+++PGS -12/24/36
User Manual
浙江法拉迪电力科技有限公司
Zhejiang Farady Powertech Co.,Ltd
Guide
1、Overview…………………………………………………………………………………… 2
3、Features…………………………………………………………………………………… 2
5、 Structure………………………………………………………………………………… 5
10、maintenance………………………………………………………………………………19
12、random file…………………………………………………………………………20
1、Overview
Column installed insulation load switch, type PGS-12/24/36-20,is suitable for the rated voltage
12/24/36kV,rated current 400A、630A、50/60Hz power grid open circuit、load current in closed Power
system、overload current. This load switch can separate those broken distribution line automatically.
With the latest technology, it has the newest electronic controller. The switch can be used by manual
operation, electric operation and operation from a long distance. Electronic controller is installed in a
stainless steel cabinet which is suitable for using under all kinds of climatic conditions. In addition, there are
some wired and wireless modem installed in the cabinet through which it can realize the remote monitoring
and control. Simple installation on column is convenient, fast, and also can reduce the construction cost.
2.5 Installation site: No fire, no explosion hazards, no chemical corrosion and recurrent severe vibration.
2.6 Pollution class: class III, class IV.
3 FeaturesFeatures
3.1 SF6 gas-insulated
3.1.1 SF6 gas is a kind of nontoxic, nonflammable and electrical insulating gas. It has the excellent
characteristic of arc extinction.
3.2 Drivepipe with large diversity
3.2.1 In addition to the standard ceramic drivepipe, we can also provide a variety of solutions, including rubber insulators used
in the epoxy resin filling equipment
3.3 Visible open / closed status
3.3.1 It is easy to see the main contact position indicator which is color-coded just standing on the ground (Green - off; red -
closed). The indicator is directly connected with the main contacts of the drive shaft assembly to ensure accurate display of
contact states.
3.4 Quick operation
3.4.1 operating mechanism with spring energy to ensure a quick closing and opening operation (less than 100 milliseconds).
3.5 Can realize remote control
3.5.1 It is equipped with electronic controller, fit for in situ operation as well as FTU interface console operation.
3.6 Rugged switch
3.6.1 The switch is made of proven durable, corrosion-resistant materials (special used in warships 304L stainless steel
plate)which ensures that there is a very long service life (30 years), and can be implement a series of operations.It has the ideal
characteristics as a column equipment.
3.7 Standard
3.7.1 Each switch before leaving the factory has been filled with SF6 gas, sealed, and test according to IEC60265-1 (1988),
standard.
4 Type and Rating
4.1 Product mode
PGS-12/24/36-20
4.3 Types of PGS
Figure 1) ceramic bushing - molded cable outlet Figure 2) rubber split bushing - molded cable outlet
12 24 36
1 Rated voltage kV
6/10/11 15/17.5/20 33/36/36
2 Rated frequency Hz 50/60 50/60 50/60
(Lightning impulse relatively 75 125 185
Rated insulation kV
withstand voltage) Fracture 85 145 215
level(The filling
3 Power frequency relatively 42 64 95
SF6 gas 0.07Mpa
withstand voltage kV
/ 20 ° C) Fracture 50 79 110
1min
Insulation level of Power frequency withstand voltage
30
zero gauge 1min
4 kV
pressure. RP-pressure 1min 30
The highest phase voltage 5min 9
5 Rated current A 630(400) 630(400) 630(400)
6 Rated breaking load current (0.07Mpa / 20 ° C) A 630(400) 630(400) 630(400)
7 breaking current under zero gauge pressure A 630(400) 630(400) 630(400)
8 peak withstand current kA 50 50 50
9 Rated short time making current kA 50 50 50
11 rated short time withstand current KA/s 20/4 20/4 20/4
12 rated cable charging breaking current A 25 25 25
13 rated line charging breaking current A 16 16 16
14 rated closed-loop breaking current A 630(400) 630(400) 630(400)
15 exciting current A 21 21 21
16 rated current breaking times Times ≥400 ≥400 ≥400
17 rated working pressure MPa 0.07 0.07 0.25
18 Per-phase main circuit resistance μΩ ≤150 ≤150 ≤150
19 relative gas leakage rate year ≤1% ≤1% ≤1%
SF6 gas moisture Factory transfer of value ppm ≤150 ≤150 ≤150
20
content Switch running value ppm ≤300 ≤300 ≤300
21 operation of echanical stability times 6000 6000 6000
rated operating voltage and auxiliary circuits rated DC 220/ DC 220/ DC 220/
22 voltage V 110/48/24 110/48/24 110/48/24
AC 220/110 AC 220/110 AC 220/110
Type M 115 125 135
23 Weight kg
Type A 135 145 155
24 institutions boxes and controller protection class IP44 IP54
25 Type of Mounting The lifting type (suspended)/block (horizontal)
5. Structure
5.1 switch and controller appearance (Model: PGS-12/24/36)
Connection diagram
(table 2)
5.3.1 SF6 gas insulated switchgear is a three-phase linkage operation switch device designed for the
distribution system cables and overhead power line segment applications. It can be manually operated on the
scene or also can be controlled from control center.
5.3.2 The switch body using welding to seal the casing and the casing using rubber ring seal, and all the other
parts are assembled in the welding of stainless steel tank shell.
5.3.3 The switch body designed to be able to withstand pressure without affecting the switch to normal
operating performance.
5.3.4 The shell casing is made of a thickness exceeding 3 mm cold-rolled stainless steel (SUS 304L) or better
materials to withstand the internal gas pressure.
5.4Insulating gas
10
9
8
压力(kgf/cm )
7
2
6 高压泄压装置动作范围
5 (4 -6 kgf/cm2)
4 充气压力
3 (0.7 kgf/cm2)
2
低压报警装置动作范围
1
(0.3-0.4kgf/cm2)
0
-1
-1
-50 -40 -30 -20 -10 0 10 20 30 40 50 60 70 80
温度(℃)
Figure 8) temperature - pressure curve
Ground
Figure 15) ground terminal terminal
5.5.8 lug
The main box on top of the four transport lug, and four carrying handles for easy handling and lifting.
Carrying handle
Lifting lug
5.5 5.6 Polymer rubber casing
Figure 17) rubber casing Figure 18) terminal of rubber and rubber molded cable
5.6.1 The casing material is an epoxy resin and EPDM rubber or ceramic.
5.6.2 The switch inlet and outlet casing ceramic casing and casing of organic insulator, the casing creepage
5.7.1 molded cable lead, high-voltage insulated cables have a great deal of flexibility and good weather
resistance, greater than 125 mm 2 (159/1.0) nominal cross section is used to 400A, 630A when the nominal
5.7.2 The terminal type, terminal blocks for copper tinned with bus equipment clamp connection faying
surface of the outlet terminals for 76mm x 40mm cross-section to allow the current of 630 A,.
ITEM NAME
1 Backplane
2 Triangle crank
3 Spring
4 Link
5 Closing instructions
6 Tripping indication
5.8.1.2Rapid spring actuator and to seal in the switch body, does not occur condensation, corrosion, can
guarantee that the closing of the switch, opening speed is not because of the size of the power operation of
technical proficiency and closing the power supply instabilityaffected, to ensure that the switch in the
short-circuit state, with reliable breaking;
The operating mechanism uses a novel miniaturized spring operating mechanism, sub-gate open /
close position to maintain the function of opening and closing low energy consumption
The operating mechanism is placed in the sealed box of institutions, to solve the corrosion problem
of the institution, to improve the reliability of the agency. Switch points, closing operation can be
manual or electric operation and remote operation of the instruction from afar.
Can be manually or electrically operated storage. After the switch is closed, the stored energy motor
energy storage on the storage spring. After the end of the energy storage spring energy, the switch
is in the ready state of the sub-gate; storage latch, so that agencies can not be re-charged.
Switch is closed, while opening spring energy storage. Institutions in the closing state and energy
storage operations, the closing spring was again energy storage and atresia, avoid agencies
mistakenly closing. Reclose storage state agencies in the coincidence state can achieve the
"sub-0.3s-Hop sub" a reclosing operation.
Spring actuator, can guarantee the switch closing and opening speed is not because of the size of
the power operation of skilled and closing of power instability affected to ensure that the circuit
breaker short circuit condition, reliable breakingfunction;
The operating mechanism uses a novel miniaturized spring operating mechanism, sub-gate open /
close position to maintain the function of opening and closing low energy consumption;
The operating mechanism is placed in the sealed box of institutions, to solve the corrosion problem
of the institution, to improve the reliability of the agency. Switch points, closing operation can be
manual or electric operation and remote operation of the instruction from afar.
Can be manually or electrically operated storage. After the switch is closed, the stored energy motor
energy storage on the storage spring. After the end of the energy storage spring energy, the switch
is in the ready state of the sub-gate; storage latch, so that agencies can not be re-charged.
Switch is closed, while opening spring energy storage. Institutions in the closing state and energy
storage operations, the closing spring was again energy storage and atresia, avoid agencies
mistakenly closing. Reclose storage state agencies in the coincidence state can achieve the
"sub-0.3s-Hop sub" a reclosing operation.
6. electronic automatic controller
图 20)控制器外观
mounting bracket
pictorial diagram of mounting bracket
1 80
500
10 maintenance
Manufactured products, have been adjusted to the best condition, switch maintenance, generally limited
to the following conditions:
10.1 run for a certain period after the switch casing for cleaning;
10.2 within five years from the factory, due to manufacturing quality failure or leak, the manufacturer is
responsible for exchange or repair (mainly around the repair or maintenance center).
10.3 SF6 gas pressure - temperature curve Cheung shown in Figure 8.
11. transport, inspection and custody
11.1 Transport
This product must be packaged transport. Transport or lifting, not allowed to have a strong vibration,
does not allow inversion, rolling.
11.2 Acceptance
Acceptance in accordance with the following procedures:
11.2.1 indoors out of the box, packing list to check random files are complete;
11.2.2 Carefully remove the switch, bumps traces from the outside observation products, with particular
attention to whether the porcelain sets and chipped;;
11.2.3 observed gauge pressure of 0.07MPa (20 ° C) (according to user requirements to install the pressure
gauge);
11.2.4 switch trial operation five times, there should be no refuse to co-and refused grading phenomenon.
11.2.5 conditions, can detect the loop resistance values (less than 130 micro-Europe).
11.3 store
This product should be stored indoors difficult to collisions and a well-ventilated place.
All users:
Note: (1) although this manual after careful check, but still appears unavoidably omissions that with actual
se shall prevail.
(2) the instruction content if there is any change to the actual product shall prevail without prior notice.
(3) the final right of explanation belong to Zhejiang Farady Powertech Co.,Ltdif you
have any questions please contact with Zhejiang Farady Powertech Co.,Ltd