REMARKS:
A A
1 AS PRE-FAT 21.12.09 RS
0 FOR TNB APPROVAL 02.06.09 RS
B B
P0 PRELIMINARY REVIEW 17.04.09 RS
Revision Description Date Approved
DRAWN BY: LILI JULIANA DATE: 17.04.09
DESIGNED BY: LILI JULIANA DATE: 17.04.09
CHECKED BY: TENG SAY CHUAN DATE: 17.04.09
REVIEWED BY: R.SUNDARAVADIVELU DATE: 17.04.09
OWNER/CLIENT:
TENAGA
C
NASIONAL BERHAD C
CONTRACTOR: EPE SWITCHGEAR (M)
SDN. BHD.
LOT 6, JALAN PERMATA 2,
ARAB MALAYSIAN INDUSTRIAL PARK,
71800 NILAI, NEGERI SEMBILAN, MALAYSIA.
TEL: 606-7998500 (General) 7998634
FAX NO: 606-7998640/30
TITLE DRG. NO. SHEET NO. REV. DATE SUMMARY OF CURRENT REVISION REMARKS
4.0 AC SUPPLY DISTRIBUTION CIRCUIT iTEC EPE 96000 11 S 02 04 1 21.12.09 AS PRE-FAT NIL
5.0 DC SUPPLY DISTRIBUTION CIRCUIT iTEC EPE 96000 11 S 02 05 1 21.12.09 AS PRE-FAT NIL
B B
8.0 DC SUPPLY PROTECTION CIRCUIT iTEC EPE 96000 11 S 02 08 & 08A 1 21.12.09 AS PRE-FAT NIL
9.0 INDICATING & CONTROL CIRCUIT iTEC EPE 96000 11 S 02 09 1 21.12.09 AS PRE-FAT NIL
C C
10.0 COMMON ANNUNCIATOR ALARM CIRCUIT iTEC EPE 96000 11 S 02 10 1 21.12.09 AS PRE-FAT NIL
11.0 AUXILIARY RELAY CIRCUIT iTEC EPE 96000 11 S 02 11 1 21.12.09 AS PRE-FAT NIL
12.0 INTERTRIP ALARM SIGNAL CIRCUIT iTEC EPE 96000 11 S 02 11A 1 21.12.09 AS PRE-FAT NIL
15.0 ANNUNCIATION CONTACT DISTRIBUTION iTEC EPE 96000 11 S 02 14 1 21.12.09 AS PRE-FAT NIL
16.0 SUPERVISORY CONTROL & ALARM CIRCUIT iTEC EPE 96000 11 S 02 15 & 15A 1 21.12.09 AS PRE-FAT NIL
17.0 CT CONNECTION iTEC EPE 96000 11 S 02 16 & 16A 1 21.12.09 AS PRE-FAT NIL
E E
18.0 APPARATUS LIST iTEC EPE 96000 11 S 02 17 1 21.12.09 AS PRE-FAT NIL
TITLE DRG. NO. SHEET NO. REV. DATE SUMMARY OF CURRENT REVISION REMARKS
23.0 TERMINAL FUNCTION DRAWING - AREVA P123 iTEC EPE 96000 11 S 02 22 & 22A 1 21.12.09 AS PRE-FAT NIL
24.0 TERMINAL FUNCTION DRAWING - AREVA MVAJ055 iTEC EPE 96000 11 S 02 23 1 21.12.09 AS PRE-FAT NIL
25.0 TERMINAL FUNCTION DRAWING - AREVA MCAG14 iTEC EPE 96000 11 S 02 24 1 21.12.09 AS PRE-FAT NIL
B B
C C
D D
E E
A A
=KS01+RW =K04+RW
FROM ADJACENT BAY 240V AC, 50Hz (L) -XH 2 H11 H11 -XH 1 240V AC, 50Hz (L) FROM ADJACENT BAY
11kV PROTECTION -XH 1 -XH 2 11kV PROTECTION
& CONTROL PANEL & CONTROL PANEL
(BUSWIRE) 240V AC, 50Hz (N) 4 H12 H12 3 240V AC, 50Hz (N) (BUSWIRE)
3 4
B B
H11 H12
1 3
-F52/1
6A
SH.17
2 4
C C
1
-SD 1
-SH ON SH.20
SH.20 OFF
2 2
H15 H19
D D
1 -EC L
-S23
SH.19 SH.17
2 N
H17
1
X1
-H1 -EH
SH.17 SH.17
X2
2
E E
-F52/1
T1 TYPE T2 REF
14
11 SH.11/C3
12
A A
C 1 3 1 3 C
-F72/1 -F72/2
10A 10A
SH.17 SH.17
2 4 2 4
2 2
D -K27DCF1 -K27DCF2 D
SH.18 SH.18
10 10
L102
L101
P2
L2
P1
L1
SH.08/E4
SH.08/E1
SH.08/B1
SH.08/B4
SH.13/D1
SH.13/D1
E E
-F72/1 -K27DCF1 -F72/2 -K27DCF2
T1 TYPE T2 REF T1 TYPE T2 REF T1 TYPE T2 REF T1 TYPE T2 REF
14 4 14 4
11 SH.11/C3 1 SH.14/C4 11 SH.11/C4 1 SH.14/C4
12 5 12 5
6 6
3 SH.15/D4 3 SH.15/D4
7 7
9 9
11 SPARE 11 SPARE
8 8
A -FMCBM A
M1
-FMCBCL
B B
-XK1
T
N
C
C -XK 6 C
-XK1
-XK 7
110VDC
SUPPLIY
FROM
ADJ. BAY
D D
1
-F86E
SH.08A/D2
3
E E
2
-XK 4
A A
B -XP 3 B
C C
110VDC
SUPPLY
FROM
ADJ. BAY
D D
E E
A A
P1 P1 L1 L1
SH.05/D3 SH.08A/A1 SH.05/D4 SH.09/A1
B B
13
-X51OCEF
SH.21
14
C C
D D
P2 P2 L2 L2
SH.05/D3 SH.08A/E1 SH.05/D4 SH.09/F1
E E
A A
P1
SH.08/B3
B B
11
-K64REF
SH.11/D2
12 14
DWG.11 S 18 SH.11A
C C
D 27 25 D
26
P2
SH.08/E3
E E
A L1 L1 A
SH.08/B5 SH.11/A1
1A2
B B
1
L7
1
L7A -KQO1
C SH.15A/D2 C
5 4
L7
1
-PAC
SH.19
2
D -XL 8 D
=KT02+S X1
8 -S86
SH.18
FOR DETAIL REFER DWG. NO.:
EPE U0801001AA S 02 SH.10
9
X2
E E
L2 L2
SH.08/E5 SH.11/D1
A A
=KS01+RW =K02+RW
L401 L401
2
L405 L405
4
B B
C C
6
D D
E K74ATT E
T1 TYPE T2 REF
4
1 SPARE
5
6
3 SH.13/C4
7
9
11 SH.13/C5
8
A A
B B
-F86E
2 9
-F64REF/LV -F52/1 -F72/1 -F72/2 -F52/2 -F86E
SH.04/C3 SH.04/C3 SH.04/C4 SH.16A/C5
SH.24 4 SH.23 11
-XL2 15
C C
-XL 11
A1
-K64REF
SH.21
A2
D D
A A
B B
C 5 43 C
-F86E -K86E
SH.23 SH.11/D7
7 44
SH.XX SH.XX
E E
A A
WINDOW ARRANGEMENT
B F1 F2 F9 F10 B
RESTRICTED LOCKOUT &
INTERTRIP
EARTH FAULT MASTER TRIP SPARE
FROM HV 33KV
TRIP OPERATED
R R R R
F3 F4 F11 F12
TX. NO.1
OVER CURRENT EARTH FAULT
SBEF 1
PROTECTION PROTECTION SPARE
STAGE 2
C TRIP TRIP C
OPERATED
R R R R
F5 F6 F13 F14
PROTECTION
TRIP CIRCUIT
RELAY SPARE SPARE
FAIL
FAIL
A A A A
D F7 F8 D
ATTENDED/UNATTENDED
SUPPLY BUS
A A
L111 L111
SH.14/B1
B B
L103 L107
21 23 16 20
3 11 -K64REF -K86E -F51OCEF -F51OCEF
-K74ATT -K74ATT SH.11/D2 SH.11/D7 SH.22 SH.22
SH.10/D4 SH.10/D4 22 24 24 14 18
C 7 6 8 9 C
-H30
C M A1 U/M A2 A/F F1 F2 F3 F4
D D
SH.05/D6 +VE C RST. ACK. MUTE TEST (R) (R) (R) (R)
MINILEC
MBAS-9400 (2D)
SH.05/D6 -VE
LV RESTRICTED LOCKOUT OVER CURRENT EARTH FAULT
EARTH FAULT MASTER TRIP PROTECTION PROTECTION
OPERATED RELAY OPERATED TRIP TRIP
I1 C1 I2 C2
REFER TO SH.10/C4
E E
A A
L111 L111
SH.13/B8
B B
1 1 1 1 1 1 1 1
-K510CEFX2 -K510CEFX1 -K74AUX2 -K74AUX1 -K27DCF1 -K27DCF2 -K86 -K64SBEF
SH.11/D2 SH.11/D1 SH.11/D5 SH.11/D3 SH.05/D3 SH.05/D5 SH.11/D8 SH.11/D7
5 4 5 4 5 4 5 4 5 4 5 4 5 4 5 4
C C
D D
(A) (A) (A) (A) (R) (R) (R) (R) (A) (A)
E E
A A
B B
C C
-XY 7 8 9 10 14
Y49
11 15 33
15
-F51OCEF
D D
SH.11/D7
SH.22
S
SH.19
-K86E
-S43
12 16 34 13
=KT02+S
E E
A A
+RTU
MCB
B B
C C
Y11 Y15
D D
B
-K86R
SH.18
A
E E
1600/5A
-XC CL.5P20
D S1 C110 D
7 11kV NER
S1 C130
8
S1 C150 C70 -XC
CT RATIO: P1 9 10
1600/800/5A C90
CL.5P20 P2 11
15VA S2 C20
4
S2 C40
5 -X51OCEF
E S2 C60 E
SH.21
6
S3 C10 -XC 1 21 22 41 42 7
1
S3 C30 2 23 24 43 44 8
2
S3 C50 3 25 26 45 46 9
R Y B 3
4 27 28 47 48 10
REMOVE LINK
CONTINUED TO NEXT PAGE UPON CONNECTION
=KT02+S
F 1 21.12.09 LILI/NNS/RS DATE 17.04.09 CLIENT: CONTRACTOR : TITLE: = KT02 + RW / S1 F
SCHEMATIC DIAGRAM
0 02.06.09 LILI/TSC/RS DRAWN LILI EPE SWITCHGEAR (M) SDN. BHD.
11KV TRANSFORMER FEEDER NO.2 -11RT1
CONTRACT NO.: TNB 213/2008 SUPPLIER : DRAWING NO.: REV.: 16
P0 17.04.09 LILI/TSC/RS CHECKED TSC CT CONNECTION THIS SHEET:
REV. DATE DRN/CHK/APP APPROVED RS TENDER NO.: T 0213107 EPE SWITCHGEAR (M) SDN. BHD.
SUBSTATION: 11kV PPU STATION 1 NEXT SHEET: 16A
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A A
S1 D110 -XD
7
S1 D130
8
S1 D150 D70 -XD
P1 9 10
D90
P2 11
S2 D20 SPARE
4
S2 D40
B B
5
S2 D60
6
S3 D10
1
S3 D30
2
S3 D50
3
REMOVE LINK
UPON CONNECTION
C C
-TU
PHASE R E10 E11
-XE
A a
1
CL.0.5
N n E71 E70
4
D -TU D
PHASE Y E30 E31
A a
2
EARTH CL.0.5
SWITCH
-Q8
N n E72 E70
5
-TU
PHASE B E50 E51
L110 A a
E -HVI 3 E
L190 L130 CL.0.5
L150
N n E73 E70
6
E90 -F52/2
7 T1 TYPE T2 REF
14
30MVA 11 SH.11/C6
33/11kV 12
TRANSFORMER
=KT02+S
F 1 21.12.09 LILI/NNS/RS DATE 17.04.09 CLIENT: CONTRACTOR : TITLE: = KT02 + RW / S2 F
SCHEMATIC DIAGRAM
0 02.06.09 LILI/TSC/RS DRAWN LILI EPE SWITCHGEAR (M) SDN. BHD.
11KV TRANSFORMER FEEDER NO.2 -11RT1
CONTRACT NO.: TNB 213/2008 SUPPLIER : DRAWING NO.: REV.: 16A
P0 17.04.09 LILI/TSC/RS CHECKED TSC CT CONNECTION THIS SHEET:
REV. DATE DRN/CHK/APP APPROVED RS TENDER NO.: T 0213107 EPE SWITCHGEAR (M) SDN. BHD.
SUBSTATION: 11kV PPU STATION 1 NEXT SHEET: 17
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
DEVICE
DESIGNATION DEVICE DETAILS LOCATION TERMINAL FUNCTION DETAIL
A A
-EC DEVICE FUNCTION : FLOURESCENT LAMP, 15W =KT02+RW
MAKE : GE
-EC SH.04/D4
MAKE : FUJI
TYPE : SPSR-30S
-HQ8
A A
-K27DCF1 DEVICE FUNCTION : AUXILIARY RELAY c/w FRONT CONNECTED BASE =KT02+RW
-K27DCF2 MAKE : OMRON
-K64SBEF TYPE : MK3P c/w BASE PF113A-E
-K74ATT
-K510CEFX1 RATED AUX. VOLTAGE (Vs) : 110V DC
-K510CEFX2 POWER CONSUMPTION : 2.7 VA
-K86 TYPICAL PICK-UP TIME VALUES : 30ms
-K74AUX1 (MAKE/BREAK CONTACT) -K27DCF1
-K74AUX2 -K27DCF2
-KQ01 TYPICAL DROP-OUT TIME VALUES : 20ms -K64SBEF
(MAKE/BREAK CONTACT) -K74ATT
-K510CEFX1
-K510CEFX2
B -K86 B
-K74AUX1
-K74AUX2
-KQ01
-K86E CONTACTOR
A1 13 23 33 43
MANUFACTURER : SIEMENS
TYPE : 3RH1140-1BF40
RATED VOLTAGE : 110V DC A2 14 24 34 44
A A
-PA DEVICE FUNCTION : AMMETER =KT02+RW
MAKE : CROMPTON
TYPE : --
SCALE : 0-1920/960A
CT RATIO : 1600/800/5A
SIZE : 96 x 96 mm sq
CLASS : 1.5
-S23
A A
-SA DEVICE FUNCTION : AMMETER SELECTOR SWITCH =KT02+RW
MAKE : KRAUS & NAIMER
TYPE : CA10-A058-621
RATED OPERATION CURRENT : 10A
NO. OF POLES : 6 POLES
-SD
C C
-T100 DEVICE FUNCTION : SINGLE PHASE SATURATION
-T101 CURRENT TRANSFORMER
-T102 MAKE : DTMB
CT RATIO : 5/5A
BURDEN : 2VA
CT CLASS : CLASS 0.5
2 4 6 8 10 12 14 16 18 20 22 24 26 28
V2
V1
SWITCH
MAKE : KRAUS & NAIMER
C TYPE : CA10-A007-622 C
RATED OPERATION
CURRENT : 10A
NO. OF POLES : 4 POLES
B
Y
R
N
-SV SH.16A/C7
-RC1 DEVICE FUNCTION : STABILISING RESISTOR
D D
-RC1 SH.16/C6
-RD1 DEVICE FUNCTION : METROSIL
-RD1 SH.16/C7
-K64REF PRIMA PLUG IN RELAY
E MANUFACTURER : PRIMA AREVA E
TYPE : PRSIIN048
RATED VOLTAGE : 110/125V DC
11 14 12 21 24 22 31 34 32 41 44 42
-K64REF
TECHNICAL DATA
INPUT RATINGS AC VOLTAGE, V N 110 -120V nominal phase-phase 110V DC 33 + 35 RELAY FAULTY
AC CURRENT, I N 1 A or 5 A AUX. VOLTAGE
SUPPLY 34 - 37 SH.11/C1
RATED FREQUENCY, f N 50 Hz
SH.08/C2 WATCHDOG
AUXILIARY DC VOLTAGE RATED AUX. VOLTAGE, 110 V 36
BINARY INPUTS DC OPERATING VOLTAGE Vx 24/250 Vdc 49 1A
IR R PHASE CURRENT
4 LOCKOUT MTR
6 SH.08A/C2
B TRIP CONTACTS SWITCHING CAPACITY, MAKE 30 A and carry for 3s
50 I B
51 RL1
BREAK 50 W resistive, 25W inductive (L/R = 40ms) 1A 2
CARRY 5A Continuous IS Y PHASE CURRENT
10 TCS FAIL (CONTACT MULTIPLICATION)
SERIAL COMMUNICATIONS K-BUS 52 I SH.11/C2
TRANSMISSION MODE SYNCHRONOUS
12
53 1A
SIGNAL LEVELS RS485 IT B PHASE CURRENT
RL2
8
MESSAGE FORMAT HDLC
DATA RATE 64 kbit/s 54 I
CONNECTION MULTIDROP (32 UNITS) 14 OVERCURRENT TRIP
CABLE TYPE SCREENED TWISTED PAIR 55 1A
CABLE LENGTH 1000M IN NEUTRAL RL3 16 SH.13/C7
CONNECTOR SCREW TERMINALS (M4) ANNUNCIATOR
ISOLATION SELV 56 I
SERIAL (RS232) 18 EARTHFAULT TRIP
C SIGNAL LEVELS RS232 DTE (9 pin D-type female) 41 5A C
RL4 20 SH.13/C8
MESSAGE FORMAT IEC870-5(FT1.2) IR R PHASE CURRENT
DATA RATE UP TO 19200 BAUD
CONNECTION SINGLE ENDED 42 I 1 AUTO TRIP COUNTER
CONNECTOR 25 WAY D-TYPE
CABLE TYPE SERIAL (SCREENED MULTI-CORE) 43 5A
RL5 SH.09/B2
ISOLATION IS 3
ELV Y PHASE CURRENT
DOCUMENTATION
CT INPUT 44 I
SH.16/E4,F4 5
ENGLISH : 45 5A
RL6
MANUAL P123 (OVERCURRENT PROTECTION RELAY) TG1.1509 IT 7
B PHASE CURRENT
SELECTION AND ORDERING DATA 46 I
MICOM P123 MICOM P123 00 1 47 5A 9 OVERCURRENT TRIP
D Earth Current Input: IN NEUTRAL
RL7 SH.15/D3
D
0.01 - 8 Ion B 11 RTU
Auxiliary Supply Voltage:
48 I
48-150 Vcc F EARTHFAULT TRIP
13
Communication Protocol: SH.15/D3
1 RL8 15
MODBUS TCS MONITOR 22
HMI Languages: CB CLOSE 24 L1
English 1 SH.07/C7
TCS MONITOR 26
CB OPEN 28 L2
SH.07/C7
17 31
E L3 E
19
RS-485
21 (OPTION) 32
23 L4 30
25
27 L5
A A
D D
E E
TECHNICAL DATA
OPERATING TIME 10ms at rated voltage
OUTPUT RELAY CONTACTS Make & carry continuously 1250Va.c. or 1250Wd.c. within limits of 660V and 5A -F86E
Make & carry for 3 seconds 7500Va.c. or 7500Wd.c. within limits of 660V and 30A LOCKOUT MASTER TRIP RELAY
Break: 1250Va.c. or 100W (resistive) d.c. or 50W (inductive) d.c. AREVA MVAJ055
within limits of 250V and 5A
RL1 1
25 CB CLOSING INTERLOCK
B 3 SH.06/E6 B
MASTER TRIP RESET
DOCUMENTATION 26 RESET
SH.08A/D2
ENGLISH : FACT SHEET : TR-A SERIES HIGH SPEED TRIPPING RELAYS
RL2 2
TRIP CB
4 SH.07/C6
SELECTION AND ORDERING DATA 27
BURDEN HIGH MASTER TRIP OPERATED 5
SH.08A/D2 28 OPERATE RL3 INTERTRIP TO HV (TRIPPING)
CONTACT RESET HAND/ELECTRICAL RESET 7 SH.11A/C3
NUMBER OF CONTACTS 1 NC 4 NO
RL4 6
C AUX. SUPPLY 110VDC MASTER TRIP RESET C
8 SH.09/B8
D D
E E
TECHNICAL DATA
INPUT RATINGS AC CURRENT, N 1 A or 5 A
RATED FREQUENCY, f N 50 Hz
-F64REF/LV
TRIP CONTACTS 2 PAIRS OF MAKE SELF RESETTING CONTACTS AREVA - MCAG14
TAP SETTING ( s) 5 - 20% of n
10 - 40% of n
RL1
20 - 80% of n
R1 C1
B STABILISING RESISTOR 470 ohm, 220 ohm or 47 ohm (STANDARD)
2 B
1
TRIP CONTACT
3 (TO CB TRIP COIL)
SH.07/C6
1
2 2
3
4 CONTACT MULTIPLICATION
4 SH.11/C2
SELECTION AND ORDERING DATA 5
RELAY TYPE MCAG14
6
7
C C
CT SECONDARY RATING 1A 8
R S 9
SETTING RANGE 10-40% of In
W 10
AUXILIARY SUPPLY VOLTAGE BN
P
STABILISING RESISTOR VALVE 0-1500 ohm T1 GY
(IF NON STANDARD) Y
V
BE
BK
F
D D
27 28
REXT SMS
E E
A A
B B
C C
D D
-RD1 - - 1
-RC1 - - 1
E E
-K64REF AREVA PRSIIN04B 1