PZ series programmable

ammeters & voltmeters


1 General
PZ series ammeters and voltmeters are programmable and intelligent, which adopt
AC sampling technology, and can measure current and voltage directly. They can be used
for local display, and also can be connected with the industrial control equipment to form
the measurement and control system.
It can be equipped with RS485 communication interface under Modbus-RTU
protocol;Electric signals can be converted to the standard analog output ;
it can be with 1 channel alarm or 4(2) channels DI/2 channels DO. According to
different request,meter’s parameters can be set by keys on its panel.

2 Technical features

Technical Parameters Value

AC voltage: AC100V, 220V, 380V; AC current: AC1A, 5A;


Nominal value
(Special specifications can be prior consultation)
Voltage: 1.2 times(continuous), 2 times/1s;
Input Overload
Current: 1.2 times(continuous), 10 times/1s
Frequency 45Hz~65Hz
Consumption < 0.5VA
Accuracy 0.5 class
LED or LCD, set multiplying power at will. Alarm、switching
indication: Analog, programmable settings corresponding
to display PZ48 three-phase table display mode
Display
programmable three-phase data display, rotational or
manual switching display (press the right and left key
switch), the corresponding indicator light will be bright.
RS485,Modbus-RTU protocol;1 start bit, 8 data bits, 1
communication stop bit, No parity; the baud rate:2400/4800/9600/19200
bps
Function
1 channel passive relay; Contact capacity 1A/30VDC,
Alarm
1A/250VAC,High, low, unbalance alarm etc.
DC4~20mA、DC0~20mA(Load < 600Ω),
Analog
DC0~5V(Load > 1kΩ)etc.
2 or 4 channel dry contacts, power inside,
input
Optocoupler isolation.
Switching 2 switch outputs, the normally open contact of the
output relay
Contact capacity: 1A/30VDC, 1A/250VAC.
Voltage range AC85~265V or DC100-350V
Power
Power
supply < 5VA
consumption
Insulation resistance ≥ 100MΩ
Power frequency withstand
2kV/1min(RMS)
voltage
Mean time between failures ≥ 50000h
Operation:-10℃~+55℃(LED display);-10℃~+45℃(LCD
Temperature display)
Enviro
Storage:-20℃~+70℃
nment
Humidity ≤ 93%RH,no condensation,without corrosive
Altitude ≤ 2500m

3 Product specifications

Outline
Model The basic functions Optional functions
dimension

Single phase current 1、one channel


PZ48-AI
measurement,LED digital display ; 48*48mm RS485communication
(/C)
Single phase I measurement, LCD 2、one channel Analog
PZ48L-AI
digital display ; output(/M)

Three phase current measurement,


PZ48-AI3
LED digital display ; 48*48mm
None
Three phase current measurement,
PZ48L-AI3
LCD digital display ;

1、one channel
Single phase current measurement, RS485communication
PZ72-AI (/C)
LED digital display ;
2、one channel Analog
output(/M)
75*75mm
3、Analog
output+RS485(/MC)
Single phase current measurement, 4、RS485+2DI (/KC)
PZ72L-AI
LCD digital display ; 5、RS485+2DI2DO
(/KC)

1、one channel
Three phase current measurement, RS485communication
PZ72-AI3
LED digital display ; (/C)
75*75mm 2、one channel Analog
output(/M)
3、Analog
Three phase current measurement, output+RS485(/MC)
PZ72L-AI3 4、RS485+2DI2DO
LCD digital display ;
(/KC)
1、one channel
PZ96-AI Single phase current(or voltage) RS485communication
(/C)
PZ96-AV measurement, LED digital display ; 2、Up to three channel
Analog output(/M OR
96*96mm /M3)
3、Analog
PZ96L-AI Single phase current(or voltage) output+RS485(/MC
OR /M3C)
PZ96L-AV measurement, LCD digital display ; 4、RS485+4DI2DO
(/KC)

1、one channel
PZ96-AI3 Three phase current (or voltage) RS485communication
(/C)
PZ96-AV3 measurement, LED digital display ; 2、Up to three channel
96*96mm Analog output(/M OR
/M3)
3、Analog
PZ96L-AI3 Three phase current (or voltage) output+RS485
(/MC or /M3C)
PZ96L-AV3 measurement, LCD digital display ; 4、RS485+4DI2DO
(/KC)

Remarks: /J is one way relay output(the key is the some with the second road of DO),
have any special request, please contact us first。

4 Installation

4.1 For single phase ammeters、voltmeters

4.2 For three phase ammeters


4.3 For three phase voltmeters

3P3W 3P3W 3P4W

4.4 power supply,RS485 communication terminals

Power supply RS485 communication

4.5 Analog output terminals

4.6 DI/DO(alarm) terminals

DI DO
Note:
1. Symbol "*" represent the current inlet terminal, this connection is only for reference,
the practice is decided by actual condition
2. Alarm output relay and switch output multiplexing DO2
5 Installation guide
5.1 Outline and size of cut out

Outline Panel size Housing size Cutout size

unit:mm Height Width Height Width Depth Width Height


48*48 48 48 43.8 43.8 100 45 45
75*75 75 75 66 66 98 67 67
96*96 96 96 86 86 85 88 88

5.2 Outline diagrams

5.3 Installation diagrams

6. Ordering example
Model:PZ48-AI/C
Technical requirements:Current Conversion Ratio 50A/5A; Class 0.5.
communication:RS485 Modbus/RTU
Power supply:AC/DC220V

7、communication protocol
7.1General
PZ Series meter adopt Modbus-RTU protocol:”9600, 8, n, 1”, in it 9600 is default baud
rate; Based on request, it can be revised as 2400,4800,19200 etc. 8 indicate 8 data bits; n
indicate no parity bit;1 indicate 1 stop bit.
Error detecting: CRC16 (cyclic redundancy checks)
7.2 Protocol
When data frame reach terminal device, it enter addressed device by a simple "port".
The device remove data frame "envelope"(data head), and read data, if there is no error,
executing task requested by data, then, add the new produced data in the obtained
"envelope", return the data frame to the transmitter. Returned responding data include
following content: slave terminal address (Address), executed command (Function),
requested data produced by executing command (Data) and one CRC check code
(Check). If any error occurs, no successful responding or returning one error indication
frames.

7.2.1 Data frame format

Address Function Data Check

8-Bits 8-Bits N×8-Bits 16-Bits

7.2.2 Address (Address) domain

The address domain is at the front of the frame, composed of one byte (8-Bits,8 bit
binary code), decimal scale is 0~255, in our system, only 1~247 is used, other address
is reserved. These bits indicate the terminal unit address specified by users,this unit will
accept host computer data connected with it. Every terminal unit address in the same
Fieldbus must be one and only, only the addressed terminal can respond the query
including this address. When the terminal is sending one responding, the slave machine
address data in this responding can tell host computer which terminal unit is
communicating with it.

7.2.3 Function domain

The function domain code tells the addressed terminal which function shall be executed.
The function code and its meaning and function in this Series meters are listed below:
Code(hex) Meaning Operation
Obtain current binary system value of one or
03H Read holding register
multiple holding register
Set actual binary system value into a series of
10H Preset multiple register
continuous holding register

7.2.4 Data domain

The data domain includes: the needed data for terminal to execute specified function or
the collected data when terminal respond the query. These data may be value,parameter
address or setting.
Example:Function domain tell terminal unit to read one register, data domain must specify:
The reading is starting from which register and how many data is needed. For the
embedded address and data, the content depends on the different type and different slave
machine.
7.2.5 Error check domain

This domain adopts CRC16 cyclic redundancy check, for host computer and terminal,
the error in checking and transmitting is allowable. Due to electric noise and other
interfere, when one group of data is transmitting from one device to another device, on the
transmitting line, some change may be produced. The error check can enable the host
computer or slave computer not responding those changed data, so, safety, reliability and
efficiency of system are upgraded.

7.3 Parameter address table


7.3.1 Single phase meter

Address Content Brief Explanation


Read/Write: R - read; W
0000H U Effective value voltage(unit:V) - write
0~9999 The 00212H is partial
0001H U Exponential
writable, the rest is
0002H I Effective value current(unit:A) read-only.
0~9999 Explanation::
0003H I Exponential
voltage, current data
0010H Pt Voltage transformation ratio numerical value
Computing Method:
0011H Ct Current transformation ratio
Reading = Effective
0012H Alarm and I/O Detail explanation see below value×
10E( Exponential-3)
0013H After this are reserved words.

0012H: alarm and switching Input / output condition words:

15 … 10 9 8 7 6 5 4 3 2 1 0

— AL.L AL.H DI1 DI2 — — DO1 DO2

(R) HIGH, LOW alarm (R) HIGH, LOW alarm (R/W) HIGH, LOW alarm
Indication Indication Indication

Note:① — Said a reserved word or reserved bit。


② Alarming mark bit: 1 for alarming, 0 for no alarming.
7.3.2 Three phase meter communication parameter address meter (word):

Address Content Brief Explanation Brief Explanation

0000H Ua Effective value


Three phase voltage Read/Write: R - read; W - write ,
0001H Ua Exponential Three phase three The 002aH is partial writable,
0002H Ub Effective value wire: Line Voltage the rest is read-only.
Three phase four
0003H Ub Exponential wire: Phase
0004H Uc Effective value voltage

0005H Uc Exponential

0006H Ia Effective value

0007H Ia Exponential

0008H Ib Effective value


Three phase current
0009H Ib Exponential

000aH Ic Effective value

000bH Ic Exponential
Explanation:
000cH ① “-” indicate Reserved word
… or Reserved bit.
— Reserved word
② voltage, current etc.
0029H data numerical value
Detail explanation Computing Method:
002aH Alarm and I/O Reading = Effective value×
see below
10E( Exponential-3)
Voltage
002bH Pt
transformation ratio
Current
002cH Ct
transformation ratio
002dH IL Effective value
Residual current
002eH IL Exponential

002fH
— Reserved word

002aH: alarm and switching Input / output condition word (control word):

15 14 13 12 11 10 9 8

— AL.-b AL.Lo1 AL.Hi1 AL.Lo2 AL.Hi2 AL.Lo3 AL.Hi3

(R)unbalance alarm
(R) HIGH, LOW alarm Indication
Indication

7 6 5 4 3 2 1 0

DI1 DI2 DI3 DI4 — DO1 DO2

Switching Input Indication(R) 1 indicate switching output Indication (R/W) 1


closing, 0 opening closing, 0 opening

ACREL CO.,LTD