to provide a proper water distribution.
Recessed pendent types consist of a sprinkler installed in a decorative recessed cup which reduces the protrusion of the sprinkler from the ceiling. Concealed pendent types incorporate a cover plate
which is heat activated and can be manually removed to prevent over-painting of the cover plate. All of these sprinkler types are intended for use in light hazard occupancies where attractive appearance
under a ceiling is desired. The FM Global Property Loss Prevention Data Sheets should be closely followed when designing and installing automatic fire protection systems utilizing these sprinklers. Quick
response ECLH flush recessed and concealed sprinklers are FM Approved for use in Wet Systems and Pre-action Systems qualifying as Wet Systems only.

K11.2 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed Types (Class 2022)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3411 11.2 Recessed Pendent SR 5 mm 34 Brass, Chrome, Bright Brass, Polyester, 135°, 155°F (57°,68°C)
NICOTEF

K11.2 Wax Coated, High Temperature

There are instances where high temperature sprinklers, rated 250-300°F (121-149°C), are installed for purposes other than expected ambient temperatures above 225°F (107°C) and where the
environment is corrosive. The sprinklers listed below have been coated with a wax normally intended for intermediate temperature sprinklers, 175-225°F (79-107°C) These sprinklers are not
recommended for installation in areas where the ambient temperature may exceed 150°F (66°C).

Wax Coated, High Temperature, Upright (Class 2043)


Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3403 11.2 Upright SR 5 mm 3 Wax, Wax Over Lead 286°F (141°C)
4

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide Page 12
Automatic Sprinkler Systems
K11.2 Wax Coated, High Temperature, Pendent (Class 2043)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3407 11.2 Pendent SR 5 mm 3 Wax, Wax Over Lead 286°F (141°C)
4

K14.0 Extended Coverage Light Hazard (ECLH)

Control mode, Extended Coverage-Light Hazard (ECLH) sprinklers are designed to be installed at spacing and coverage areas greater than the standard spacing of 15 ft by 15 ft (4.6 m by 4.6 m) for
upright and pendent standard sprinklers and 14 ft by 14 ft (4.3 m by 4.3 m) for vertical and horizontal sidewall sprinklers. Upright and pendent ECLH sprinklers, regardless of nominal discharge coefficient,
have a maximum spacing (width by length) of 20 ft by 20 ft (6.1 m by 6.1 m). The FM Global Property Loss Prevention Data Sheets should be closely followed when designing and installing automatic fire
protection systems utilizing these sprinklers. FM Approved ECLH sprinklers are limited to a maximum temperature rating of 175°F (79°C).

K14.0 Extended Coverage Light Hazard (ECLH), Pendent (Class 2023)

Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3413 14.0 Pendent SR 5 mm 34 Brass, Chrome, Polyester, NICOTEF
135°, 155°, 175°F (57°,68°,79°C)

K14.0 Extended Coverage Light Hazard (ECLH), Pendent, Quick Response (Class 2020)
Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3414 14.0 Pendent QR 3 mm 34 Brass, Chrome, Polyester, NICOTEF 135°, 155°F (57°,68°C)

K14.0 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed (Pendent)

Control mode, Extended Coverage-Light Hazard (ECLH) flush, recessed and concealed sprinklers are ECLH sprinklers intended for use with a concealed piping system. Flush pendent types are
constructed with an operating element which extends a short distance below the ceiling. Upon actuation, the sprinkler deflector drops below the ceiling level to provide a proper water distribution.
Recessed pendent types consist of a sprinkler installed in a decorative recessed cup which reduces the protrusion of the sprinkler from the ceiling. Concealed pendent types incorporate a cover plate
which is heat activated and can be manually removed to prevent over-painting of the cover plate. All of these sprinkler types are intended for use in light hazard occupancies where attractive appearance
under a ceiling is desired.

K14.0 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed (Class 2015)

Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3413 14.0 Recessed Pendent SR 5 mm 3 Brass, Chrome, Polyester, NICOTEF 135°, 155°F (57°,68°C)
4

K14.0 Extended Coverage Light Hazard (ECLH), Flush, Recessed and Concealed, Quick Response (Class 2020)

Company Model K Type Response Element NPT (in.) Finishes Temp Ratings, °F(°C)
Victaulic V3414 14.0 Recessed Pendent QR 3 mm 3 Brass, Chrome, Polyester, NICOTEF 135°F (57°C)
4

Company Model Type Sprinklers FM Approved with Sprinkler Types


Victaulic V27 Guard V2703, V2704, V2707, V2708
Victaulic V27 Guard/Shield V2703, V2704 Upright automatic sprinklers

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide Page 13
Automatic Sprinkler Systems
Victaulic V34 Guard V3401, V3402, V3403, V3404, V3405, V3406, V3407, V3408
Victaulic V34 Guard/Shield V3401, V3402, V3403, V3404 Upright automatic sprinklers

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide
Automatic Sprinkler Systems

Victaulic Company, Box 31, Easton PA 18044

Model NPT Hose Assembly length Equivalent Length of 1 in.


in. ft (m) Schedule 40 Pipe,
ft (m)
Style 744 12 2.5 1.6
(750) (0.5)
Style 744 12 3.9 9.5
(1200) (2.9)
Style 744 12 5.6 13.6
(1700) (4.1)
Style 943 12 2.5 8.7
(750) (2.6)
Style 943 12 3.9 16.7
(1200) (5.1)
Style 943 12 5.6 22.5
(1700) (6.9)
Style 943 12 2.5 8.7
(750) (2.6)
Style 943 12 3.9 16.7
(1200) (5.1)
Style 943 12 5.6 22.5
(1700) (6.9)
Style 940 12 2.0 6.8
(610) (2.1)
Style 940 12 2.6 8.7
(790) (2.6)
Style 940 12 3.0 11.5
(915) (3.5)
Style 940 12 4.0 16.7
(1220) (5.1)
Style 940 12 5.0 20.6
(1525) (6.3)
Style 940 12 5.6 22.5
(1700) (6.9)
Style 940 12 6.0 24.0
(1830) (7.3)
Style 940 12 7.2 28.3
(2200) (8.6)
Style 940 12 8.5 34.5
(2600) (10.5)
Style 940 34 2.0 4.7
(610) (1.4)
Style 940 34 2.6 7.2
(790) (2.2)
Style 940 34 3.0 10.6
(915) (3.2)
Style 940 34 4.0 12.7
(1220) (3.9)
Style 940 34 5.0 17.0
(1525) (5.2)
Style 940 34 5.6 18.8
(1700) (5.7)
Style 940 34 6.0 19.8
(1830) (6.0)
Style 720 TestMaster II. Sizes 1, 1 4,1 2 and 2 in. NPT female threads, sizes 1 4,1 2 and 2 in. NPS grooved ends.
nominal orifice inserts. 5.6 and 8.0 nominal K-factor. Rated working pressure is 300 psi (2070 kPa).
1
1
Style 720P TestMaster II. Sizes 1, 1 4,1 2, and 2 in. NPT female threads. Equipped with a pressure relief valve set for 175 psi (1205 kPa)
cracking pressure.

RISER MANIFOLD ASSEMBLIES

These devices are intended to replace a field fabricated assembly of components, which normally include a shutoff valve, an
orifice made from an open sprinkler head, a sight glass, a water collection wastecone, a vane-type waterflow indicator and
interconnecting pipe and fittings. They are usually mounted aboveground and indoors where the water supply enters a
© 2008 FM Approvals LLC. All rights reserved.
May 2008 — Approval Guide
Automatic Sprinkler Systems
building.
Model Nominal Pipe End Rated working
Designation Size, in. connections pressure, psi (kPa) Nominal K-factors Remarks
175
747P 2, 3, 4, 6 Grooved 5.6, 8.0 a
(1208)
300
1
2
747 2, 2 , 3, 4, 6 Grooved 5.6, 8.0 b
(2070)
365
1
747M 2 2, 3 Grooved 5.6, 6.9, 8.0, 11.2 c, d
(2515)
365 5.6, 6.9, 8.0, 11.2.
747M 4, 6 Grooved c, d
(2515) 14.0, 16.8
a. Equipped with the Style 720P TestMaster II, with female NPT threaded end connections, with a pressure relief valve set for 175 psi (1208 kPa) cracking pressure.
b. Equipped with the Style 720 TestMaster II Alarm Tester with grooved ends, a vane type flow indicator, and a pressure gage and gage valve.
c. Riser manifold and sprinkler system alarm tester are one casting.
d. The 6.9 nominal k-factor is for use only with residential automatic sprinklers.

BRANCH LINE TESTERS

Line testers are installed on sprinkler system branch lines between the last sprinkler and its fitting. Opening a side outlet
allows water to flow through the tester. This simplifies and reduces the cost of testing and flushing system branch lines.
Product Nominal Pipe Size, Max Working Pressure,
Designation Description in. (mm) psi (kPa) Remarks
Series 751 Alarm Check Valve, 1 1 300 a, b, c
FireLock Grooved Ends 1 2,2,2 2,3,4,6 (2065)
76.1, 165.1 mm
Series 751 Alarm Check Valve, 300
4, 6 a, b, c
FireLock Flanged by Grooved (2065)

Series 756 Firelock Dry Pipe Valves, sizes 1 2,2,2 2, 3, 4, 6, and 8 in. NPS, grooved inlet and grooved outlet or flanged inlet and grooved outlet
in sizes 4, 6, and 8 in. NPS, vertical or horizontal orientation; sizes 76.1 and 165.1 mm NPS, grooved inlet and outlet. Consists of the Series
756 FireLock dry pipe valve, Style 753-A dry actuator, Series 749 Auto Drain (pressure operated relief valve), Series 748 Ball Check Valve,
and Series 729 Ball Drip Valve. Optional Series 757 or 757-P air maintenance device; It may include an optional accelerator, the Series 746.
300 psi (2069 kPa) rated working pressure, except for the 8 in. valves, which have a rated working pressure of 225 psi (1551 kPa). Series
756-LPA Firelock Dry Pipe Valves, sizes 11 2,2,21 2, 3, 4, 6, and 8 in. NPS, grooved inlet and grooved outlet or flanged inlet and grooved outlet
in sizes 4, 6, and 8 in. NPS, vertical or horizontal orientation; sizes 76.1 and 165.1 mm NPS, grooved inlet and outlet, vertical or horizontal
orientation. Consists of Series 756 FireLock dry pipe valve, Series 776 low pressure actuator for low pressure, nominally 10 psi, supervised
system pressure; Series 749Auto Drain (pressure operated relief valve), Series 748 Ball Check Valve, Series 729 Ball Drip Valve. It may
include an optional accelerator, the Series 746, and/or the Series 757 air maintenance device. 300 psi (2069 kPa) rated working pressure,
except for the 8 in. valves, which have a rated working pressure of 225 psi (1551 kPa). The Series 757-P Air Maintenance Trim Assembly is
an option used to control the system air pressure on dry pipe valves. All dry pipe valves offer the Series 75-W Water Column Drain Kit as an
option, which automatically drains water from the sprinkler systems and subsequently reseals to maintain air pressure in the system piping.
All dry pipe valves discussed above offer the Series 75-B supplemental alarm valve as an option recommended for systems where continuous
flow to the alarm port, which supplies flow to the water motor alarm, must be positively maintained.

ACCELERATORS AND EXHAUSTERS

An accelerator or exhauster, attached to a dry pipe valve, causes the valve to trip quickly upon sprinkler operation. These
devices operate when loss of system air pressure exceeds a predetermined rate. Unless otherwise noted in the listing, these
accelerators and exhausters have 175 psi (1205 kPa) rated working pressure.

Series 746 Accelerator, 300 psi (2070 kPa) rated pressure. For use with Series 756 Firelock Dry Pipe Valves and Series 758 Firelock
Actuated Valves.

Series 758 FireLock Automatic Water Control Valves. Includes the Series 753-A pneumatic actuator for a dry pilot sprinkler line.

Series 758-LPA FireLock Automatic Water Control Valves. Includes the Series 776 low pressure pneumatic actuator for a low pressure dry
pilot sprinkler line, nominally 10 psi.

Series 758 and Series 758-LPA available in sizes 1 2,2,2 2, 3, 4, 6, and 8 in. NPS, grooved inlet and outlet or flanged inlet and grooved outlet
in 4, 6, and 8 in. NPS, vertical or horizontal orientation; sizes 76.1 and 165.1 mm NPS, grooved inlet and outlet, vertical or horizontal
orientation. Both the Series 758 and 758-LPA include the Series 749 Auto Drain (pressure operated relief valve); the Series 755 manual pull
station; the Series 748 Ball Check; the Series 729 Ball Drip; the optional Series 757 or Series 757-P air maintenance devices for a dry pilot
sprinkler line. Rated working pressure is 300 psi (2069 kPa) except: for electric activation it is 175 psi (1207 kPa) with the ASCO Model No.
8210G207 solenoid valve; 300 psi (2069 kPa) with the Victaulic Series 753-E solenoid valve, except the 8 in. valves, which have a rated
working pressure of 225 psi (1551 kPa).

Series 769 Firelock NXT Deluge Valves with Dry Pilot Line Pneumatic Release. Sizes 11/2,2,2 2, 3, 4, 6 and 8 in. NPS. Grooved inlet and
grooved outlet, installed vertically. The system rated working pressure is 300 psi (2070 kPa). Major trim components consist of the following:

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide
Automatic Sprinkler Systems
Series 776 Low Pressure Pneumatic Actuator with Auto Vent pressure operated system air pressure relief valve
Series 749 Auto Drain pressure operated piston charge line water relief valve; Series 729 alarm line Drip Check Valve
Series 768 alarm line 3-Way Ball Valve for alarm/test/of
Series 768 dry pilot line Air Manifold Assembly with integral restrictor/screen/anti-flood ball check valve
Water Supply Main Drain/Flow Test Valve, size 2 in. with three 1 2
in. NPT outlets for gage and drain connections
System Main Drain Valve, size 2 in. with three 1 2
in. NPT outlets for gage and drain connections
Series 752 piston charge line Strainer/Check Valve/Restrictor assembly.

Optional system components include:

Regulated pilot line Air Maintenance Trim Assemblies


Series 757 or 757-P (with pressure switch) Air Maintenance Devices
System Sensor EPS10-2 alarm line pressure switch
System Sensor EPS40-2 pilot line system air pressure supervisory switch
Series 755 Manual Pull Station
Series 760 Water Motor Alarm
Series 705W water supply butterfly shutoff valve.

Series 769 Firelock NXT Deluge Valves with Wet Pilot Line Hydraulic Release. Sizes 11/2,2,2 2, 3, 4, 6 and 8 in. NPS. Grooved inlet and
grooved outlet, installed vertically. The system rated working pressure is 300 psi (2070 kPa). Major trim components consist of the following:

Series 749 Auto Drain pressure operated piston charge line water relief valve
Series 729 alarm line Drip Check Valve
Series 768 alarm line 3-Way Ball Valve for alarm/test/off
Water Supply Main Drain/Flow Test Valve, size 2 in. with three 1 2
in. NPT outlets for gage and drain connections
System Main Drain Valve, size 2 in. with three 1 2
in. NPT outlets for gage and drain connections
Series 752 piston charge line Strainer/Check Valve/Restrictor assembly.

Series 758-LPAFireLockAutomatic Water Control Valve, electric release, available in sizes 1 2,2,2 2, 3, 4, 6, and 8 in. NPS, grooved inlet and
grooved outlet, and flanged inlet and grooved outlet in sizes 4, 6, and 8 in. NPS, vertical or horizontal orientation; sizes 76.1 and 165.1 mm
NPS, grooved inlet and grooved outlet, vertical or horizontal orientation. The 758-LPAincludes the Series 776 pneumatic actuator for low
pressure, nominally 10 psi, supervised system pressure. Series 749 Auto Drain (pressure operated relief valve); the Series 755 manual pull
station; the Series 748 Ball Check; the Series 729 Ball Drip; the optional Series 757 or Series 757-P air maintenance devices for a dry pilot
sprinkler line. Rated working pressure is 300 psi (2069 kPa) except: for electric activation it is 175 psi (1207 kPa) with the ASCO Model No.
8210G207 solenoid valve; 300 psi (2069 kPa) with the Victaulic Series 753-E solenoid valve, except the 8 in. valves, which have a rated
working pressure of 225 psi (1551 kPa). The Series 75-D Water Column Drain Kit is an option, which automatically drains water from the
sprinkler system and subsequently reseals to maintain air pressure in the system piping.

Series 769 Firelock NXT Single-Interlocked Valve with Electric Release. Sizes 1 2,2,2 2, 3, 4, 6 and 8 in. NPS. The system rated working
pressure is 300 psi (2070 kPa). Grooved inlet and grooved outlet, installed vertically. Major trim components consist of the following:

Series 753-E normally closed solenoid valve


Series 749 Auto Drain pressure operated piston charge line water relief valve
Series 748 anti-flood Ball Check Valve
Series 729 alarm line Drip Check Valve
Series 768 alarm line 3-Way Ball Valve for alarm/test/off
Water Supply Main Drain/Flow Test Valve, size 2 in. with three 1 2
in. NPT outlets for gage and drain connections
System Main Drain Valve, size 2 in. with three 1 2
in. NPT outlets for gage and drain connections
Series 752 piston charge line Strainer/Check Valve/Restrictor assembly.

Optional system components include:

System Sensor EPS10-2 alarm line pressure switch


System Sensor EPS40-2 system air pressure supervisory switch
Series 755 Manual Pull Station
Series 760 Water Motor Alarm
Series 705W water supply butterfly shutoff valve.

All preaction sprinkler systems discussed above offer the Series 75-B supplemental alarm valve as an option recommended for systems
where continuous flow to the alarm port, which supplies flow to the water motor alarm, must be positively maintained. Some Preaction
Sprinkler Systems are available factory assembled in the Victaulic Series 745 Fire-Pac enclosure, a cabinet containing all system components
and accessories, and requires only the connection to the water supply inlet, water outlet (to system), main drain, the alarm and detection
connections, and the electrical power supply. The Series 745 Fire-Pacs may be connected to Notifier AFP-200 Pro-grammable Analog Fire
control with software no. AFP2R2.42 or System Sensor PDRP-1001 fire control with operating system firmware revision level A. The AFP-200
control contains FMM-1 Module with a signaling line circuit which can be configured to meet Styles 4, 6 or 7 wiring performance as described
in NFPA72. The addressable panels utilize model XP-10M module which may be configured at the factory to monitor the Fire-Pac cabinet and
valve station. Optional LED Interface Module 4XTM and Relay Module RTM-8 provide outputs for auxiliary applications.

Double-interlocked, uses a Series 758-DPA FireLock Automatic Water Control Valve controlled by pneumatic dry pilot line pressure and

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide
Automatic Sprinkler Systems
1 1
pneumatic system pressure. Sizes 1 2,2,2 2, 3, 4, 6, and 8 in. NPS, grooved inlet and grooved outlet, and flanged inlet and grooved outlet in
sizes 4, 6, and 8 in. NPS, vertical or horizontal orientation; sizes 76.1 and 165.1 mm NPS, grooved inlet and outlet, vertical or horizontal
orientation. Includes the Series 798 pneumatic/pneumatic actuator for low pressure, nominally 10 psi, supervised system pressure, a single
component containing both pneumatic releases; Series 749 Auto Drain (pressure operated relief valve); Series 755 manual pull station;
optional Series 757 or 757-P air maintenance devices. Rated working pressure is 300 psi (2069 kPa), except for the 8 in. valves, which have a
rated working pressure of 225 psi (1551 kPa).
Double-interlocked Series 758 FireLock Automatic Water Control Valve, pneumatic/electric release, electric/electric release, and
1 1
pneumatic/electric/electric releases. Sizes 1 2,2,2 2, 3, 4, 6, and 8 in. NPS, grooved inlet and outlet, and flanged inlet and grooved outlet in
sizes 4, 6, and 8 in. NPS, vertical or horizontal orientation; sizes 76.1 and 165.1 mm NPS, grooved inlet and outlet, vertical or horizontal
orientation. Compatible FM Approved automatic release control panel capable of cross-zone operation with appropriately sized battery to
provide 90 hours of emergency power and FMApproved pressure alarm switch. Only FMApproved fixed temperature, heat sensitive devices
shall be used in the release system and in the sprinkler piping. Series 749 Auto Drain (pressure operated relief valve); Series 755 manual pull
station; optional Series 757 or 757-P air maintenance devices; rated working pressure for electric activation is 175 psi (1207 kPa) with the
ASCO Model No. 8210G207 solenoid valve; 300 psi (2069 kPa) with the Victaulic Series 753-E solenoid valve, except the 8 in. valves, which
have a rated working pressure of 225 psi (1551 kPa).

Series 769 Firelock NXT Double-Interlocked Valve with Electric-Pneumatic/Electric Release for Cross-Zoned Control Panel. Sizes 1 1 2,2, 21 2,
3, 4, 6 and 8 in. NPS. Grooved inlet and grooved outlet, installed vertically. The system rated working pressure is 300 psi (2070 kPa). Major
trim components consist of the following:

Series 753-E normally closed solenoid valve

System Sensor EPS40-2 system air pressure supervisory switch


Series 749 Auto Drain pressure operated piston charge line water relief valve
Series 748 anti-flood Ball Check Valve
Series 729 alarm line Drip Check Valve
Series 768 alarm line 3-Way Ball Valve for alarm/test/off
Water Supply Main Drain/Flow Test Valve, size 2 in. with three 1 2
in. NPT outlets for gage and drain connections
System Main Drain Valve, size 2 in. with three 1 2
in. NPT outlets for gage and drain connections
Series 752 piston charge line Strainer/Check Valve/Restrictor assembly.

Optional system components include:

System Sensor EPS10-2 alarm line pressure switch


Series 755 Manual Pull Station
Series 760 Water Motor Alarm
Series 705W water supply butterfly shutoff valve

Figure USP2*. Resilient Seated Gate Valves. 200 psi (1380 kPa) rated working pressure. Available with the following end connections.
1
2 2, 3, 4, 6, 8, 10, 12 Flanged
1
2 2, 3 Threaded
3, 4, 6, 8, 10, 12 Standardized Mechanical Joint
3, 4, 6, 8, 10, 12 Standardized Mechanical Joint by Flanged
4, 6, 8, 10, 12 Standardized Mechanical Joint by Tapping Flange
1
2 2, 3, 4, 6, 8, 10, 12 Slip – On
4, 6, 8, 10, 12 Slip – On by Flange

*Bonnet with indicator post flange.


**Rated Working Pressure 250 psi (1724 kPa).

AquaGrip end connections FM Approved for use with FM Approved PVC, HDPE and ductile iron pipe. 10 and 12 in. NPS AquaGrip end
connections limited to 160 psi (1105 kPa) rated working pressure when used with HDPE pipe.
Figure 771. Resilient Seated Gate Valve, 3, 4, 6 and 8 in. NPS. 200 psi (1380 kPa) rated working pressure. Available with the following end
connections:

3, 4, 6, 8 Grooved

Figure 771H. Resilient Seated Gate Valve. Sizes 21 2 through 12 in. NPS and 165.1 mm DN, 250 psi (1725 kPa) rated working pressure.
Available with the following end connections:

1
2 2, 3, 4, 6, 8, 10, 12, (165.1 mm) Grooved

Figure 771F. Resilient Seated Gate Valve. Sizes 21 2 through 12 in. NPS and 165.1 mm DN, 250 psi (1725 kPa) rated working pressure.
Available with the following end connections:

1
2 2, 3, 4, 6, 8, 10, 12, (165.1 mm) Grooved × Flanged

Figure 772. Resilient Seated Gate Valve. 3, 4, 6 and 8 in. NPS. 200 psi (1380 kPa) rated working pressure.Available with the following end
connections:
3, 4, 6, 8 Grooved

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide
Automatic Sprinkler Systems
Figure 772H. Resilient Seated Gate Valve. Sizes 21 2 through 12 in. NPS and 165.1 mm DN, 250 psi (1725 kPa) rated working pressure. All
valves are available with an operating nut or indicator post flange with operating nut. Available with the following end connections:
1
2 2, 3, 4, 6, 8, 10, 12, (165.1 mm) Grooved

Figure 772F. Resilient Seated Gate Valve. Sizes 21 2 through 12 in. NPS and 165.1 mm DN, 250 psi (1725 kPa) rated working pressure. All
valves are available with an operating nut or indicator post flange with operating nut. Available with the following end connections:
1
2 2, 3, 4, 6, 8, 10, 12, (165.1 mm) Grooved × Flanged

Model Product Nominal Pipe Rated Working Remarks


Number Type Size Pressure,psi
in. (mm) (kPa)
1
Series 702 Butterfly Valve, 2 2,3,4,6,8,10 175 a, b, c
Grooved Ends (1205)
1 1
Series 728 Ball Valve, 1, 1 4,1 2, 2 350 a, b, c
Threaded and (2415)
Grooved Ends
1
Series 705W Butterfly Valve, 2 2,3,4,5,6,8,10,12 300 a, b, c
Grooved Ends (65, 76.1, 80, 100, 125, (2070)
139.7, 150, 165.1, 200,
250, 300)
Series 774
Series 773 Wall Type
Style 722. 1 2, 3 4, in., 600 psi (4135 kPa) rated working pressure; 1 through 2 in., 500 psi (3445 kPa) rated working pressure.

SINGLE CHECK VALVES

Single check valves are used in fire protection systems to allow waterflow in one direction only. Typical applications are at
connections between public water supplies and private fire service systems, at the discharge from fire pumps, at gravity tank
connections and at fire service pumper connections.
Valves identified in the listing by a single asterisk (*) have side covers; valves identified by a double asterisk (**) have no
removable covers; others have top covers. Clearance must be provided for side-cover valves to permit clapper removal.
Valves without covers must be removed from the system for clapper replacement or repair. Unless otherwise noted in the
listing, these valves have 175 psi (1205 kPa) rated working pressure.
Product Nominal Pipe Max Working Pressure,
Description Remarks
Designation Size, in./ mm psi (kPa)
Swing Check Valve, 4, 5, 6, 8, 10, 12 250
Style 717 a
Cut Groove 139, 165 mm (1725)
Swing Check Valve, 4, 5, 6, 8, 10, 12 250
Style 717R a, b
Cut Groove 139, 165 mm (1725)

Remarks

a. For use in horizontal and vertical installations.


b. With trim package.

Product Valve Size Flow Rate,gal/min Friction Loss, psi


3
Designation in./ mm (dm
/min) (kPa)
750 3.53
Style 717* 4
(2840) (24)

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide Page 19
Automatic Sprinkler Systems
1000 1.97
Style 717* 5
(3875) (14)
1500 2.00
Style 717* 6
(5675) (14)
3000 2.31
Style 717* 8
(11 625) (16)

Model 168-205.
Series 760 Water Motor Alarm.

GROOVED COUPLINGS

Grooved couplings are used to join pipe and fittings in both wet and dry sprinkler systems. Unless otherwise noted, these couplings are intended to
provide some flexibility in piping systems. Typical applications are in sprinkler risers, in feed mains passing through walls from one building area to
another, in locations subject to earthquakes, in the discharge line from aboveground pump suction tanks, in new connections to existing feed mains
and in air or water fire service lines subject to excessive vibration or difficult alignment.
Unless otherwise noted, these couplings are limited to use with rolled or cut groove-ended pipe, valves and fittings, at a minimum rated working
pressure of 175 psi (1205 kPa) and are suitable for aboveground service. Higher rated pressures are noted in the text of the listing. Selection of
pipe schedules for use with grooved pipe couplings should be made according to applicable FM Global Property Loss Prevention Data Sheets
installation standards. These pipe schedules determine system pressure ratings and may take precedence over the higher rated working
pressures listed for some couplings.
Installation must be made according to the manufacturer’s instructions and requirements. Where couplings are used to join FM Approved pipe, the
pipe manufacturer’s installation instructions and requirements must also be observed. Grooves should be made according to ANSI/AWWA C606
(latest edition), ‘‘Grooved and Shouldered Joints’’, unless otherwise specified.
FM Approved grooved pipe couplings joining steel pipe may be used in underground service, subject to the installation restrictions placed upon the
pipe and to the coupling manufacturer’s recommendations and requirements.
Unless otherwise stated in the listing, these couplings have been evaluated for a maximum ambient temperature of 225°F (107°C), suitable for use
in normal warehouse protection. For special applications, temperatures, or environments, the manufacturer’s recommendations and requirements
are to be followed.

Grooved Couplings, Standard — Flexible

These couplings join pipe, valves or fittings having equal nominal-sized diameters.
Product Nominal Pipe Pipe Max Working
Designation Size, in. Ends Remarks Pressure, psi
(kPa)
1 1
75 1 4,1 2, 2 Rolled Groove a, e, x, aa 175
(1205)
1 1
1 4,1 2,2 ’’ e, h, aa 300
(2070)
1
1 2,2 ’’ t, aa 300
(2070)
1 1 1
1 4,1 2,2,2 2,3,4 ’’ a, e, g, j, k, u, w, z, 300
aa, ab (2070)
1 1 1
1 4,1 2,2,2 2, ’’ o, q, s, v, y, aa 300
3, 4, 6 (2070)
1 1
1 2,2,2 2,3 ’’ a, e, p, aa 175
(1205)
1 1
1 2,2,2 2,3 ’’ a, e, l, aa 300
(2070)
1 1
1 2,2,2 2,3,4 ’’ a, e, aa 175
(1205)
6 ’’ e, s, aa 175
(1205)
6 ’’ a, e, z, aa 300
(2070)
3, 4 ’’ e, s, aa 300
(2070)
3, 4, 6, 8 ’’ a, e, i, v, y, aa 300
(2070)
1-8 Cut Groove a, c, e, aa 500
(3445)
3.0 Rolled Groove b, d, e 300
(2070)
1 1
1 2,2,2 2, ’’ a, d, e, aa 500
3, 4, 5, 6, 8 (3445)
(kPa)
5 Cut Groove a, c, e 300
(2070)
6 ’’ a, c, e 400
(2760)

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide Page 20
Automatic Sprinkler Systems
8 ’’ a, c, e 450
(3105)
10, 12 Cut Groove a, b, c, e 250
Rolled Groove (1725)
76, 165 mm Cut Groove c, e, n 300
Rolled Groove (2070)

*For installation where greater rigidity of pipe system is required. Not for use as flexible joints in locations subject to earthquake.

a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket (green stripe). For use with standard lubricant or dry lubricant.
e. Also available with Tri-Seal EPDM gasket. Recommended by the manufacturer for dry systems. For use with standard lubricant or dry lubricant. f. For use with Allied Tube & Conduit ‘‘Dyna-
Flow’’, Northwest ‘‘EZ-Flow’’ and Allied ‘‘Super-Flo’’ non-threadable Lightwall pipe, in sizes up to 4 in. NPS. g. For use with Allied Tube & Conduit ‘‘BLT’’ threadable Thinwall pipe, in 6 in. NPS size.
h. For use with Allied Tube & Conduit ‘‘Dyna-Thread’’ threadable Thinwall pipe.
i. For use with Wheatland WLS.
j. For use with Bull Moose ‘‘Ultra-EDDY’’ Schedule 5 pipe.
l. For use with Northwest ‘‘EZ-flow’’ Pipe in 6 in. NPS size.
m. For use with IDOD Systems Sch. 5 Pipe.
n. For use with BS 1387 medium and heavy wall pipe.
o. For use with Youngstown Tube Co. ‘‘Fire-Flo’’ non-threadable Lightwall steel sprinkler pipe.
p. For use with Youngstown Tube Co. ‘‘EZ-Thread’’ threadable Thinwall steel sprinkler pipe.
q. For use with Wheatland Tube Co. ‘‘Mega-Flow’’ non-threadable Lightwall pipe.
r. For use with Wheatland Tube Co. ‘‘Mega-Thread’’ threadable Thinwall pipe.
s. For use with Wheatland Tube Co. ‘‘WLS’’ threadable Thinwall pipe.
t. For use with Wheatland Tube Co. ‘‘MLT’’ threadable Thinwall pipe.
u. For use with Wheatland Tube Co. ‘‘WST’’ Schedule 5 non-threadable Lightwall pipe.
v. For use with IDOD’s Gal-7 and Gal-Flo pipe.
w. For use with Bull Moose ‘‘EDDY-flow’’ non-threadable Lightwall pipe.
Nominal Pipe Pipe Max Working

Product
Designation Size, in. Ends Remarks Pressure, psi
(kPa)
1
005* 1 4-4 Rolled Groove a, c, g, k, l, t 350
(2415)
5-8 ’’ a, c, g, k 300
(2070)
1 1 1
005H* 1 4,1 2,2,2 2,3,4,6 ’’ i, m, o, q, s, z, aa 300
(2070)
1 1 1
1 4,1 2,2,2 2,3 ’’ a, k, p, aa 175
(1205)
1 1
1 4,1 2,2 ’’ e, i, aa 300
(2070)
1 1
1 2,2,2 2,3,4 ’’ d, e, u, aa 300
(2070)
1 1 1
1 4,1 2,2,2 2, 3 Cut Groove a, c, k, aa 350
(2415)
4-8 ’’ a, c, k, aa 300
(2070)
1 1
005H* 1 2,2,2 2, 3, 4 Rolled Groove a, k, aa 175
(1205)
76, 108, 133, ’’ a, b, e, k, n, aa 350
139.7, 159, 165 mm (2415)
1 1
005H* 1 2,2,2 2,3,4 ’’ a, e, w, r, aa 300
(2070)
1
1 4-2 ’’ a, c, g, k, aa 300
(2070)
1 1
1 4-1 2 ’’ a, c, g, k, l, o, p, q, aa 175
(1205)
2-3 ’’ a, k, l, p, aa 175
(1205)
1 1 1
1 4,1 2,2,2 2 ’’ a, *, k, l, o, q, t, aa 175
(1205)
125A JIS, 200A JIS ’’ a, e, f, k 300
(2070)
3-8 ’’ a, e, k, y, aa 300
(2070)
6 ’’ a, e, r, aa 300
(2070)
1
009* 1 4-4 Rolled Groove c, d, g, i, j, k, l, m, o 300
Cut Groove p, q, r, s, x, y, z (2070)
aaa, bb, cc, dd, ee, ff, gg
1
009V* 1 4-4 Rolled Groove b, c, g, k 300
Cut Groove (2070)
07* 267, 318 mm Rolled Groove e, k, f 175
Cut Groove (1205)
07* 250A JIS, 300A JIS Rolled Groove e, f, k 300
Cut Groove (2070)
Nominal Pipe Max Working Pressure,
Product
Pipe Ends Remarks
Designation Size, in. psi (kPa)
300
© 2008 FM Approvals LLC. All rights reserved.
May 2008 — Approval Guide Page 21
Automatic Sprinkler Systems
1
2×1 2 through 6×4 ’’ c, n, w
(2070)
76 mm by 2, 3 by 76 mm,
Rolled Groove, 300
Figure 716 4 by 76 mm, 139 by 4, c, x, y
Cut Groove (2070)
165 by 5

a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
b. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. or larger – 0.188 in. (5 mm) wall.
c. With EPDM gasket (green stripe). For use with standard lubricant or dry lubricant.
e. For use with Allied Tube & Conduit ‘‘BLT’’ threadable Thinwall pipe.
f. For use with Allied Tube & Conduit ‘‘Dyna-Thread’’ threadable Thinwall pipe.
g. For use with Allied Tube & Conduit ‘‘Super-Flo’’ non-threadable Lightwall pipe.
h. For use with Allied Tube & Conduit ‘‘Dyna-Flow’’ non-threadable Lightwall pipe.
m. For use with 4 in. Northwest ‘‘EZ-Flow’’ pipe.
n. For use with Welded Tube–Berkeley LLC ‘‘Steady-Flow’’ pipe.
o. For use with Youngstown ‘‘Fire-Flo’’ Pipe.
p. For use with Youngstown ‘‘EZ-Thread’’ Pipe.
q. For use with Wheatland Tube Co. ‘‘Mega-Flow’’ non-threadable Lightwall pipe.
r. For use with Wheatland Tube Co. ‘‘Mega-Thread’’ threadable Thinwall pipe.
s. For use with Wheatland Tube Co. ‘‘WLS’’ threadable Thinwall pipe.
t. For use with Wheatland Tube Co. ‘‘MLT’’ threadable Thinwall pipe.
u. For use with Wheatland Tube Co. ‘‘WST’’ Schedule 5 non-threadable Lightwall pipe.
v. For use with IDOD’s Gal-7 and Gal-Flo pipe.
w. For use with Bull Moose Tube Co. ‘‘EDDY-flow’’ non-threadable Lightwall pipe.
x. For use with BS 1387 Medium and Heavy pipe.
y. For use with ISO 4200 steel sprinkler pipe.
Nominal Pipe Max Working Pressure,

Product
Designation Size, in. Pipe Ends Remarks psi (kPa)
750 1 Cut Groove a, d 350
2×1 2; (2415)
1
2 2×2;
1
3×2, 2 2;
1
4×2, 2 2,3;
5×4;
6×4, 5;
8×6
750 1 Rolled Groove c, d 350
2×1 2; (2415)
1
2 2×2;
1
3×2, 2 2;
750 1 ’’ c, d, f 200
4×2, 2 2,3; (1380)
5×4;
6×4, 5;
8×6
300
750 2-4 ’’ g, i, k (2070)
750 1 ’’ d, h 300
2×1 2; (2070)
1
2 2×2;
1
3×2, 2 2; 4×2, 21 ,3
2

a. Min schedule cut groove pipe to be joined: 6 in. or smaller – Schedule 40; 8 in. or larger – Schedule 30.
c. Min schedule rolled groove pipe to be joined: 6 in. or smaller – Schedule 10S; 8 in. or larger – 0.188 in. (5 mm) wall.
d. With gasket E (green stripe), H (white stripe) or L (solid red), using standard gasket lubricant or Vic-Plus dry lubricant.
f. When joining Allied Tube & Conduit ‘‘Super-Flo’’ Lightwall non-threadable pipe, up to 4 in. dia., 200 psi (1380 kPa) limit.
g. With Allied Tube & Conduit ‘‘Dyna-Flow.’’
h. For use with Central 7 pipe.
i. For use with Western ‘‘Fire-Flow’’ and ‘‘Fire-Thread’’ pipe.
j. For use with Bull Moose ‘‘EDDY-Flow’’ pipe.
Outlet Nominal Pipe Max Rated Pressure,
Product
Remarks
Designation Connection Size, in. psi (kPa)
Mechanical
300
920 Branch Outlet 4×21 2
,3 c, k
(2070)
(Grooved Outlet)
108 mm × 76 mm,
Mechanical
165 mm × 76 mm 300
920 Branch Outlet c
165 mm × 89 mm (2070)

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide Page 22
Automatic Sprinkler Systems
(Grooved Outlet)
165 mm x 114 mm
108 mm × 76 mm,
Mechanical
165mmx76mm 300
920 Branch Outlet c
165 mm × 89 mm (2070)
or ISO or BSP)
165 mm x 114 mm
Mechanical
300
920 Branch Outlet 6×4, 3 c, m
(2070)
(FNPT)
Mechanical
300
920 Branch Outlet 6×4, 3 c, m
(2070)
(Grooved Outlet)
Mechanical
300
1
1
920N Branch Outlet 2×1, 1 4,1 2 c, k, l
(2070)
(Grooved Outlet)

Couplings or Fittings, Side Outlet, Flexible

These couplings allow installation of a perpendicular branch line of reduced size, while joining inline pipes of equal diameters. These fittings bolt
over a hole in the run pipe, and allow installation of a perpendicular branch line of reduced size.

Style 72. Flexible outlet coupling for grooved pipe.

Nominal Pipe Max Rated


Size, in. Outlet Remarks Pressure, psi
Connection (kPa)
1 1 3
1 2× 2, 4, 1 NPT internal a, c 500
(3445)
1 3
2× 2, 4 ’’ a, c 500
(3445)
2×1 Grooved, NPT external, a, c 500
NPT internal (3445)
1 1 3 1
2 2× 2, 4,1,1 4 NPT internal a, c 500
(3445)
1 1
2 2×1 2 Grooved, NPT external a, c 500
(3445)
3
3× 4 NPT internal a, c 500
(3445)
3×1 Grooved, NPT external, a, c 500
NPT internal (3445)
1
3×1 2 Grooved, NPT external a, c 500
(3445)
3
4× 4 NPT internal a, c 500
(3445)
4×1 Grooved, NPT external a, c 500
(3445)
1
4×1 2 NPT internal b, c 400
(2760)
4×2 Grooved, NPT external, b, c 400
NPT internal (2760)
1
6×1, 1 2 NPT internal b, c 400
(2760)
6×2 Grooved, NPT external b, c 400
(2760)

a. Max rated pressure limited to 300 psi (2070 kPa) when joining Schedule 10S rolled groove-ended pipe.
b. Max rated pressure limited to 200 psi (1380 kPa) when joining Schedule 10S rolled groove-ended pipe.
c. With gasket E (green stripe), H (white stripe) or L (solid red).

m. For use with Youngstown ‘‘Fire-flo’’, ‘‘EZ-Thread’’ pipe, and Welded Tube–Berkeley LLC ‘‘Steady-Flow’’ pipe.
q. For use with Wheatland Tube Co. ‘‘Mega-Flow’’ non-threadable Lightwall pipe.
r. For use with Wheatland Tube Co. ‘‘Mega-Thread’’ threadable Thinwall pipe.
s. For use with Wheatland Tube Co. ‘‘WLS’’ threadable Thinwall pipe.
t. For use with Wheatland Tube Co. ‘‘MLT’’ threadable Thinwall pipe.
u. For use with Wheatland Tube Co. ‘‘WST’’ Schedule 5 non-threadable Lightwall pipe.
v. BS 1387 pipe, medium and heavy wall or ISO 4200 pipe.

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide Page 23
Automatic Sprinkler Systems
Style 741 Vic-Flange. For working pressures up to 250 psi (1725 kPa). For use with pipe conforming to the following min schedules:
Cut groove-ended - Schedule 40, 6 in. or smaller; Schedule 30, 8 in. or larger.
Rolled groove-ended - Schedule 10S, 6 in. or smaller; 0.188 in. (5 mm) wall, 8 in. or larger. Also for use with Central 7 and Wheatland
‘‘Mega-Flow’’ pipe, 2-6 in. sizes.

Product Nominal Pipe


Designation Fitting Description Size, in.
1
741 Vic-Flange 2, 2 2,3,4,5,6,8,10,12
ANSI Class 125, 150
741 Vic-Flange 165 mm

Style 743 Vic-Flange. For working pressures up to 500 psi (3445 kPa). For use with pipe conforming to the following min schedules:
Cut or rolled groove-ended - Schedule 40, 6 in. or smaller; Schedule 30, 8 in. or larger.

1
743 Vic-Flange 2 2,3,4,5,6,8,10,12
ANSI Class 300

Style 744 Vic-Flange. For working pressures up to 175 psi (1205 kPa). For use with pipe conforming to the following min schedules:
Cut groove-ended - Schedule 40, 6 in. or smaller; Schedule 30, 8 in. or larger.
Rolled groove-ended - Schedule 10S, 6 in. or smaller; 0.188 in. (5 mm) wall, 8 in. or larger.
Also FM Approved for use on Allied ‘‘XL’’, Dyna-Flow, EZ-Flow and Super-Flo Lightwall pipe in appropriate sizes.

1
744 Vic-Flange 2, 2 2,3,4,5,6,8
ANSI Class 125, 150

PIPE FITTINGS

These fittings are suitable for interconnecting piping, valves and other components in both wet and dry automatic sprinkler systems. Installation
should be according to applicable sprinkler system fabrication rules. These rules limit the minimum size of sprinkler piping to 1 in., nominal.
FMApproved pipe fittings of smaller sizes are intended for use as valve trim, gauge connections, and for other peripheral service. The water flow
path of the sprinkler system cannot be designed using smaller sizes than 1 in., nominal. Unless otherwise noted in the listing, these fittings have
175 psi (1205 kPa) rated working pressure.
Threaded connections on fittings can be made to FM Approved threadable thinwall pipe or to Schedule 40 pipe. Refer to the ‘‘Steel Pipe’’ listings
for a summary of the various types of FMApproved steel pipe suitable for threading or grooving.
The fittings manufacturer’s installation instructions must be observed in all cases. When connections are made to FM Approved pipe, the pipe
manufacturer’s installation instructions must also be followed.
Unless otherwise stated below, the maximum ambient temperature to which these fittings should be subjected is 225°F (107°C).

Standard grooved-end fittings for use with Victaulic FM Approved grooved couplings.

Product Fitting Nominal Pipe Max Working Pressure,


Designation Description Size, in. psi (kPa)
3
4
through 12
500
76, 108, 133,
(3445)
139.7, 159, 165 mm
10 90° Elbow
300
216, 267, 318 mm
(2070)
1
2 2 through 6
10D 90° Elbow
with drain outlets
3
4
through 12
500
76, 108, 133, 139.7,
(3445)
159, 165 mm
11 45° Elbow
300
216, 267, 318 mm
(2070)
1 1 1
12 22 2° Elbow 1 4,1 2,4
1
13 111 1 1
4° Elbow 1 4,1 2,2,2 2,3,4,6,8
3
4
18 90° Adapter Elbow through 6
3
4

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide Page 24
Automatic Sprinkler Systems
19 45° Adapter Elbow through 6
3
4 through 12
500
20 Tee 76, 108, 133, 139.7,
(3445)
159, 165 mm
5×8;
21 Bullhead Tee
6×8
3
1
2× 4,1,2 2×1;
3×1, 2;
1
1
4×1, 1 2,2,2 2,3;
25 Reducing Tee
1
5by2 2
165 mm×114 mm
114 mm×76 mm
Standpipe Tee
1
1
27 4×2 2;6
×2 2
(NPT Branch)
3
4
through 4;
3
1
2× 4,1,2 2×1;
Adapter Tee 3×1, 2;
29 1
1
(NPT Branch) 4×1, 1 2,2,2 2,3;
5 1
×2 2
6×2, 3
30 Lateral 2, 3, 4, 8
2, 3, 4
35 Cross
76, 165 mm

Victaulic FireLock™ CPVC SDR 13.5 pipe and Schedule 40 and 80 fittings joined by the solvent cement method using either of the following one-step solvent
cements: Victaulic Model #899, Spears FS-5, IPEX BM-5, and Tyco TFP-500. For joints using threaded fittings (plastic to plastic, plastic to metal), Teflon tape is
recommended. The pressure rating is 175 psi (1205 kPa) at 150°F (66°C).

Approved for exposed use when all of the following criteria are met:
Occupancy must be covered in Data Sheet 3-26, Fire Protection Water Demands for Nonstorage Sprinklered Properties, Table 2,
Section L, Miscellaneous Non-manufacturing.
Sprinklers must have quick response thermal sensing elements.
Sprinkler systems must be wet pipe type.

Designation Product Description Nominal Pipe Size, in.


N/A SDR 13.5 pipe 3 1
1
4,1,1 4,1 2, and 2
810 90° Elbow (All Socket) 3 1
1
4,1,1 4,1 2, and 2
811 45° Elbow (All Socket) 3 1
1
4,1,1 4,1 2, and 2
812 Reducing 90° Elbow (All Socket) 1 × 34
3 1
4 × 2
1
Sprinkler Head 90° Elbow 1× 2
813
3
(Socket × Brass* FIPT) 1× 4
11 1
2

3
1
4 × 2
1
Sprinkler Head 90° Elbow 1× 2
814
3
(Socket × SR FIPT)B 1× 4
11 1
2

Equal Tee
820 3 1
1
4,1,1 4,1 2, and 2
(Soc × Soc × Soc)

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide Page 25
Automatic Sprinkler Systems
3
4 ×3 1
2
4 ×
1
1×1× 2
Sprinkler Head Tee 1×1×1
821
1 1 1
(Soc × Soc × Brass FIPT*) 1 4 ×1 4 × 2
1
1 1 2
1 2×1 2×
2 × 2 × 12
Sprinkler Head Tee
822 1 × 12× 1
(Soc × Brass FIPT* × Soc)
3
3 1
4 × 4 × 2
3 1
1× 4 × 2
1
1×1× 2
1×1×1
1 1
Sprinkler Head Tee 1 4 ×1× 2
823
1 1 1
(Soc × Soc × SR FIPT) 1 4 ×1 4 × 2
1 1 1
1 2 ×1 4 × 2
1 1 1
1 2 ×1 2 × 2
1 1
2×1 2× 2
2 × 2 × 12
Sprinkler Head Tee
824 1 × 12× 1
(Soc × SR FIPT × Soc)
3 3
4 × 4 ×1
3 3
1× 4× 4
1 × 34× 1
3
1×1× 4
1 3
1 4 ×1× 4
1
1 4 ×1×1
1 1
1 4 ×1×1 4
1 1 3
1 4×1 4× 4
11 1
4×1 4×1
Reducing Tee
1 1 1
825 1 4 ×1 4 ×1 2
(Soc × Soc × Soc)
1 1 3
1 2 ×1 4 × 4
1 1
1 2 ×1 4 ×1
1 1 3
1 2×1 2× 4
11 1

2×1 2×1
1
1 1
1 2×1 2×1 4
11 1

2×1 2×2
3
4
2×2×
2×2×1
× 2 × 11
2 2

Tee, Reducing, Sidewall


826 1 1
2
(SR FIPT × SR FIPT × Soc) 2
× x1
830 Coupling (Soc × Soc) 3 1
1
4,1,1 4,1 2, and 2
3
1× 4
3
1 4
1 4 ×
1
1 4 ×1

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide Page 26
Automatic Sprinkler Systems
1 3
1 2 × 4
1
1 2×1
831 Reducer Coupling (Soc × Soc)
1 1
1 2×1 4
2 × 34
2×1
1
2×1 4
2 × 11
2

1
1 4
Grooved Coupling Adapter (Grv ×
1
1
832 2
Soc)
2
Product Nominal Pipe
Description Size, in. Remarks
90° Long Radius Elbow 4 through 12 Flg and Flare
Return Bend 4 through 12 Flg, Flg

*Min thickness in 4 in. size is Class 51.

B-Bell End, S-Spigot End, TJ-Tyton Joint, MJ-Mechanical Joint, TRF-TR-Flex Joint, Flg-Flanged End, PE-Plain End.

MJ Field Lok Retainer Gland for ductile iron pipe. Used to secure spigot ends of ductile iron pipe into standardized mechanical joint-ended fitting or other components.
Rated Working
Product Nominal Pipe Pressure, psi
Description Size, in. (kPa)
MJ Field Lok 4, 6, 8, 10, 12 175
(1205)

Cast Ductile iron grooved-end pipe fittings for use with cast iron and ductile iron pipe in underground fire service mains connected with Style 31 pipe couplings.

Product Fitting Nominal Pipe


Description Description Size, in.
100-C 90° Long Radius Elbow 4, 6, 8, 10, 12
1
12-C 22 2° Elbow 4, 6, 8, 10, 12
1
13-C 11 4° Elbow 4, 6, 8, 10, 12
10-CR Reducing Elbow 4×3;
6×3, 4;
8×4, 6;
10×6, 8
25-C Reducing Tee 4×3;
6×4;
8×4, 6;
10×4, 6, 8;
12×4, 6, 8, 10
30-C Lateral 4, 6, 8, 10, 12
35-C Cross 4, 6, 8, 10, 12
50-C Reducer 4×3;
6×4;
8×4, 6;
10×4, 6, 8;
12×4, 6, 8, 10
60-C Cap 4, 6, 8, 10, 12
10-C 90° Elbow 4, 6, 8, 10, 12
11-C 45° Elbow 4, 6, 8, 10, 12
20-C Tee 4, 6, 8, 10, 12

Products listed below are rated at 250 psi (1725 kPa)

10-C 90 Elbow 14, 16


11-C 45 Elbow 14, 16
20-C Tee 14, 16
60-C Cap 14, 16

Style 341 Vic-Flange. For use with cut grooved cast iron or ductile iron pipe in underground installations. With Grade H or M gasket
material.

341 Vic-Flange 4, 6, 8, 10, 12

Product Nominal Pipe Ends (Remarks) Max Working


Designation Pipe Size, Pressure, psi
in. (kPa)
307 3-12 Rolled Groove, Cut Groove (a, d) 175
(1205)
31 4-12 Cut Groove (a, b) 250

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide Page 27
Automatic Sprinkler Systems
(1725)
14-16 Cut Groove (a, c) 175
(1205)

a. With gasket M.
b. Joins Cast Iron or Ductile Iron Pipe and fittings in underground main installations.
c. Joins Ductile Iron Pipe and fittings in underground main installations.
d. Joins rolled or cut grooved steel pipe to Ductile Iron pipe.
Nominal Pipe Pressure

Product
Designation Size, in. Rating, psi
(kPa)
Style 994 Flanges 4-8 200
(1725)
Style 995 Couplings 4-14 200
(1725)
Style 997 Couplings 4-8 200
(1725)
Style 995T Transition Fittings 10-14 200
(1725)
Style 43 Transition Nipples 10-14 200
(1725)

For use with FM Approved polyethylene pipe in Class 150 and Class 200 wall thicknesses. Style 06 and 60 end caps may be used with Style 997 couplings to close a
line.

Fiber Reinforced Composite Pipe and Fittings

Pipe and fittings made in various configurations of fiber reinforced composites are acceptable when FM Approved.
Installation of pipe and fittings should be according to pipe manufacturer’s instructions and FM Approvals standards. For underground
use only.

Pump Rating, Meter Line Size, Model


3
gal/min (dm /min) in. Designation
100
1 1
2 2 735-100-2 2
(380)
150
1 1
2 2 735-150-2 2
(565)
200
3 735-200-3
(755)
250
4 735-250-4
(945)
300
4 735-300-4
(1135)
450
4 735-450-4
(1705)
500
5 735-500-5
(1895)
750
6 735-750-6
(2840)
1000
6 735-1000-6
(3785)
1250
6 735-1250-6
(4730)
1500
8 735-1500-8
(5680)
2000
8 735-2000-8
(7570)
8 735-2500-8
(9465)
3000
8 735-3000-8
(11 355)
3500
10 735-3500-10
(13 250)
4000

© 2008 FM Approvals LLC. All rights reserved.


May 2008 — Approval Guide Page 28
Automatic Sprinkler Systems
10 735-4000-10
(15 140)
4500
10 735-4500-10
(17 035)
6000
12 735-5000-12
(18 925)

Each system consists of a grooved end Victaulic Venturi for use with Victaulic FMApproved grooved couplings, a differential pressure meter reading in gpm or dm /min
and associated fittings. Systems are available with either a 4 2 in. dial meter (Model S) or a 6 in. dial meter (Model L). Portable installations (meter mounted on Venturi)
or permanent installations (wall or panel mounted meter) are available with either model. Max rated working pressure 500 psi (3445 kPa) for systems with Model S dial
meter, 175 psi (1205 kPa) for systems with Model L dial meter.

PUMP SUCTION TANKS

Steel tanks for fire pump suction are used to provide a reliable source of water at desired rates and durations for fire protection purposes under
anticipated design conditions. Tanks consist of a cylindrical shell, floor and a roof all of which rest on a foundation. Tanks are filled with water from
an outside source and withdrawn in emergency situations. Accessory items are provided to monitor the water level, gain access for inspection and
repair and to prevent positive and negative pressures which could impair the structural integrity of the tank. Consideration shall be given to tank
heating equipment and/or insulation in colder regions to keep water from freezing. FM Approvals recognizes five (5) earthquake zones: 50-yr;
100-yr; 250-yr; 500-yr; and 500-yr. With this methodology, zone 50-yr is the most severe. These earthquake zones are unique to FM Global
and FM Approvals and do not necessarily correlate with the zoning of other code bodies such as the AWWA. Refer to the earthquake maps
contained in FM Global Loss Prevention Data Sheet 1-2 to determine the applicable earthquake zone. An approximate correlation is shown below.
New FM Return Period Former FM Probable AWWA
Earthquake Zone of Damaging Earthquake Zone Earthquake Zone
Designation Ground Motion Designation Desigation
50-yr Up to 50 years 40 4
100-yr 51 to 100 years 70 4
250-yr 101 to 250 years No correlation 3
500-yr 251 to 500 years 150 3
500-yr 500 years 1000 0,1 and 2

Post Indicator Valve Switch. Style 737-P with 2 SPDT switches used for supervision of butterfly valves. Style 737-0 used for supervision of OS&Y gate valves. Switch
contacts rated 10 A at 125/250 V ac, 0.5 A at 125 V dc, and 0.25 A at 250 V dc.

© 2008 FM Approvals LLC. All rights reserved.

You might also like