Doble Engineering Pvt. LTD: P442 Relay Characteristic Simulator

You might also like

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 3

P442 RELAY CHARACTERISTIC SIMULATOR - KAMIN DAVE- DOBLE ENGINEERING PVT.

LTD, 305-SAKAR, OLD PADRA ROAD


In 1A

Z1 1.35 Ohm
R1ph 5 Ohm
R1G 15 Ohm
ZP 1.35 Ohm
RPph 5 Ohm
RPG 15 Ohm
Z2 5.57 Ohm
R2ph 5 Ohm
R2G 15 Ohm
Z3 6.14 Ohm
R3ph 5 Ohm
R3G 15 Ohm NOTE: Enable: "Use Separate Arc Resistance" Option in F6TEST
Z4 0.135 Ohm
R4ph 5 Ohm
R4G 15 Ohm
KZ1 0.766
Ang 9.6 °
KZP 0.766
Ang 9.6 °
KZ2 0.766
Ang 9.6 °
KZ3 0.766
Ang 9.6 °
KZ4 0.833
Ang 0°
t1 for Zone-1 0.032 s
tP for Zone-P 0.032 s
t2 for Zone-2 0.39 s
t3 for Zone-3 0.8 s
t4 for Zone-4 0.44 s
Dir Line Ang1 (Ph-Ph) -30 °
Dir Line Ang1 (Ph-E) -30 ° X reach
Line Angle 71.49 ° Zone1 0.948268 ###
ZoneP 0.948268 ###
Zone2 0.948268 ###
Zone3 0.948268 ###
Zone4 0.948268 ###
, 305-SAKAR, OLD PADRA ROAD, VADODARA

Resistance" Option in F6TEST


Testing of Distance Protection
Create RIO file for testing. "Press" on "Create RIO-File" button. It will create RIO file. Same RIO file have to be "Import" in F6TEST Software.

Nominal values
Generator CT / VT
Vn 6.6 kV KnI 2500 A / 1A
Sn 25 MVA KnV 6600 V / 110 V

primary

DOBLE ENGINEERING PVT LTD