2 Technical features
3 Product specifications
Outline
Model The basic functions Optional functions
dimension
1、one channel
Single phase current measurement, RS485communication
PZ72-AI (/C)
LED digital display ;
2、one channel Analog
output(/M)
75*75mm
3、Analog
output+RS485(/MC)
Single phase current measurement, 4、RS485+2DI (/KC)
PZ72L-AI
LCD digital display ; 5、RS485+2DI2DO
(/KC)
1、one channel
Three phase current measurement, RS485communication
PZ72-AI3
LED digital display ; (/C)
75*75mm 2、one channel Analog
output(/M)
3、Analog
Three phase current measurement, output+RS485(/MC)
PZ72L-AI3 4、RS485+2DI2DO
LCD digital display ;
(/KC)
1、one channel
PZ96-AI Single phase current(or voltage) RS485communication
(/C)
PZ96-AV measurement, LED digital display ; 2、Up to three channel
Analog output(/M OR
96*96mm /M3)
3、Analog
PZ96L-AI Single phase current(or voltage) output+RS485(/MC
OR /M3C)
PZ96L-AV measurement, LCD digital display ; 4、RS485+4DI2DO
(/KC)
1、one channel
PZ96-AI3 Three phase current (or voltage) RS485communication
(/C)
PZ96-AV3 measurement, LED digital display ; 2、Up to three channel
96*96mm Analog output(/M OR
/M3)
3、Analog
PZ96L-AI3 Three phase current (or voltage) output+RS485
(/MC or /M3C)
PZ96L-AV3 measurement, LCD digital display ; 4、RS485+4DI2DO
(/KC)
Remarks: /J is one way relay output(the key is the some with the second road of DO),
have any special request, please contact us first。
4 Installation
DI DO
Note:
1. Symbol "*" represent the current inlet terminal, this connection is only for reference,
the practice is decided by actual condition
2. Alarm output relay and switch output multiplexing DO2
5 Installation guide
5.1 Outline and size of cut out
6. Ordering example
Model:PZ48-AI/C
Technical requirements:Current Conversion Ratio 50A/5A; Class 0.5.
communication:RS485 Modbus/RTU
Power supply:AC/DC220V
7、communication protocol
7.1General
PZ Series meter adopt Modbus-RTU protocol:”9600, 8, n, 1”, in it 9600 is default baud
rate; Based on request, it can be revised as 2400,4800,19200 etc. 8 indicate 8 data bits; n
indicate no parity bit;1 indicate 1 stop bit.
Error detecting: CRC16 (cyclic redundancy checks)
7.2 Protocol
When data frame reach terminal device, it enter addressed device by a simple "port".
The device remove data frame "envelope"(data head), and read data, if there is no error,
executing task requested by data, then, add the new produced data in the obtained
"envelope", return the data frame to the transmitter. Returned responding data include
following content: slave terminal address (Address), executed command (Function),
requested data produced by executing command (Data) and one CRC check code
(Check). If any error occurs, no successful responding or returning one error indication
frames.
The address domain is at the front of the frame, composed of one byte (8-Bits,8 bit
binary code), decimal scale is 0~255, in our system, only 1~247 is used, other address
is reserved. These bits indicate the terminal unit address specified by users,this unit will
accept host computer data connected with it. Every terminal unit address in the same
Fieldbus must be one and only, only the addressed terminal can respond the query
including this address. When the terminal is sending one responding, the slave machine
address data in this responding can tell host computer which terminal unit is
communicating with it.
The function domain code tells the addressed terminal which function shall be executed.
The function code and its meaning and function in this Series meters are listed below:
Code(hex) Meaning Operation
Obtain current binary system value of one or
03H Read holding register
multiple holding register
Set actual binary system value into a series of
10H Preset multiple register
continuous holding register
The data domain includes: the needed data for terminal to execute specified function or
the collected data when terminal respond the query. These data may be value,parameter
address or setting.
Example:Function domain tell terminal unit to read one register, data domain must specify:
The reading is starting from which register and how many data is needed. For the
embedded address and data, the content depends on the different type and different slave
machine.
7.2.5 Error check domain
This domain adopts CRC16 cyclic redundancy check, for host computer and terminal,
the error in checking and transmitting is allowable. Due to electric noise and other
interfere, when one group of data is transmitting from one device to another device, on the
transmitting line, some change may be produced. The error check can enable the host
computer or slave computer not responding those changed data, so, safety, reliability and
efficiency of system are upgraded.
15 … 10 9 8 7 6 5 4 3 2 1 0
(R) HIGH, LOW alarm (R) HIGH, LOW alarm (R/W) HIGH, LOW alarm
Indication Indication Indication
0005H Uc Exponential
0007H Ia Exponential
000bH Ic Exponential
Explanation:
000cH ① “-” indicate Reserved word
… or Reserved bit.
— Reserved word
② voltage, current etc.
0029H data numerical value
Detail explanation Computing Method:
002aH Alarm and I/O Reading = Effective value×
see below
10E( Exponential-3)
Voltage
002bH Pt
transformation ratio
Current
002cH Ct
transformation ratio
002dH IL Effective value
Residual current
002eH IL Exponential
002fH
— Reserved word
…
002aH: alarm and switching Input / output condition word (control word):
15 14 13 12 11 10 9 8
(R)unbalance alarm
(R) HIGH, LOW alarm Indication
Indication
7 6 5 4 3 2 1 0
ACREL CO.,LTD