DESCRIPTION
The YFE models are a new offering in our successful LX Series
split system air conditioner lineup. These units are optimized for
the new 14 SEER Regional Minimum Efficiency in the South-
east US, and feature a tube-in-fin condenser coil, scroll com-
pressor, and copper filter-drier. These outdoor units have been
specifically designed to be matched with Johnson Controls Uni-
tary Products indoor coils, furnaces, and air handlers to provide
TECHNICAL GUIDE FOR INSTALLATION ONLY IN US SOUTHEAST
AND NORTHERN REGIONS AND CANADA a complete system solution.
FEATURES
LX SERIES
• Quality Coils - Enhanced aluminum fins are mechanically
SPLIT SYSTEM bonded to copper tubing.
AIR CONDITIONERS Installation Allowed
• Scroll Compressor - Featuring the newest generation of
high efficiency scroll compressors.
14 SEER – R-410A – 1 PHASE
• Copper filter-drier - The factory installed filter drier features
1.5 THRU 5 NOMINAL TONS copper construction for reliable long term protection.
MODELS: YFE18 THRU 60 • Easier Installation - Independent panels provide quick
access for unit setup. Installation time is reduced by easy
power and control wiring access. Select indoor matches with
factory-mounted TXVs are available for quicker system
installation. The factory installed filter-drier and factory
charge for a 15-Ft lineset means less time spent brazing and
charging the system. The small base dimension and reduced
unit clearances make for easier retrofits.
• Accessible Information - QR code on unit provides quick
access to technical documents and warranty information.
• Durable Finish - The coated steel wire fan guard, coated
external fasteners, and pre-treated G90-equivalent galva-
nized steel chassis components resist corrosion and rust
creep. Champagne colored powdercoat paint further protects
external panels.
• Rugged Coil Protection - Coils are protected from mechan-
ical damage by a proven stamped steel coil guard design.
• Protected Compressor - Compressors are protected inter-
nally by a high pressure relief valve and a temperature sen-
sor, and externally by the system high pressure switch. The
liquid line filter-drier is factory installed to protect the com-
pressor against moisture and debris.
• Reliable Operation - Ball bearing fan motors provide supe-
rior performance in extreme temperatures.
® • Environmentally Friendly - CFC-free R-410A refrigerant
delivers environmentally friendly performance with zero
ozone depletion.
• Top Discharge - Warm air is blown up, away from the struc-
Due to continuous product improvement, specifications ture and any landscaping and allows compact location on
are subject to change without notice.
multi-unit applications.
Visit us on the web at
• Low Operating Sound Levels - The sturdy cabinet and top
www.upgnet.com and www.york.com design provides sound performance of 76 dBA or lower.
Additional rating information can be found at Compatible accessories for further sound reduction are also
www.ahridirectory.org available.
• Better Service Access - Diagonal base valves with open
WARRANTY SUMMARY* access for low-loss fittings, single panel access to the electri-
Standard 5-Years limited parts warranty. cal controls, swing out control box for full corner access, and
Standard 10-Years limited compressor warranty. removable fan guard allow easy access for unit mainte-
Extended 10-Years limited parts warranty when product is nance.
registered online within 90 days of purchase for replacement • Agency Listed - Safety certified by CSA to UL 1995 / CSA
or closing for new home construction. 22.2. Performance certified to ANSI/AHRI Standard 210/240
*Does not apply to R-22 models, 3-Phase models, or Internet sales.
in accordance with the Unitary Small Equipment certification
See Limited Warranty certificate in User's Information Manual for details. program.
DIMENSIONS
&
Dimensions Refrigerant Connection
Unit (Inches) Service Valve Size
Model
A B C Liquid Vapor
YFE18B21S 36-1/4 24 24
YFE24B21S 30 29-1/4 29-1/4
3/4
YFE30B21S 39-1/2 35-1/4 31-3/4
COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils (Coil Only Ratings)
COIL COOLING
CFM RANGE
UNIT MODEL RATED NET MBH
MODEL WIDTH (MIN.-MAX.) SEER 1 EER
CFM TOTAL SENS.
YFE18B21S CF/CM/CU18A 14.5 450 - 750 600 17.8 13.3 14.00 12.20
YFE18B21S CF/CM/CU18B 17.5 450 - 750 600 17.8 13.3 14.00 12.20
YFE18B21S CF/CM/CU24A 14.5 450 - 750 600 18.0 13.5 14.00 12.20
YFE18B21S CF/CM/CU24B 17.5 450 - 750 600 18.0 13.5 14.00 12.20
YFE18B21S CF/CM/CU24C 21.0 450 - 750 600 18.0 13.5 14.00 12.20
YFE18B21S CF/CM/CU30A 14.5 450 - 750 600 18.0 13.6 14.00 12.20
YFE18B21S CF/CM/CU30B 17.5 450 - 750 600 18.0 13.6 14.00 12.20
YFE18B21S CF/CM/CU30C 21.0 450 - 750 600 18.0 13.6 14.00 12.20
YFE18B21S CF/CM/CU30D 24.5 450 - 750 600 18.0 13.6 14.00 12.20
YFE18B21S CF/CM/CU36B 17.5 450 - 750 600 18.0 13.4 14.50 12.25
YFE18B21S CF/CM/CU36C 21.0 450 - 750 600 18.0 13.4 14.50 12.25
YFE18B21S CF/CM/CU36D 24.5 450 - 750 600 18.0 13.4 14.50 12.25
YFE18B21S CF/CM36A 14.5 450 - 750 600 18.0 13.4 14.50 12.25
YFE24B21S CF/CM/CU24A 14.5 600 - 1000 800 24.0 18.0 14.00 11.75
YFE24B21S CF/CM/CU24B 17.5 600 - 1000 800 24.0 18.0 14.00 11.75
YFE24B21S CF/CM/CU24C 21.0 600 - 1000 800 24.0 18.0 14.00 11.75
YFE24B21S CF/CM/CU30A 14.5 600 - 1000 800 24.0 18.0 14.00 11.75
YFE24B21S CF/CM/CU30B 17.5 600 - 1000 800 24.0 18.0 14.00 11.75
YFE24B21S CF/CM/CU30C 21.0 600 - 1000 800 24.0 18.0 14.00 11.75
YFE24B21S CF/CM/CU30D 24.5 600 - 1000 800 24.0 18.0 14.00 11.75
YFE24B21S CF/CM/CU36B 17.5 600 - 1000 800 24.0 17.8 14.25 12.25
YFE24B21S CF/CM/CU36C 21.0 600 - 1000 800 24.0 17.8 14.25 12.25
YFE24B21S CF/CM/CU36D 24.5 600 - 1000 800 24.0 17.8 14.25 12.25
YFE24B21S CF/CM/CU42C 21.0 600 - 1000 800 24.0 17.8 14.50 12.25
YFE24B21S CF/CM/CU42D 24.5 600 - 1000 800 24.0 17.8 14.50 12.25
YFE24B21S CF/CM36A 14.5 600 - 1000 800 24.0 17.8 14.25 12.25
YFE24B21S CF42B 17.5 600 - 1000 800 24.0 17.8 14.50 12.25
YFE30B21S CF/CM/CU30B 17.5 800 - 1200 1000 29.0 21.0 14.00 11.75
YFE30B21S CF/CM/CU30C 21.0 800 - 1200 1000 29.0 21.0 14.00 11.75
YFE30B21S CF/CM/CU30D 24.5 800 - 1200 1000 29.0 21.0 14.00 11.75
YFE30B21S CF/CM/CU36B 17.5 800 - 1200 1000 29.4 21.2 14.00 11.75
YFE30B21S CF/CM/CU36C 21.0 800 - 1200 1000 29.4 21.2 14.00 11.75
YFE30B21S CF/CM/CU36D 24.5 800 - 1200 1000 29.4 21.2 14.00 11.75
YFE30B21S CF/CM/CU42C 21.0 800 - 1200 1000 29.6 21.4 14.00 11.75
YFE30B21S CF/CM/CU42D 24.5 800 - 1200 1000 29.6 21.4 14.00 11.75
YFE30B21S CF42B 17.5 800 - 1200 1000 29.6 21.4 14.00 11.75
YFE36B21S CF/CM/CU36B 17.5 1000 - 1400 1200 35.0 24.6 14.00 11.75
YFE36B21S CF/CM/CU36C 21.0 1000 - 1400 1200 35.0 24.6 14.00 11.75
YFE36B21S CF/CM/CU36D 24.5 1000 - 1400 1200 35.0 24.6 14.00 11.75
YFE36B21S CF/CM/CU42C 21.0 1000 - 1400 1200 36.0 26.0 14.00 11.75
YFE36B21S CF/CM/CU42D 24.5 1000 - 1400 1200 36.0 26.0 14.00 11.75
YFE36B21S CF/CM/CU48C 21.0 1000 - 1400 1200 36.0 25.6 14.00 11.75
YFE36B21S CF/CM/CU48D 24.5 1000 - 1400 1200 36.0 25.6 14.00 11.75
YFE36B21S CF42B 17.5 1000 - 1400 1200 36.0 26.0 14.00 11.75
YFE42B21S CF/CM/CU42C 21.0 1200 - 1600 1400 40.0 31.0 14.00 12.20
YFE42B21S CF/CM/CU42D 24.5 1200 - 1600 1400 40.0 31.0 14.00 12.20
YFE42B21S CF/CM/CU48C 21.0 1200 - 1600 1400 41.0 30.0 14.00 12.20
YFE42B21S CF/CM/CU48D 24.5 1200 - 1600 1400 41.0 30.0 14.00 12.20
For Notes See Page 10.
COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils (Coil Only Ratings) (Continued)
COIL COOLING
CFM RANGE
UNIT MODEL RATED NET MBH
MODEL WIDTH (MIN.-MAX.) SEER 1 EER
CFM TOTAL SENS.
YFE42B21S CF/CM/CU60C 21.0 1200 - 1600 1400 41.0 30.5 14.00 12.20
YFE42B21S CF/CM/CU60D 24.5 1200 - 1600 1400 41.0 30.5 14.00 12.20
YFE42B21S CF/CM64D 24.5 1200 - 1600 1400 41.5 31.0 14.25 12.25
YFE42B21S CF42B 17.5 1200 - 1600 1225 38.5 27.0 14.00 12.20
YFE48B21S CF/CM/CU48C 21.0 1400 - 1800 1600 46.5 33.5 14.00 11.75
YFE48B21S CF/CM/CU48D 24.5 1400 - 1800 1600 46.5 33.5 14.00 11.75
YFE48B21S CF/CM/CU60C 21.0 1400 - 1800 1600 48.0 36.5 14.00 11.75
YFE48B21S CF/CM/CU60D 24.5 1400 - 1800 1600 48.0 36.5 14.00 11.75
YFE48B21S CF/CM64D 24.5 1400 - 1800 1600 48.0 36.5 14.25 12.25
YFE60B21S CF/CM/CU60C 21.0 1530 - 1930 1715 56.0 39.0 14.00 11.75
YFE60B21S CF/CM/CU60D 24.5 1530 - 1930 1725 56.0 39.0 14.00 11.75
YFE60B21S CF/CM64D 24.5 1530 - 1930 1725 57.5 40.5 14.00 11.75
For rated condition information, see the footnotes below the System Capacity - Single Piece and Modular Air Handlers table.
1. Requires a S1-2FD06700224 Blower Time Delay unless a standard furnace is equipped with one.
— = Not Applicable.
MP Modular Air Handlers use Coil Only Ratings.
PSC furnaces, such as the TG8S, TGLS, and TG9S, use Coil Only Ratings.
MECHANICAL SPECIFICATIONS • Units shall be factory leak checked, run tested, and shipped
MANUFACTURE AND CERTIFICATIONS with a holding charge of R-410A refrigerant.
• Units shall be manufactured in an ISO 9001 certified facility. • Unit cabinet components shall be G90 equivalent steel fin-
ished with powder-coat paint rated at a minimum of 500
• Units shall be certified by CSA to UL 1995 / CSA 22.2 and
hours under ASTM B117 testing.
performance certified to ANSI/AHRI Standard 210/240.
• Unit base pan shall be stamped G90 equivalent steel fin-
• Units shall be sound tested according to ANSI/AHRI Stan-
ished with powder-coat paint rated at a minimum of 500
dard 270.
hours under ASTM B117 testing.
• Certified matched system ratings will be available for down-
• Units shall have a single corner post opposite the electrical
load from the AHRI online directory at www.ahridirectory.org
control box and two independently removable steel coil
• Unit packaging shall be marked, “Assembled in the USA” guard panels to optimize cabinet strength and serviceability.
UNIT APPLICATION
• Units shall have L-shaped stamped sheet metal coil guards
• Units shall be approved for cooling operation between 55ºF with punched and extruded slots for maximum panel durabil-
and 125°F without modification. ity and stiffness.
• Units shall be approved for linesets up to 80 feet equivalent • Units shall have a factory installed filter-drier for faster instal-
length without modification. lation and improved system reliability.
• Units shall be approved for installation within 6 inches of a • Unit base valves shall be mounted diagonally on the unit
flat vertical wall without modification, according to the base pan with service ports that provide sufficient clearance
instructions in the technical literature. for low-loss hose fittings.
• Units shall be certified to the 5th Edition (2014) of the Florida • Units shall be constructed with a high pressure switch for
Building Code for a combined allowable lateral and uplift system protection.
wind force of 200 psf and 100 psf, respectively, for both
• Units shall be constructed with all badging and labels applied
ground-mounted and rooftop-mounted applications up to 200
at the factory.
feet above grade with approved mounting kit.
UNIT COMPONENTS
• Units shall be designed to 76dBA or less to minimize sound
• Compressor shall be hermetic with internal electrical over-
pollution.
load protection and internal overpressure protection.
UNIT ACCESS
• Compressor shall be mounted on rubber vibration isolators
• Units shall have a removable fan guard that can be removed
that do not require the removal of transportation clips or
independently of the top for interior access through the top of
brackets.
the unit without damaging the coil.
• Units shall be constructed with scroll compressors.
• Units shall have two removable stamped steel coil guards for
exterior coil access. • Condenser fan shall be direct drive with vertical air discharge
for low sound levels.
• Units shall have a separate compartment for electrical con-
trols that can be accessed without disturbing the unit airflow. • Condenser fan motor shall be totally enclosed with perma-
nently lubricated ball bearings motors approved for vertical
• Units shall have a blockoff panel that can be removed to pro-
shaft applications.
vide interior unit access through the side of the unit.
• Condenser coil shall be air cooled and constructed of
• Units shall have a removable blockoff panel and a swing
enhanced aluminum fins mechanically bonded to internally
away removable electrical panel that provides sufficient inte-
enhanced Ø 7mm copper tubing.
rior unit access for removing the compressor through the
UNIT WARRANTIES
side of the unit.
UNIT CONSTRUCTION
• Unit manufacturer shall provide a 10-Year compressor war-
ranty without a requirement for unit registration.
• Units shall be shipped completely wired, piped and assem-
bled. Wiring pigtails shall be provided for field control wiring • Unit manufacturer shall provide a 5-Year parts warranty with-
connections. Service valves shall be provided for field refrig- out a requirement for unit registration.
erant line connections.
TYPICAL INSTALLATION
&$87,216SHFLDOFDUHPXVWEHWDNHQWRDYRLGUHFLUFXODWLRQRIGLVFKDUJHDLUWKURXJKFRQGHQVHUFRLO 127(
(QVXUHDGHTXDWH
´29(5+($'&/($5$1&( ZDOOVXSSRUW
1(&&/$66:,5,1*
:($7+(53522) 7+(50267$7
',6&211(&7
6:,7&+
1(&&/$66:,5,1*
´&/($5$1&(
'RQRWORFDWH %5$&(6
RXWGRRUXQLWFORVHU 8VHIRUZDOOPRXQWZLWK
WKDQWKHLQGLFDWHG FHQWHUEUDFHXQGHU
FOHDUDQFHWRDGU\HU FHQWHURIFRPSUHVVRU
72)851$&(25
YHQWRUWRD $,5+$1'/(5
IXUQDFHÀXH 7(50,1$/%/2&.
1(&&/$66:,5,1*
´&/($5$1&(
$5281'3(5,0(7(5
´FOHDUDQFH
SHUPLVVLEOHRQRQH 127(
VLGHRQO\VHH $OORXWGRRUZLULQJ
$OWHUQDWLYH PXVWEHZHDWKHUSURRI
,QVWDOODWLRQ
&OHDUDQFHV
&21752/
127( $&&(66 6($/23(1,1*6 612:3803836
(QVXUHDPLQLPXPRI 3$1(/ 8VHSHUPDJXPRUHTXLYDOHQW 8VHLQGHHSVQRZDUHDV
´FOHDUDQFHEHWZHHQ ZLWK¿IWKSXPSXSXQGHU
DQ\WZRXQLWV 0,1,080´6(59,&($&&(66&/($5$1&(
0DLQWDLQPLQLPXPFOHDUDQFHRQRQHVLGHRIDFFHVVSDQHO
FHQWHURIFRPSUHVVRU
$
! CAUTION
Care must be taken to prevent ice from damaging the unit. Damage may occur from ice falling onto unit from a sloped roof or from a vertical drip
line due to a partial overhang.
OVERHANG COMPLETELY
NO OVERHANG COVERING UNIT
COVERING UNIT OVERHANG PARTIALLY
COVERING UNIT
48” MINIMUM
OVERHEAD
CLEARANCE
NOTE: NOTE:
The unit must be installed on a solid base above the grade. Install unit on flat surface. If installation surface is sloped, ensure
The base must not be able to settle or shift causing strain on that unit slopes away from house structure at 1/4” per foot.
refrigerant lines and possible leaks.
CAUTION:
Special care must be taken to avoid recirculation of discharge air through condenser coil. A0291-001
C Y R G W
* TERMINAL W IS ONLY
REQUIRED ON SYSTEMS
CONTACTOR WITH HEAT.
TERMINALS
GND.
LUG COIL *
Y R G W
FENCE
24” 24” 24” NOTE:
SERVICE SERVICE SERVICE Clearance between two units may be
reduced to 18” minimum provided
the service access clearance is
increased to 24” minimum, and the
18” 18” clearance on each remaining side
UNIT- UNIT- is maintained at 18” minimum.
TO-UNIT TO-UNIT
18” 18”
NOTE:
MINIMUM CLEARANCE FROM WALL
Clearance to one side of the
unit may be reduced to 6” provided
the clearance to each remaining side
is increased to 12” minimum, the 6” 6”
service access is increased to 24”
minimum, and the clearances between WALL 24”
any two units is maintained at 24” SERVICE 12”
24”
minimum. SERVICE
AND UNIT-
TO-UNIT
12” 12”
CAUTION: FENCE
Special care must be taken to avoid recirculation of discharge air through condenser coil.
A0287-001