Doc.No.CE093A/GS/D04/0301 - Rev.

D E W A Contract CE/093/2002 -
132/11KV GOLDEN SANDS SUBSTATION

11kV Switchgear CT Calculation

CT CALC-093-GS-11kV SWGR,1
a) General Data :-

1) System voltage, kV = 11 kV

2) System fault level, If = 25 kA, 3 sec.

3) CT Manufacturer = M/s.ETAH, Malaysia

CT CALC-093-GS-11kV SWGR,2
b) Lead Resistance Calculation

2.5 Sq.mm Cable

From Manufacturer’s table,

With a size of 2.5 sq.mm cable the lead resistance = 7.41 Ohms/Km
at 20ºC
= 0.00741 Ohms/Meter

CT CALC-093-GS-11kV SWGR,3
Temperature co-efficient of resistance ( 20) = 0.00393

RL at 75 C = R 20 [ 1 +  20 (T2 - T1) ]


= 0.009 Ohms / Metre

i) Lead length for protection relays in = 50 Meters


11kV Buszone & 132kV Relay panel

Therefore RL for corresponding length = 50 x 0.009


= 0.45 Ohms.

CT CALC-093-GS-11kV SWGR,4
ii) Lead length for protection relays within = 5 Meters
switchgear is considered

Therefore RL for corresponding length = 5 x 0.009


= 0.045 Ohms.

iii) Lead length for protection relays in 11kV = 100 m


swgr. & Neutral CT

CT CALC-093-GS-11kV SWGR,5
Therefore RL for corresponding length = 100 x 0.009
= 0.9 Ohms.

Doc.No.CE093A/GS/D04/0301

I) IDT CIRCUITS

CT CALC-093-GS-11kV SWGR,6
1) T3L :-

Application : Transformer Differential & ET HV REF protection


Relay type/Make : DUOBIAS – M , M/s.VA Tech. Reyrolle,U.K /
DCD 124A ,M/s.VA Tech Reyrolle, U.K
CT Ratio : 3200/1A

1.1) CT Requirement for Transformer Differential Protection

The relay for this protection application will be mounted at 132kV Relay panel.

CT CALC-093-GS-11kV SWGR,7
Calculation of VK at 11kV Side

As per M/s.Reyrolle recommendations, the knee point voltage of CT’s is governed by the
following relation :

Vk  4I (A + C)

Vk = Knee point voltage in volts

CT CALC-093-GS-11kV SWGR,8
I = Either the maximum three phase through fault current limited by the
Transformer impedance or the high set setting which ever is greater.

A = CT Sec. resistance at 75C in Ohms. = 14 Ohms.

C = CT Sec. loop resistance = 2 x 0.45 = 0.9 Ohms.

Transformer impedance considered = 31.5%

CT CALC-093-GS-11kV SWGR,9
Fault MVA = 50 = 158.73 MVA
0.315

The maximum through fault current = 158.73 x 103


 3 x 11

= 8331 Amps

Corresponding secondary current = 8331


3200

CT CALC-093-GS-11kV SWGR,10
= 2.6 Amps

Doc.No.CE093A/GS/D04/0301

CT CALC-093-GS-11kV SWGR,11
Hence, the selected value of I = 3 Amps

Vk  4 x 3 (14 + 0.9)

 178.8 Votls

CT CALC-093-GS-11kV SWGR,12
Therefore Vk requiredfor transformer differential protection

= 180 Volts

CT CALC-093-GS-11kV SWGR,13
CT CALC-093-GS-11kV SWGR,14
CT CALC-093-GS-11kV SWGR,15
Doc.No.CE093A/GS/D04/0301

1.2) CT Requirement for Main Transformer LV REF/ Earthing Transformer


HV REF Protection :-

Relay type/Make : DCD124A, M/s.VA Tech Reyrolle, U.K


CT Ratio : 3200/1A
Class of accuracy : CL.X

CT CALC-093-GS-11kV SWGR,16
1.2.1) Calculation of Knee Point Voltage VK :-

The calculation of knee point voltage for REF Protection is carried out as per
ESI 48 – 3.

1.2.1.1) Stability Voltage Setting Vs :-

As per clause 7.3.1 & Fig. 9 of ESI 48 – 3

CT CALC-093-GS-11kV SWGR,17
(i) Consider an external phase to earth short circuit and assume complete
saturation of a line CT, then Vs shall not be less than

Vs > IF [A+B+F+G+(T2/T3)2 (H+2K+Rb) ] T1

Where
IF = Fault current corresponding to rated stability limit.

= 16 times rated current of power transformer


considered for phase fault

CT CALC-093-GS-11kV SWGR,18
= 16 x 50 x 103
3 x 11

= 41990 Amps (for phase fault)

= 2000 Amps (for earth fault based on earthing


transformer rating)

T1 = Turns ratio of line and neutral CTs.

CT CALC-093-GS-11kV SWGR,19
= 1__
3200

A = Resistance of wiring plus CT secondary winding for


line CT

= RCT + RL

CT CALC-093-GS-11kV SWGR,20
Where, RL = Lead resistance for 50 Meters length = 0.45 Ohms

Doc.No.CE093A/GS/D04/0301

Therefore A = 14 + 0.45

= 14.45 Ohms

CT CALC-093-GS-11kV SWGR,21
N = Resistance of wiring plus CT secondary winding for
neutral CT.

= RCT + RL

Where, RL = Lead resistance for 100 Meters length = 0.9 Ohms

Therefore N = 14 + 0.9 = 14.9 Ohms

CT CALC-093-GS-11kV SWGR,22
B = Resistance of wiring = RL
= 0.45 Ohms

F, G, K, H = Resistance of wiring

= Already included in A, B, N above

= 0

Rb = Resistance of bias coil

CT CALC-093-GS-11kV SWGR,23
= 0 (Not applicable)

T2/T3 = Turns ratio of interposing CTs

= 0 (Not applicable)

Vs  2000 x (14.45 + 0.45 + 0)


3200

CT CALC-093-GS-11kV SWGR,24
 9.3125 Volts

(ii) Consider an external phase to earth short circuit and assume complete
saturation of Neutral CT, then Vs shall not be less than

Vs  IF (N) T1

 2000 x 14.9
3200

CT CALC-093-GS-11kV SWGR,25
 9.3125 Volts

Doc.No.CE093A/GS/D04/0301

CT CALC-093-GS-11kV SWGR,26
(iii) Consider an external phase to phase short circuit and assume complete
saturation of a line CT, then Vs shall not be less than

Vs  IF (A+G+(T2/T3)2 (H + 3k + 3Rb/2) T1 Volts

 41990 x 14.45
3200
 189.6 Volts

CT CALC-093-GS-11kV SWGR,27
(iv) Consider an external three-phase short circuit and assume complete
saturation of a line CT, then Vs shall not be less than

Vs  IF (A+G+(T2/T3)2 (H + 3k + 3Rb/2) T1 Volts

 41990 (14.45 + 0)
3200
 189.6 Volts

From (i), (ii), (iii) & (iv) above, consider the stability voltage setting of

CT CALC-093-GS-11kV SWGR,28
Vs = 210 Volts

1.2.1.2) Knee Point Voltage VK :-

As per ESI 48 – 3, the knee point voltage of CTs for REF protection shall be
atleast twice that of stability voltage setting

Vk  2 Vs

CT CALC-093-GS-11kV SWGR,29
 2 x 210

 420 Volts

However as per item 1.1, the Vk required for transformer differential protection is
180 V.

Hence the required Vk  420 Volts

CT CALC-093-GS-11kV SWGR,30
CT CALC-093-GS-11kV SWGR,31
Doc.No.CE093A/GS/D04/0301

1.3) Magnetising Current Imag :-

CT CALC-093-GS-11kV SWGR,32
As per ESI 48 – 3 when the protected winding of the transformer is not connected
to a solidly earthed power system, the fault setting shall be between 10% and 25%
of the minimum current available for earth fault at the transformer terminals

Minimum fault current at 11kV bus = 2000A

The fault setting shall be between 200 to 500 A

Primary operating current IOP = (Is + In + 3 I1 + Im) / T1

CT CALC-093-GS-11kV SWGR,33
Where

Is = Relay setting current


= 0.1A

In = Neutral CT magnetizing
current at Vk/2

= 3 mA at Vk/2

CT CALC-093-GS-11kV SWGR,34
I1 = Line CT magnetizing
current at Vk/2

= 3 mA at Vk/2

T = Turns ratio

= 1_
3200

CT CALC-093-GS-11kV SWGR,35
Im = Metrosil current

= 5 mA (Assumed)

Iop = [0.1+0.003+(3x0.003)+
0.005]x3200

= 374.4 Amps.

= 18.7%

CT CALC-093-GS-11kV SWGR,36
Approximate 19% of the minimum earth fault current.

Doc.No.CE093A/GS/D04/0301

CT CALC-093-GS-11kV SWGR,37
Since the fault setting is between 10% and 25% of the rated current of the
protected winding, as per ESI 48 – 3, the selected magnetizing current 3 mA is
suitable for the system protection

1.4) Stabilising Resistor :-

Relay voltage setting Vs = 210 Volts

Relay current setting Is = 0.1A

CT CALC-093-GS-11kV SWGR,38
Relay burden VA = 0.2 VA

Stabilising resistor Rsr = Vs - VA


Is Is2

= 210 - 0.2_
0.1 0.12

= 2080 Ohms.

CT CALC-093-GS-11kV SWGR,39
Selected stabilizing resistor = 0 – 2700 Ohms (variable)

1.5) Requirement of Metrosil :-

The maximum voltage in the absence of CT saturation is

Vf = IF T1 (RCT+2RL+RSR+Rrelay)

CT CALC-093-GS-11kV SWGR,40
= 13.12 (14 + (2 x 0.45) + 2080 + 100)

= 28797.1 Volts

Peak voltage developed across relay

Vp = 2  2Vk (Vf – Vk)

CT CALC-093-GS-11kV SWGR,41
Doc.No.CE093A/GS/D04/0301

CT CALC-093-GS-11kV SWGR,42
Vk = 550V (Actual knee pt. voltage of CT)

= 2  2 x 550 (28797.1 - 550)

= 11148 Volts

Since peak voltage developed across relay is more than 3 kV, metrosil is
provided.

CT CALC-093-GS-11kV SWGR,43
Type : 600A / S1 / S1088

C : 900

 : 0.25

CT Provided by the Manufacturer :-

CT Ratio : 3200/1 A

CT CALC-093-GS-11kV SWGR,44
Class of accuracy : CL X

CT Secondary resistance at 75ºC, Rct  14 Ohms

Knee point voltage Vk  550 Volts

Magnetising current, Imag  3mA at Vk/2

CT CALC-093-GS-11kV SWGR,45
Rated continuous thermal current : 120%

CT CALC-093-GS-11kV SWGR,46
CT CALC-093-GS-11kV SWGR,47
Doc.No.CE093A/GS/D04/0301

2) CT : - T3L1

CT CALC-093-GS-11kV SWGR,48
Application : 3 Pole O/C Protection & Energy meter + BCU
Type : DCD314B,M/s. VA Tech Reyrolle, U.K/Prometer,CEWE
CT Ratio : 3200 – 1600/1A

2.1) Calculation of Burden at Rated Current :-

1) DCD 314B = 0.05 VA

2) BCU = 0.1 VA

CT CALC-093-GS-11kV SWGR,49
3) Cabling loop = 0.09 VA

4) ICT = 1.00 VA

5) Energy meter = 0.2 VA


------------
Total = 1.44 VA
------------
Total burden required = 1.44 VA

CT CALC-093-GS-11kV SWGR,50
2.2) Verification of Accuracy limit factor

The CT VA rating considering rated resistance burden shall be  the total actual burden
considering actual resistance burden
i.e., VACT  (ALF) x (VADEVICE + VACTR) - VACTR
N

Maximum fault current on the 11kV System is 25 kA.

CT CALC-093-GS-11kV SWGR,51
Required ALF = 25,000 = 7.813 For 3200 A tap………(i)
3,200

= 25,000 = 15.625 For 1600 A tap………(ii)


1,600

N = Rated accuracy limit factor

= 15

CT CALC-093-GS-11kV SWGR,52
VACT = CT Rated burden

= 15 – 15 VA

Doc.No.CE093A/GS/D04/0301

CT CALC-093-GS-11kV SWGR,53
VADEVICE = Actual connected burden

= 1.44 VA

VACTR = CT Secondary resistance


19.5 Ohms for 3200 A tap
9.5 Ohms for 1600 A tap

VACT  7.813 [1.44 + 19.5] – 19.5

CT CALC-093-GS-11kV SWGR,54
15

 - 8.59 For 3200 A Tap

VACT  15.625 [1.44 + 9.5] – 9.5


15

 1.89 For 1600 A Tap

Hence, accuracy limit factor of 15 and burden 15 VA are adequate for both the CT taps.

CT CALC-093-GS-11kV SWGR,55
CT Provided by the Manufacturer :-

Current transformer ratio : 3200 - 1600 / 1A

Class of accuracy : CL 5P15

Burden : 15 VA - 15 VA

CT CALC-093-GS-11kV SWGR,56
Rated continuous thermal current : 120% - 120%

CT CALC-093-GS-11kV SWGR,57
CT CALC-093-GS-11kV SWGR,58
Doc.No.CE093A/GS/D04/0301

4) T2L & T2L/1 : -

Application : High Impedance Busbar Protection


Relay type/Make : MCAG 34, M/s.Alstom, UK
CT Ratio : 3200/1A

CT CALC-093-GS-11kV SWGR,59
4.1) Calculation of VK :-

4.1.1) Voltage Setting Vs :-

As per ESI 48 – 3, clause 7.12, fig 18

(i) Consider an external phase to earth short circuit and assume complete saturation
of a line CT, then Vs shall not be less than

Vs > IF [A+D+2G] T

CT CALC-093-GS-11kV SWGR,60
Where

IF = Fault current corresponding to rated stability limit.


(100 percentage of switchgear short circuit rating as per
clause 5.6 of ESI 48 – 3)

= 25 kA

A = Resistance of wiring plus CT secondary winding

CT CALC-093-GS-11kV SWGR,61
= RCT + RL

= 10 + 0.45

= 10.45 Ohms.

D = Lead burden

= 0.45 Ohms.

CT CALC-093-GS-11kV SWGR,62
G = Lead burden (Already included in A & D)

= 0 Ohms

T = Turns ratio

= 1__
3200

CT CALC-093-GS-11kV SWGR,63
Doc.No.CE093A/GS/D04/0301

Therefore, Vs  25000 (10.45 + 0.45)


3200

CT CALC-093-GS-11kV SWGR,64
 85.16 ~ 85 Volts

(ii) Also consider phase to phase or 3 phase external short circuit and assume
complete saturation of a line CT, then Vs shall not be less than

Vs = IF (A+G) T

 25000 (10.45 + 0)
3200

CT CALC-093-GS-11kV SWGR,65
 81.64 Volts ~ 82 Volts

From (i) & (ii) above, consider voltage setting of Vs = 95 Volts

4.1.2) Knee Point Voltage Calculation :-

As per ESI 48 – 3, the knee point voltage of CT’s shall be atleast twice the value of
setting voltageVs

CT CALC-093-GS-11kV SWGR,66
Knee point voltage Vk  2 x Vs

 2 x 95

 190 Volts

4.2) Magnetising Current Imag :-

As per ESI 48 – 3, the fault setting shall be between 10% and 30% of a minimum fault
current available

CT CALC-093-GS-11kV SWGR,67
Minimum fault current at 11kV bus = 2000 Amps.

The fault setting shall be between 200 and 600 Amps.

Effective primary fault setting, Ifs is given by

Ifs = [Is + nI1 + Isr + Ims] / T Amps.

Where,

CT CALC-093-GS-11kV SWGR,68
Is = Selected Relay Setting Current = 0.05 Amps.

n = No. of CT’s in parallel for = 57


CHECK Zone.

Doc.No.CE093A/GS/D04/0301

CT CALC-093-GS-11kV SWGR,69
= No. of CT’s in parallel for = 20 (for zone-1& zone-3)
DISC. Zone (minimum)

I1 = Magnetising current at Vs = 0.002 Amps

Isr = Current drawn by the supervision = (95/90,000)


Relay at Vk/2

Ims = Metrosil current at selected voltage = 0.005A (Assumed)


Setting

CT CALC-093-GS-11kV SWGR,70
Ifs (For check zone) = [0.05 + (57x0.002) + (95/90,000) + 0.005] x 3200

= 544 Amps.

= 27.2% of minimum fault current

Ifs (For disc.zone) = [0.05 + (20x0.002) + (95/90,000) + 0.005] x 3200

= 307.4 Amps.

CT CALC-093-GS-11kV SWGR,71
= 15.4% of minimum fault current

4.3) Stabilising Resistor :-

Approximate value of series = Vs VA


Is - Is2
= 95.00 - 1
0.05 (0.05)2

CT CALC-093-GS-11kV SWGR,72
= 1500 Ohms

Hence, selected value of Rsr = 0-2700 Ohms (variable)

4.4) Metrosil :-

The maximum voltage in the absence of CT saturation

Vf = IF T (Rct + 2RL + Rsr + Rrelay)

CT CALC-093-GS-11kV SWGR,73
= 25,000 x (10+(2x0.45)+1500+400)
3200

= 14929 Volts

CT CALC-093-GS-11kV SWGR,74
Doc.No.CE093A/GS/D04/0301

Peak voltage developed across the relay,

Vp = 2 2 Vk (Vf – Vk)

= 2 2 x 200 (14929 - 200)

CT CALC-093-GS-11kV SWGR,75
= 4855 Volts

Since the peak voltage developed across the relay is more than 3kV, metrosils are
provided.

Type = 600A / S3 / I / S802

C = 450

 = 0.25

CT CALC-093-GS-11kV SWGR,76
CT Provided by Manufacturer

CT Ratio : 3200/1 A

Class of accuracy : CL X

CT Secondary Resistance at 75 C, Rct  10 Ohms.

Knee point voltage, Vk  200 Volts

CT CALC-093-GS-11kV SWGR,77
Magnetising Current, Imag  2 mA at Vk/2

Rated continuous thermal current : 120%

CT CALC-093-GS-11kV SWGR,78
CT CALC-093-GS-11kV SWGR,79
Doc.No.CE093A/GS/D04/0301 - Rev.A

5) T3LN Core 1 :-

ET HV Neutral CT : -

Application : Standby Earth fault protection

CT CALC-093-GS-11kV SWGR,80
Relay type/Make : DCD114A,VA Tech Reyrolle,U.K
CT Ratio : 3200 – 1600/1A

5.1) Calculation of Burden at Rated Current :-

1) DCD114A = 0.05 VA

2) Cabling loop = 1.8 VA


------------
Total = 1.85 VA

CT CALC-093-GS-11kV SWGR,81
------------
Total burden required = 1.85 VA

5.2) Verification of Accuracy limit factor


The CT VA rating considering rated resistance burden shall be  the total actual burden
considering actual resistance burden
i.e., VACT  (ALF) x (VADEVICE + VACTR) – VACTR
N

CT CALC-093-GS-11kV SWGR,82
Maximum fault current on the 11kV System is 25 kA.

Required ALF = 25,000 = 7.81 For 3200 A tap


3200

= 25,000 = 15.625 For 1600 A tap


1,600

N = Rated accuracy limit factor

CT CALC-093-GS-11kV SWGR,83
= 20

VACT = CT Rated burden

= 15VA

VADEVICE = 1.85 VA

VACTR = CT Secondary resistance


23.3 Ohms for 3200 A tap

CT CALC-093-GS-11kV SWGR,84
11.4 Ohms for 1600 A tap

Doc.No.CE093A/GS/D04/0301 - Rev.A

VACT  7.81 [1.85 + 23.3] - 23.3


20

CT CALC-093-GS-11kV SWGR,85
 - 13.48 For 3200 A tap

VACT  15.625 [1.85 + 11.4] - 11.4


20

 -1.05 for 1600 A tap

Hence, accuracy limit factor of 15 and burden 15 VA are adequate for both the CT taps.

CT CALC-093-GS-11kV SWGR,86
CT Provided by the Manufacturer :-

Current transformer ratio : 3200 - 1600 / 1A

Class of accuracy : CL 5P20 - CL 5P20

Burden : 15 VA - 15 VA

CT CALC-093-GS-11kV SWGR,87
Rated continuous thermal current : 120% - 120%

CT CALC-093-GS-11kV SWGR,88
CT CALC-093-GS-11kV SWGR,89
Doc.No.CE093A/GS/D04/0301

6) T3LN Core 2 :-

ET - HV Neutral CT : -

Application : REF Protection


Relay type / Make : DCD124A , M/s.VA Tech Reyrolle, U.K

CT CALC-093-GS-11kV SWGR,90
CT Ratio : 3200 / 1A

For knee point voltage calculation, magnetizing current requirement, please refer the
calculation of for item 1.2.

CT Provided by the Manufacturer :-

Current transformer ratio : 3200 / 1A

Class of accuracy : CL X

CT CALC-093-GS-11kV SWGR,91
CT Secondary resistance 75 deg. C, Rct  14 Ohms.

Knee point voltage, Vk  550 Volts

Magnetising current, Imag  3 mA at Vk/2

Rated continuous thermal current : 120%

CT CALC-093-GS-11kV SWGR,92
CT CALC-093-GS-11kV SWGR,93
CT CALC-093-GS-11kV SWGR,94
Doc.No.CE093A/GS/D04/0301 - Rev.A

II) OUTGOING FEEDER CIRCUITS (WITH METERING)

1) CT Core T7L :-

Application : 3 O/C & E/F Protection + BCU


Relay Type / Make : DCD314B/DCD114A, M/s.VA Tech. Reyrolle, U.K

CT CALC-093-GS-11kV SWGR,95
CT Ratio : 400 / 1A

1.1) Calculation of Burden at Rated Current :-

1) DCD314B = 0.05 VA

2) DCD114A = 0.05 VA

3) BCU = 0.1 VA

CT CALC-093-GS-11kV SWGR,96
4) Cabling loop = 0.09 VA
------------
Total = 0.29 VA
------------
Total burden required = 0.29 VA

1.2) Verification of Accuracy limit factor

CT CALC-093-GS-11kV SWGR,97
The CT VA rating considering rated resistance burden shall be  the total actual burden
considering actual resistance burden
i.e., VACT  (ALF) x (VADEVICE + VACTR) – VACTR
N

Maximum fault current on the 11kV System is 25 kA.

Required ALF = 25,000 = 62.5 For 400A tap


400

CT CALC-093-GS-11kV SWGR,98
N = Rated accuracy limit factor
= 15

VACT = CT Rated burden

= 15VA

VADEVICE = 0.29 VA

VACTR = CT Secondary resistance

CT CALC-093-GS-11kV SWGR,99
3 Ohms for 400 A tap

Doc.No.CE093A/GS/D04/0301 - Rev.A

VACT  62.5 [0.29 + 3] - 3


15

 10.7 For 400A tap

CT CALC-093-GS-11kV SWGR,100
Hence, accuracy limit factor of 15 and burden 15 VA are adequate for the CT ratio,
400/1A.

CT Provided by the Manufacturer :-

Current transformer ratio : 400 / 1A

Burden : 15 VA

CT CALC-093-GS-11kV SWGR,101
Class of accuracy : 5P15

Rated continuous thermal current : 120 %

CT CALC-093-GS-11kV SWGR,102
CT CALC-093-GS-11kV SWGR,103
CT CALC-093-GS-11kV SWGR,104
Doc.No.CE093A/GS/D04/0301 - Rev.A

CT CALC-093-GS-11kV SWGR,105
2) CT Core T7L1 :-

Application : Metering
Type/Make : Energymeter - Prometer 3222, M/s.CEWE,Sweden
MDI 244-16XG, M/s.Crompton
CT Ratio : 400/1A

2.1) Calculation of Burden at Rated Current :-

CT CALC-093-GS-11kV SWGR,106
1) Energy meter (Prometer) = 0.2 VA (For R & B phases)

2) MDI = 2.5 VA (For Y phase only)

3) Cabling loop = 0.09 VA

Total burden = 0.29 VA (For R & B phases)

= 2.59 VA (For Y phase)

CT CALC-093-GS-11kV SWGR,107
2.2) Verification of Instrument Security Factor :-

Connected burden VA device = 0.29 VA (For R&B phases)

= 2.59 VA (For Y phase)

Rated burden VACT = 10 VA

Rated Fs (N) = 5

CT CALC-093-GS-11kV SWGR,108
In order to maintain the rated instrument security factor 5,the rated burden shall be
equal to the connected burden. In this case, the connected burden is 0.29VA for R&B
phases and 2.59VA for Y phase. However, the higher VA rating is possible since the
ISF of energy meter is 40xIn for 1 sec. & for MDI 20xFL for 1 sec. Hence the CT
shall be supplied with more rated burden.

VACT < (ALF) x (VADEVICE + VACTR) – VACTR


N
Where,

CT CALC-093-GS-11kV SWGR,109
N = Rated accuracy limit factor (Fs)

= 5

CT CALC-093-GS-11kV SWGR,110
Doc.No.CE093A/GS/D04/0301 - Rev.A

VACT = CT Rated burden

= 10 VA

VADEVICE = 0.29 VA (For R & B phases)

CT CALC-093-GS-11kV SWGR,111
= 2.59 VA (For Y phase)

VACTR = CT Secondary resistance


2.1 Ohms for 400 A tap

Therefore, N x (VACT+VACTR) < ALF x (VADEV+VACTR)

5 x (VACT+2.1) < 40 x (0.29+2.1) -For R & B phases

5 x (VACT+2.1) < 20 x (2.59+2.1) -For Y phase

CT CALC-093-GS-11kV SWGR,112
VACT < 17.02 (For R & B phases – Energy meter)

VACT < 16.66 (For Y phase – MDI)

The CT with 10 VA burden will be supplied which is adequate.

CT Provided by the Manufacturer :-

CT CALC-093-GS-11kV SWGR,113
Current transformer ratio : 400 / 1A

Class of accuracy : CL 0.5 Fs5

Burden : 10 VA

Rated short time thermal current : 120%

CT CALC-093-GS-11kV SWGR,114
CT CALC-093-GS-11kV SWGR,115
Doc.No.CE093A/GS/D04/0301 - Rev.A

CT CALC-093-GS-11kV SWGR,116
3) CT Core T8L & T8L1 :-

Application : High Impedance Busbar Protection


Relay type / Make : MCAG 34, M/s.Alstom, UK
CT Ratio : 3200/1A

For CT requirement calculation refer item no. 4 of IDT feeder CT Calculation

CT Provided by the Manufacturer :-

CT CALC-093-GS-11kV SWGR,117
CT Ratio : 3200 / 1 A

Class of accuracy : CL X

CT Secondary resistance at 75ºC, Rct  10 Ohms

Knee point voltage Vk  200 Volts

Magnetising current, Imag  2 mA at Vk/2

CT CALC-093-GS-11kV SWGR,118
Rated continuous thermal current : 120%

CT CALC-093-GS-11kV SWGR,119
CT CALC-093-GS-11kV SWGR,120
CT CALC-093-GS-11kV SWGR,121
Doc.No.CE093A/GS/D04/0301 - Rev.A

III) OUTGOING FEEDER CIRCUITS (WITHOUT METERING)

1) CT Core T7L :-

Application : 3 O/C & E/F Protection + BCU


Relay/ Make : DCD314B/DCD114A, M/s.VA Tech. Reyrolle, U.K

CT CALC-093-GS-11kV SWGR,122
CT Ratio : 400 / 1A

1.1) Calculation of Burden at Rated Current :-

1) DCD314B = 0.05 VA

2) DCD114A = 0.05 VA

3) BCU = 0.1 VA

CT CALC-093-GS-11kV SWGR,123
4) Cabling loop = 0.09 VA
------------
Total = 0.29 VA
------------
Total burden required = 0.29 VA

1.2) Verification of Accuracy limit factor

CT CALC-093-GS-11kV SWGR,124
The CT VA rating considering rated resistance burden shall be  the total actual burden
considering actual resistance burden
i.e., VACT  (ALF) x (VADEVICE + VACTR) – VACTR
N

Maximum fault current on the 11kV System is 25 kA.

Required ALF = 25,000 = 62.5 For 400A tap


400

CT CALC-093-GS-11kV SWGR,125
N = Rated accuracy limit factor
= 15

VACT = CT Rated burden

= 15VA

VADEVICE = 0.29 VA

VACTR = CT Secondary resistance

CT CALC-093-GS-11kV SWGR,126
3 Ohms for 400 A tap

Doc.No.CE093A/GS/D04/0301 - Rev.A

VACT  62.5 [0.29 + 3] - 3


15

CT CALC-093-GS-11kV SWGR,127
 10.7 For 400A tap

Hence, accuracy limit factor of 15 and burden 15 VA is applicable for the CT ratio,
400/1A.

CT Provided by the Manufacturer :-

Current transformer ratio : 400 / 1A

CT CALC-093-GS-11kV SWGR,128
Burden : 15 VA

Class of accuracy : 5P 15

Rated continuous thermal current : 120 %

CT CALC-093-GS-11kV SWGR,129
CT CALC-093-GS-11kV SWGR,130
CT CALC-093-GS-11kV SWGR,131
Doc.No.CE093A/GS/D04/0301 - Rev.A

CT CALC-093-GS-11kV SWGR,132
2) CT Core T7L1 :-

Application : Metering
Type/Make : MDI 244-16XG, M/s.Crompton
CT Ratio : 400/1A

2.1) Calculation of Burden at Rated Current :-

CT CALC-093-GS-11kV SWGR,133
1) MDI = 2.5 VA (Y phase only)

2) Cabling loop = 0.09 VA


------------
Total = 2.59 VA
------------
Total burden required = 2.59 VA

2.2) Verification of Instrument Security Factor :-

CT CALC-093-GS-11kV SWGR,134
Connected burden VA device = 2.59 VA

Rated burden VACT = 10 VA

Rated Fs (N) = 5

In order to maintain the rated instrument security factor 5,the rated burden shall be
equal to the connected burden. In this case, the connected burden is 2.59VA.
However, the higher VA rating is possible since the ISF of MDI is 20xIn for 1 sec.
Hence the CT shall be supplied with more rated burden.

CT CALC-093-GS-11kV SWGR,135
VACT < (ALF) x (VADEVICE + VACTR) – VACTR
N

Where,

N = Rated accuracy limit factor (Fs)

CT CALC-093-GS-11kV SWGR,136
= 5

VACT = CT Rated burden

= 10 VA

VADEVICE = 2.59 VA

CT CALC-093-GS-11kV SWGR,137
Doc.No.CE093A/GS/D04/0301 - Rev.A

VACTR = CT Secondary resistance


2.1 Ohms for 400 A tap

Therefore, N x (VACT+VACTR) < ALF x (VADEV+VACTR)

CT CALC-093-GS-11kV SWGR,138
5 x (VACT+2.1) < 20 x (2.59+2.1)

5VACT < 83.3

VACT < 83.3 < 16.66 VA


5

Therefore the VA burden is < 16.66 VA. Hence the CT is adequate.

CT CALC-093-GS-11kV SWGR,139
The CT with 10 VA burden will be supplied.

CT Provided by the Manufacturer :-

Current transformer ratio : 400 / 1A

Class of accuracy : CL 0.5 Fs5

Burden : 10 VA

CT CALC-093-GS-11kV SWGR,140
Rated short time thermal current : 120%

Note : -

CT CALC-093-GS-11kV SWGR,141
For R & B phase CTs (Class 0.5 Fs<5), secondary will be shorted at 11kV Swgr. LV
compartment.

CT CALC-093-GS-11kV SWGR,142
Doc.No.CE093A/GS/D04/0301 - Rev.A

3) CT Core T8L & T8L1 :-

CT CALC-093-GS-11kV SWGR,143
Application : High Impedance Busbar Protection
Relay type / Make : MCAG 34, M/s.Alstom, UK
CT Ratio : 3200/1A

For CT requirement calculation refer item no. 4 of IDT feeder CT Calculation

CT Provided by the Manufacturer :-

CT Ratio : 3200 / 1 A

CT CALC-093-GS-11kV SWGR,144
Class of accuracy : CL X

CT Secondary resistance at 75ºC, Rct  10 Ohms

Knee point voltage Vk  200 Volts

Magnetising current, Imag  2 mA at Vk/2

Rated short time thermal current Ith : 25 KA for 3 sec.

CT CALC-093-GS-11kV SWGR,145
Rated continuous thermal current : 120%

CT CALC-093-GS-11kV SWGR,146
CT CALC-093-GS-11kV SWGR,147
Doc.No.CE093A/GS/D04/0301

CT CALC-093-GS-11kV SWGR,148
IV) BUS SECTION CIRCUIT :-

1) CT Core T6L :-

Application : 3 O/C & E/F Protection + BCU


Relay type / Make : DCD314B/DCD114A, M/s.VA Tech Reyrolle.U.K
CT Ratio : 3200 / 1 A

CT CALC-093-GS-11kV SWGR,149
1.1) Calculation of Burden at Rated Current :-

1) DCD314B = 0.05 VA

2) DCD114A = 0.05 VA

3) BCU = 0.1 VA

4) Cabling loop = 0.09 VA


------------

CT CALC-093-GS-11kV SWGR,150
Total = 0.29 VA
------------
Total burden required = 0.29 VA

1.2) Verification of Accuracy limit factor

The CT VA rating considering rated resistance burden shall be  the total actual burden
considering actual resistance burden
i.e., VACT  (ALF) x (VADEVICE + VACTR) – VACTR

CT CALC-093-GS-11kV SWGR,151
N

Maximum fault current on the 11kV System is 25 kA.

Required ALF = 25,000 = 7.8125 For 3200A tap


3200

N = Rated accuracy limit factor


= 15

CT CALC-093-GS-11kV SWGR,152
VACT = CT Rated burden

= 15VA

VADEVICE = 0.29 VA

VACTR = CT Secondary resistance


17 Ohms for 3200 A

CT CALC-093-GS-11kV SWGR,153
Doc.No.CE093A/GS/D04/0301

VACT  7.8125 [ 0.29 + 17 ] - 17


15

 - 7.99

CT CALC-093-GS-11kV SWGR,154
Hence, accuracy limit factor of 15 and burden 15 VA are adequate for the CT ratio
3200 / 1A .

CT Provided by the Manufacturer :-

CT Ratio : 3200 / 1 A

Burden : 15 VA

CT CALC-093-GS-11kV SWGR,155
Class of accuracy : 5P15

Rated continuous thermal current : 120%

CT CALC-093-GS-11kV SWGR,156
CT CALC-093-GS-11kV SWGR,157
CT CALC-093-GS-11kV SWGR,158
Doc.No.CE093A/GS/D04/0301

2) CT Core T4L & T5L :-

CT CALC-093-GS-11kV SWGR,159
Application : High Impedance Busbar Protection
Relay type / Make : MCAG 34, M/s.Alstom, UK
CT Ratio : 3200/1A

For CT requirement calculation refer item no. 4 of IDT feeder CT Calculation

CT Provided by the Manufacturer :-

CT Ratio : 3200 / 1 A

CT CALC-093-GS-11kV SWGR,160
Class of accuracy : CL X

CT Secondary resistance at 75ºC, Rct  10 Ohms

Knee point voltage Vk  200 Volts

Magnetising current, Imag  2 mA at Vk/2

CT CALC-093-GS-11kV SWGR,161
Rated continuous thermal current : 120%

CT CALC-093-GS-11kV SWGR,162
CT CALC-093-GS-11kV SWGR,163
CT CALC-093-GS-11kV SWGR,164
Doc.No.CE093A/GS/D04/0301

V) CAPACITOR BANK FEEDERS :

1) CT Core T7L :-

Application : 3 O/C & E/F Protection + BCU


Relay/ Make : DCD314B/DCD114A, M/s.VA Tech Reyrolle, U.K

CT CALC-093-GS-11kV SWGR,165
CT Ratio : 400/1A

1.1) Calculation of Burden at Rated Current :-

1) DCD314B = 0.05 VA

2) DCD114A = 0.05 VA

3) BCU = 0.1 VA

CT CALC-093-GS-11kV SWGR,166
4) Cabling loop = 0.09 VA
------------
Total = 0.29 VA
------------
Total burden required = 0.29 VA

1.2) Verification of Accuracy limit factor

CT CALC-093-GS-11kV SWGR,167
The CT VA rating considering rated resistance burden shall be  the total actual burden
considering actual resistance burden
i.e., VACT  (ALF) x (VADEVICE + VACTR) – VACTR
N
Maximum fault current on the 11kV System is 25 kA.

Required ALF = 25,000 = 62.5 For 400A tap


400

N = Rated accuracy limit factor

CT CALC-093-GS-11kV SWGR,168
= 15

VACT = CT Rated burden


= 15 VA

VADEVICE = 0.29 VA

VACTR = CT Secondary resistance


3 Ohms for 400 A tap

CT CALC-093-GS-11kV SWGR,169
Doc.No.CE093A/GS/D04/0301

VACT  62.5 [0.29 + 3] - 3


15

CT CALC-093-GS-11kV SWGR,170
 10.7 For 400A tap

Hence, accuracy limit factor of 15 and burden 15 VA are adequate for the CT ratio 400/1A.

CT Provided by the Manufacturer :-

Current transformer ratio : 400/1 A

CT CALC-093-GS-11kV SWGR,171
Burden : 15 VA

Class of accuracy : 5P 15

Rated continuous thermal current : 120%

CT CALC-093-GS-11kV SWGR,172
CT CALC-093-GS-11kV SWGR,173
CT CALC-093-GS-11kV SWGR,174
Doc.No.CE093A/GS/D04/0301

CT CALC-093-GS-11kV SWGR,175
2) CT Core T7L1 :-

Application : Spare
CT Ratio : 400/1A

CT Provided by the Manufacturer :-

Current transformer ratio : 400/1 A

Burden : 10 VA

CT CALC-093-GS-11kV SWGR,176
Class of accuracy : CL 0.5Fs5

Rated short time thermal current : 120%

Note : -

CT CALC-093-GS-11kV SWGR,177
Class 0.5 CT Secondary will be shorted at 11kV Swgr. LV Compartment.

CT CALC-093-GS-11kV SWGR,178
CT CALC-093-GS-11kV SWGR,179
CT CALC-093-GS-11kV SWGR,180
Doc.No.CE093A/GS/D04/0301

3) CT Core T8L & T8L1 :-

Application : High Impedance Busbar Protection


Relay type / Make : MCAG 34, M/s.Alstom, UK
CT Ratio : 3200/1A

CT CALC-093-GS-11kV SWGR,181
For CT requirement calculation refer item no. 4 of IDT feeder CT Calculation.

CT Provided by the Manufacturer :-

CT Ratio : 3200 / 1 A

Class of accuracy : CL X

CT Secondary resistance at 75ºC, Rct  10 Ohms

CT CALC-093-GS-11kV SWGR,182
Knee point voltage Vk  200 Volts

Magnetising current, Imag  2 mA at Vk/2

Rated continuous thermal current : 120%

CT CALC-093-GS-11kV SWGR,183
CT CALC-093-GS-11kV SWGR,184
CT CALC-093-GS-11kV SWGR,185
Doc.No.CE093A/GS/D04/0301 - Rev.A

VI) OUTGOING FEEDER CIRCUITS (WITHOUT METERING)

CT CALC-093-GS-11kV SWGR,186
1) CT Core T7L :-

Application : 3 O/C & E/F Protection + BCU


Relay/ Make : DCD314A/DCD114A, M/s.VA Tech. Reyrolle, U.K
CT Ratio : 400 / 1A

1.1) Calculation of Burden at Rated Current :-

1) DCD314A = 0.15 VA (0.05 x 3)

CT CALC-093-GS-11kV SWGR,187
2) DCD114A = 0.05 VA

3) BCU = 0.1 VA

4) Cabling loop = 0.09 VA


------------
Total = 0.39 VA
------------
Total burden required = 0.39 VA

CT CALC-093-GS-11kV SWGR,188
------------

1.2) Verification of Accuracy limit factor

The CT VA rating considering rated resistance burden shall be  the total actual burden
considering actual resistance burden
i.e., VACT  (ALF) x (VADEVICE + VACTR) – VACTR
N

CT CALC-093-GS-11kV SWGR,189
Maximum fault current on the 11kV System is 25 KA.

Required ALF = 25,000 = 62.5 For 400A tap


400

N = Rated accuracy limit factor


= 15

VACT = CT Rated burden

CT CALC-093-GS-11kV SWGR,190
= 15VA

VADEVICE = 0.39 VA

VACTR = CT Secondary resistance


3 Ohms for 400 A tap

Doc.No.CE093A/GS/D04/0301 - Rev.A

CT CALC-093-GS-11kV SWGR,191
VACT  62.5 [0.39 + 3] - 3
15

 11.125 For 400A tap

Hence, accuracy limit factor of 15 and burden 15 VA is applicable for the CT ratio,
400/1A.

CT CALC-093-GS-11kV SWGR,192
CT Provided by the Manufacturer :-

Current transformer ratio : 400 / 1A

Burden : 15 VA

Class of accuracy : 5P 15

CT CALC-093-GS-11kV SWGR,193
Rated continuous thermal current : 120 %

CT CALC-093-GS-11kV SWGR,194
CT CALC-093-GS-11kV SWGR,195
CT CALC-093-GS-11kV SWGR,196
Doc.No.CE093A/GS/D04/0301 - Rev.A

2) CT Core T7L1 :-

Application : Metering

CT CALC-093-GS-11kV SWGR,197
Type/Make : MDI 244-16XG, M/s.Crompton
CT Ratio : 400/1A

2.1) Calculation of Burden at Rated Current :-

1) MDI = 2.5 VA

2) Cabling loop = 0.09 VA


------------

CT CALC-093-GS-11kV SWGR,198
Total = 2.59 VA
------------
Total burden required = 2.59 VA

2.2) Verification of Instrument Security Factor :-

Connected burden VA device = 2.59 VA

Rated burden VACT = 10 VA

CT CALC-093-GS-11kV SWGR,199
Rated Fs (N) = 5

In order to maintain the rated instrument security factor 5,the rated burden shall be
equal to the connected burden. In this case, the connected burden is 2.59VA.
However, the higher VA rating is possible since the I SF of MDI is 20xIn for 1 sec.
Hence the CT shall be supplied with more rated burden.

VACT < (ALF) x (VADEVICE + VACTR) – VACTR


N

CT CALC-093-GS-11kV SWGR,200
Where,

N = Rated accuracy limit factor (Fs)


= 5

VACT = CT Rated burden

CT CALC-093-GS-11kV SWGR,201
= 10 VA

VADEVICE = 2.59 VA

Doc.No.CE093A/GS/D04/0301 - Rev.A

VACTR = CT Secondary resistance

CT CALC-093-GS-11kV SWGR,202
2.1 Ohms for 400 A tap

Therefore, N x (VACT+VACTR) < ALF x (VADEV+VACTR)

5 x (VACT+2.1) < 20 x (2.59+2.1)

5VACT < 83.3

VACT < 83.3 < 16.66 VA


5

CT CALC-093-GS-11kV SWGR,203
Therefore the VA burden is < 16.66 VA. Hence the CT is adequate.

The CT with 10VA burden will be supplied.

CT Provided by the Manufacturer :-

Current transformer ratio : 400 / 1A

CT CALC-093-GS-11kV SWGR,204
Class of accuracy : CL 0.5 Fs5

Burden : 10 VA

Rated short time thermal current : 120%

CT CALC-093-GS-11kV SWGR,205
CT CALC-093-GS-11kV SWGR,206
CT CALC-093-GS-11kV SWGR,207
Doc.No.CE093A/GS/D04/0301 - Rev.A

3) CT Core T8L & T8L1 :-

Application : High Impedance Busbar Protection


Relay type / Make : MCAG 34, M/s.Alstom, UK
CT Ratio : 3200/1A

CT CALC-093-GS-11kV SWGR,208
For CT requirement calculation refer item no. 4 of IDT feeder CT Calculation

CT Provided by the Manufacturer :-

CT Ratio : 3200 / 1 Amps

Class of accuracy : CLX

CT Secondary resistance at 75ºC, Rct  10 Ohms

CT CALC-093-GS-11kV SWGR,209
Knee point voltage Vk  200 Volts

Magnetising current, Imag at Vk  2 mA at Vk/2

Rated short time thermal current Ith : 25 KA for 3 sec.

Rated continuous thermal current : 120%

CT CALC-093-GS-11kV SWGR,210
CT CALC-093-GS-11kV SWGR,211
CT CALC-093-GS-11kV SWGR,212
Doc.No.CE093A/GS/D04/0301
- Rev.A

II) Outgoing Feeder Circuits : -

1) CT Core T7L :-

Application : 3 O/C & E/F Protection + BCU


Relay/ Make : M/s.Alstom, UK

CT CALC-093-GS-11kV SWGR,213
1.1) Calculation of Burden at Rated Current :-

1) P122 = 0.075 VA (0.025 x 3)

2) P120 = 0.025 VA

3) BCU = 0.01 VA

4) Cabling loop = 0.09 VA

CT CALC-093-GS-11kV SWGR,214
------------
Total = 0.2 VA
------------
Total burden required = 0.2 VA

CT Provided by the Manufacturer :-

Current transformer ratio : 400 / 1A

CT CALC-093-GS-11kV SWGR,215
Burden : 15 VA

Class of accuracy : 5P 15

Rated short time thermal current : 25 KA for 3 secs.

Rated continuous thermal current : 120 %

CT CALC-093-GS-11kV SWGR,216
CT CALC-093-GS-11kV SWGR,217
Doc.No.CE/093/GS/D/10006

1.2) Verification of Accuracy limit factor

Maximum fault current on the 11kV System is 25 KA.

CT CALC-093-GS-11kV SWGR,218
Required ALF = 25,000 = 62.5 For 400A tap
400

VACT = (ALF / N) x (VADEVICE + VACTR) – VACTR

N = Rated accuracy limit factor


= 15

VACT = CT Rated burden

CT CALC-093-GS-11kV SWGR,219
= 15VA

VADEVICE = 0.2 VA

VACTR = CT Secondary resistance


2 Ohms for 400 A tap

VACT  62.5 [0.2 + 2] - 2


15

CT CALC-093-GS-11kV SWGR,220
 7.167 For 400A tap

Hence, accuracy limit factor of 15 and burden 15 VA is applicable for the CT ratio,
400/1A.

CT CALC-093-GS-11kV SWGR,221
CT CALC-093-GS-11kV SWGR,222
Doc.No.CE/093/GS/D/10006

2) CT Core T7L1 :-

CT CALC-093-GS-11kV SWGR,223
Application : Metering
CT Ratio : 400/1A

2.1) Calculation of Burden at Rated Current :-

1) Energy meter (Prometer – 0.4 x 2) = 0.8 VA

2) Cabling loop = 0.09 VA


------------

CT CALC-093-GS-11kV SWGR,224
Total = 0.89 VA
------------
Total burden required = 0.89 VA

CT Provided by the Manufacturer :-

Current transformer ratio : 400 / 1A

Class of accuracy : 0.5

CT CALC-093-GS-11kV SWGR,225
Fs  5

Burden : 15 VA

Rated continuous thermal current : 25 KA For 3 secs.

Rated short time thermal current : 120%

CT CALC-093-GS-11kV SWGR,226
CT CALC-093-GS-11kV SWGR,227
CT CALC-093-GS-11kV SWGR,228
Doc.No.CE/093/GS/D/10006

2.2) Verification of Accuracy limit factor

Maximum fault current on the 11kV System is 25 KA.

Required ALF = 25,000 = 62.5 For 400A tap

CT CALC-093-GS-11kV SWGR,229
400

VACT = (ALF / N) x (VADEVICE + VACTR) – VACTR

N = Rated accuracy limit factor


= 15

VACT = CT Rated burden

= 15VA

CT CALC-093-GS-11kV SWGR,230
VADEVICE = 0.89 VA

VACTR = CT Secondary resistance


2 Ohms for 400 A tap

VACT  62.5 [0.89 + 2] - 2


15

 10.04 For 400A tap

CT CALC-093-GS-11kV SWGR,231
Hence, accuracy limit factor of 15 and burden 15 VA is applicable for the CT ratio,
400/1A.

CT CALC-093-GS-11kV SWGR,232
CT CALC-093-GS-11kV SWGR,233
Doc.No.CE/093/GS/D/10006

3) CT Core T8L & T8L1 :-

CT CALC-093-GS-11kV SWGR,234
Application : High Impedance Busbar Protection
Relay type / Make : MCAG 34, M/s.Alstom, UK
CT Ratio : 3200/1A

For CT requirement calculation refer item no. 4 of IDT feeder CT Calculation

CT Provided by the Manufacturer :-

CT Ratio : 3200 / 1 Amps

CT CALC-093-GS-11kV SWGR,235
Class of accuracy : CLX

CT Secondary resistance at 75ºC, Rct  10 Ohms

Knee point voltage Vk  200 Volts

Magnetising current, Imag at Vk  2 mA at Vk/2

Rated short time thermal current Ith : 25 KA for 3 sec.

CT CALC-093-GS-11kV SWGR,236
Rated continuous thermal current : 120%

CT CALC-093-GS-11kV SWGR,237
CT CALC-093-GS-11kV SWGR,238
Doc.No.CE/093/GS/D/10006

CT CALC-093-GS-11kV SWGR,239
III) Outgoing Cable Feeder Circuits (Without Metering) : -

1) CT Core T7L :-

Application : 3 O/C & E/F Protection


Relay/ Make : M/s.Alstom, UK

1.1) Calculation of Burden at Rated Current :-

1) P122 = 0.075 VA (0.025 x 3)

CT CALC-093-GS-11kV SWGR,240
2) P120 = 0.025 VA

3) Cabling loop = 0.09 VA


------------
Total = 0.19 VA
------------
Total burden required = 0.19 VA

CT CALC-093-GS-11kV SWGR,241
CT Provided by the Manufacturer :-

Current transformer ratio : 400 / 1A

Burden : 15 VA

Class of accuracy : 5P 15

Rated short time thermal current : 25 KA for 3 secs.

CT CALC-093-GS-11kV SWGR,242
Rated continuous thermal current : 120 %

CT CALC-093-GS-11kV SWGR,243
CT CALC-093-GS-11kV SWGR,244
Doc.No.CE/093/GS/D/10006

1.2) Verification of Accuracy limit factor

Maximum fault current on the 11kV System is 25 KA.

Required ALF = 25,000 = 62.5 For 400A tap


400

CT CALC-093-GS-11kV SWGR,245
VACT = (ALF / N) x (VADEVICE + VACTR) – VACTR

N = Rated accuracy limit factor


= 15

VACT = CT Rated burden

= 15VA

CT CALC-093-GS-11kV SWGR,246
VADEVICE = 0.19 VA

VACTR = CT Secondary resistance


2 Ohms for 400 A tap

VACT  62.5 [0.19 + 2] - 2


15

 7.125 For 400A tap

CT CALC-093-GS-11kV SWGR,247
Hence, accuracy limit factor of 15 and burden 15 VA is applicable for the CT ratio,
400/1A.

CT CALC-093-GS-11kV SWGR,248
CT CALC-093-GS-11kV SWGR,249
Doc.No.CE/093/GS/D/10006

2) CT Core T7L1 :-

Application : BCU

CT CALC-093-GS-11kV SWGR,250
CT Ratio : 400/1A

2.1) Calculation of Burden at Rated Current :-

1) BCU = 0.01 VA

2) Cabling loop = 0.09 VA


------------
Total = 0.1 VA
------------

CT CALC-093-GS-11kV SWGR,251
Total burden required = 0.1 VA

CT Provided by the Manufacturer :-

Current transformer ratio : 400 / 1A

Class of accuracy : 0.5

Fs  5

CT CALC-093-GS-11kV SWGR,252
Burden : 15 VA

Rated continuous thermal current : 25 KA For 3 secs.

Rated short time thermal current : 120%

CT CALC-093-GS-11kV SWGR,253
CT CALC-093-GS-11kV SWGR,254
Doc.No.CE/093/GS/D/10006

CT CALC-093-GS-11kV SWGR,255
2.2) Verification of Accuracy limit factor

Maximum fault current on the 11kV System is 25 KA.

Required ALF = 25,000 = 62.5 For 400A tap


400

VACT = (ALF / N) x (VADEVICE + VACTR) – VACTR

CT CALC-093-GS-11kV SWGR,256
N = Rated accuracy limit factor
= 15

VACT = CT Rated burden

= 15VA

VADEVICE = 0.1 VA

CT CALC-093-GS-11kV SWGR,257
VACTR = CT Secondary resistance
2 Ohms for 400 A tap

VACT  62.5 [0.10 + 2] - 2


15

 6.75 For 400A tap

Hence, accuracy limit factor of 15 and burden 15 VA is applicable for the CT ratio,
400/1A.

CT CALC-093-GS-11kV SWGR,258
CT CALC-093-GS-11kV SWGR,259
CT CALC-093-GS-11kV SWGR,260
Doc.No.CE/093/GS/D/10006

3) CT Core T8L & T8L1 :-

Application : High Impedance Busbar Protection


Relay type / Make : MCAG 34, M/s.Alstom, UK
CT Ratio : 3200/1A

CT CALC-093-GS-11kV SWGR,261
For CT requirement calculation refer item no. 4 of IDT feeder CT Calculation

CT Provided by the Manufacturer :-

CT Ratio : 3200 / 1 Amps

Class of accuracy : CLX

CT Secondary resistance at 75ºC, Rct  10 Ohms

CT CALC-093-GS-11kV SWGR,262
Knee point voltage Vk  200 Volts

Magnetising current, Imag at Vk  2 mA at Vk/2

Rated short time thermal current Ith : 25 KA for 3 sec.

Rated continuous thermal current : 120%

CT CALC-093-GS-11kV SWGR,263
CT CALC-093-GS-11kV SWGR,264
CT CALC-093-GS-11kV SWGR,265
Doc.No.CE/093/GS/D/10006

IV) Bus Section Circuit :-

1) CT Core T5L :-

Application : 3 O/C & E/F Protection + BCU

CT CALC-093-GS-11kV SWGR,266
Relay type / Make : M/s.Alstom, UK
CT Ratio : 3200 / 1 Amps.

1.1) Calculation of Burden at Rated Current :-

1) P122 (3 x 0.025) = 0.075 VA

2) P120 = 0.025 VA

3) BCU = 0.01 VA

CT CALC-093-GS-11kV SWGR,267
4) Cabling loop = 0.09 VA
------------
Total = 0.2 VA
------------
Total burden required = 0.2 VA

CT Provided by the Manufacturer :-

CT CALC-093-GS-11kV SWGR,268
CT Ratio : 3200 / 1 Amps

Burden : 15 VA

Class of accuracy : 5P 15

Rated short time thermal current Ith : 25 KA for 3 sec.

Rated continuous thermal current : 120%

CT CALC-093-GS-11kV SWGR,269
CT CALC-093-GS-11kV SWGR,270
Doc.No.CE/093/GS/D/10006

1.2) Verification of Accuracy limit factor

CT CALC-093-GS-11kV SWGR,271
Maximum fault current on the 11kV System is 25 KA.

Required ALF = 25,000 = 7.8125 For 3200A tap


400

VACT = (ALF / N) x (VADEVICE + VACTR) – VACTR

N = Rated accuracy limit factor


= 15

CT CALC-093-GS-11kV SWGR,272
VACT = CT Rated burden

= 15VA

VADEVICE = 0.2 VA

VACTR = CT Secondary resistance


1.4 Ohms for 3200 A

VACT  7.8125 [14 + 0.2] - 14

CT CALC-093-GS-11kV SWGR,273
15

 - 6.6

Hence, accuracy limit factor of 15 and burden 15 VA is applicable for the CT ratio
3200 / 1A .

CT CALC-093-GS-11kV SWGR,274
CT CALC-093-GS-11kV SWGR,275
Doc.No.CE/093/GS/D/10006

CT CALC-093-GS-11kV SWGR,276
2) CT Core T4L & T5L :-

Application : High Impedance Busbar Protection


Relay type / Make : MCAG 34, M/s.Alstom, UK
CT Ratio : 3200/1A

For CT requirement calculation refer item no. 4 of IDT feeder CT Calculation

CT Provided by the Manufacturer :-

CT CALC-093-GS-11kV SWGR,277
CT Ratio : 3200 / 1 Amps

Class of accuracy : CLX

CT Secondary resistance at 75ºC, Rct  10 Ohms

Knee point voltage Vk  200 Volts

Magnetising current, Imag at Vk  2 mA at Vk/2

CT CALC-093-GS-11kV SWGR,278
Rated short time thermal current Ith : 25 KA for 3 sec.

Rated continuous thermal current : 120%

CT CALC-093-GS-11kV SWGR,279
CT CALC-093-GS-11kV SWGR,280
CT CALC-093-GS-11kV SWGR,281
Doc.No.CE/093/GS/D/10006

V) OUTGOING FEEDER CIRCUIT (CAPACITOR BANK PANELS) :

1) CT Core T7L :-

Application : 3 O/C & E/F Protection

CT CALC-093-GS-11kV SWGR,282
Relay/ Make : M/s.Alstom, UK

1.1) Calculation of Burden at Rated Current :-

1) P122 = 0.075 VA (0.025 x 3)

2) P120 = 0.025 VA

3) MCVI 01 = 3.25 VA

CT CALC-093-GS-11kV SWGR,283
4) Cabling loop = 0.09 VA
------------
Total = 3.44 VA
------------
Total burden required = 3.44 VA

CT Provided by the Manufacturer :-

Current transformer ratio : 400/1A

CT CALC-093-GS-11kV SWGR,284
Burden : 25 VA

Class of accuracy : 5P 15

Rated short time thermal current : 25KA for 3 secs.

Rated continuous thermal current : 120%

CT CALC-093-GS-11kV SWGR,285
CT CALC-093-GS-11kV SWGR,286
Doc.No.CE/093/GS/D/10006

1.2) Verification of Accuracy limit factor

CT CALC-093-GS-11kV SWGR,287
Maximum fault current on the 11kV System is 25 KA.

Required ALF = 25,000 = 62.5 For 400A tap


400

VACT = (ALF / N) x (VADEVICE + VACTR) – VACTR

N = Rated accuracy limit factor


= 15

CT CALC-093-GS-11kV SWGR,288
VACT = CT Rated burden

VADEVICE = 3.44 VA

VACTR = CT Secondary resistance


2 Ohms for 400 A tap

VACT  62.5 [3.44 + 2] - 2


15

CT CALC-093-GS-11kV SWGR,289
 20.7 For 400A tap

Hence, accuracy limit factor of 15 and burden 25 VA is applicable for the CT ratio
400/1A.

CT CALC-093-GS-11kV SWGR,290
CT CALC-093-GS-11kV SWGR,291
Doc.No.CE/093/GS/D/10006

CT CALC-093-GS-11kV SWGR,292
2) CT Core T7L1 :-

Application : BCU
CT Ratio : 400/1A

2.1) Calculation of Burden at Rated Current :-

1) BCU = 0.01 VA

2) Cabling loop = 0.09 VA

CT CALC-093-GS-11kV SWGR,293
------------
Total = 0.1 VA
------------
Total burden required = 0.1 VA

CT Provided by the Manufacturer :-

Current transformer ratio : 400/1A

CT CALC-093-GS-11kV SWGR,294
Burden : 25 VA

Class of accuracy : 0.5

Fs  5

Rated continuous thermal current : 25 KA For 3 secs.

Rated short time thermal current : 120%

CT CALC-093-GS-11kV SWGR,295
CT CALC-093-GS-11kV SWGR,296
CT CALC-093-GS-11kV SWGR,297
Doc.No.CE/093/GS/D/10006

2.2) Verification of Accuracy limit factor

Maximum fault current on the 11kV System is 25 KA.

Required ALF = 25,000 = 62.5 For 400A tap

CT CALC-093-GS-11kV SWGR,298
400

VACT = (ALF / N) x (VADEVICE + VACTR) – VACTR

N = Rated accuracy limit factor


= 15

VACT = CT Rated burden

= 25VA

CT CALC-093-GS-11kV SWGR,299
VADEVICE = 0.1 VA

VACTR = CT Secondary resistance


2 Ohms for 400 A tap

VACT  62.5 [0.1 + 2] - 2


15

 6.75 For 400A tap

CT CALC-093-GS-11kV SWGR,300
Hence, accuracy limit factor of 15 and burden 25 VA is applicable for the CT ratio
400/1A.

CT CALC-093-GS-11kV SWGR,301
CT CALC-093-GS-11kV SWGR,302
Doc.No.CE/093/GS/D/10006

3) CT Core T8L & T8L1 :-

Application : High Impedance Busbar Protection

CT CALC-093-GS-11kV SWGR,303
Relay type / Make : MCAG 34, M/s.Alstom, UK
CT Ratio : 3200/1A

For CT requirement calculation refer item no. 4 of IDT feeder CT Calculation

CT Provided by the Manufacturer :-

CT Ratio : 3200 / 1 Amps

Class of accuracy : CLX

CT CALC-093-GS-11kV SWGR,304
CT Secondary resistance at 75ºC, Rct  10 Ohms

Knee point voltage Vk  200 Volts

Magnetising current, Imag at Vk  2 mA at Vk/2

Rated short time thermal current Ith : 25 KA for 3 sec.

CT CALC-093-GS-11kV SWGR,305
Rated continuous thermal current : 120%

CT CALC-093-GS-11kV SWGR,306
CT CALC-093-GS-11kV SWGR,307
========

CT CALC-093-GS-11kV SWGR,308
1.1) Calculation of Knee Point Voltage :-

1.1.1) As per M/s.Siemens catalogue, class 5P CTs are suitable for 7UT512 relays. However, we
are supplying CLX CTs for transformer differential protection.

The knee point voltage, as per relay manual is

UKN > (RNC + Ri) I2N KALF

1.3

CT CALC-093-GS-11kV SWGR,309
Where

RNC = Rated burden resistance, is also expressed as


= RBN

Ri = CT internal resistance
= 14 Ohms.

I2N = CT Nominal secondary current

CT CALC-093-GS-11kV SWGR,310
= 1A

KALF = Accuracy limiting factor

KALF = (RBC + Ri) K*ALF

(RBN + Ri)

Where

CT CALC-093-GS-11kV SWGR,311
RBC = Connected burden

= 2RL + Rrelay (Loop resistance + relay burden resistance)

= (2 x 0.54 + 0.1)

= 1.18

CT CALC-093-GS-11kV SWGR,312
Doc.No.CE/093/GS/D/10006

K*ALF = Effective accuracy limiting factor

= 50 for 7UT512 relay

CT CALC-093-GS-11kV SWGR,313
UKN = (RBN + Ri) I2N x (RBC + Ri) x K*ALF

1.3 (RBN +Ri)

= 12N x (RBC + Ri) x K*ALF

1.3

= 1__ x (1.18 + 14) x 50

CT CALC-093-GS-11kV SWGR,314
1.3

= 584 Volts

1.1.2) Alternative Formula :-

The value of K*ALF will also be calculated as follows :

K*ALF = 4 I scc max. where Isccmax = Maximum fault current for an


IN internal fault

CT CALC-093-GS-11kV SWGR,315
Iscmax = 50,000_____
1.732 x 11 x 0.315

= 8331.4A

IN = 3200A

K*ALF = 4 x 8331.4
3200

CT CALC-093-GS-11kV SWGR,316
= 10.41

Since the value of K*ALF considered in above calculation item 1.1.1 is 50, the knee pt.
voltage calculation as per item 1.1.1 is adequate.

CT CALC-093-GS-11kV SWGR,317
Doc.No.CE/093/GS/D/10006

1.1.3) 1_ < K*ALF UN IN (HV) < 2

CT CALC-093-GS-11kV SWGR,318
2
K*ALF UN IN (LV)

K*ALF (LV) = 10.41 (please refer item 1.1.2)

UN (LV) = 11kV

IN (LV) = 3200 A

UN (HV) = 132 kV

CT CALC-093-GS-11kV SWGR,319
IN (HV) = 300/150A

Iscc (LV) = 50,000____


1.732 x 132 x 0.315

= 694.28A

K*ALF (LV) = 4 x 694.28


300

CT CALC-093-GS-11kV SWGR,320
= 9.26 For 300A tap

= 4 x 694.28 = 18.5 for 150 A tap


150

1_ < 9.26 x 132 x 300 < 2


2
10.41 x 11 x 3200

CT CALC-093-GS-11kV SWGR,321
1_ < 1 < 2 for 300A tap
2

1_ < 18.5 x 132 x 150 < 2


2
10.41 x 11 x 3200

1_ < 1 < 2 For 150 A tap


2

CT CALC-093-GS-11kV SWGR,322
Hence, condition 2 is also satisfied.

CT CALC-093-GS-11kV SWGR,323