Concrete Beam Design, For New or Existing, Based On ACI 318-19
Concrete Beam Design, For New or Existing, Based On ACI 318-19
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Concrete Beam Design, for New or Existing, Based on ACI 318-19
ANALYSIS
CHECK FLEXURAL CAPACITY max = 0.003 0.85 f c'
A s' f s'
2 0.85 f 'C , E c 57 f C' , E s 29000ksi
o max or
Ec Fc
2
c c , for 0
0.85 f C 2
'
c o Parabolic
fC o o
'
0.85 f C , for c o
A sfy
s E s , for s t
fS
f , for s t
y
Cover = 1.5 in, (ACI 318 20.6.1) rprov'd = 0.0055 < rmax = 0.0119 , (ACI 318 9.3.3.1)
d= 45.44 in > rmin = 0.0033 , (ACI 318 9.6.1)
d' = 2.44 in [Satisfactory]
f= 0.90 , (ACI 318-19 21.2) c= 5.39 in, by pure math method
e c,max = 0.0006 Fc = 334.34 kips
es,max = 0.0050 , (ACI 318-19 21.2.2) dc = 1.85 in
d '
MIN ( , 24) for V s 4b wd f c
2
S max, shear
MIN ( d , 12) for V s 4b wd f ' = 22 > S= 12 in
4 c [Satisfactory]
(cont'd)
CHECK TORSION CAPACITY
Check section limitation (ACI 22.7.7.1)
2
V u T u Ph
2
V C 8 f 'c where f= 0.75 (ACI 21.2)
b d 1.7 2 b d
w Aoh w Ph = 258 in, (perimeter of centerline of outermost closed
transverse torsional reinforcement.)
Aoh = 1,287 in2 (area enclosed by centerline of the outermost
0.215 < 0.474 [Satisfactory] closed transverse torsional reinforcement.)
T u 4 f c
P cp
Determine the corresponding area of longitudinal reinforcement (derived from ACI 22.7.6.1 & 9.6.4.3)
25b w
'
At f yv 5 Acp f c f
A L MAX P h , P h yv MAX At ,
s f yL f yL f yL s f yv
0.00 in2