Project: Power supply to Plot P18 at Zayed

Military City
Project no.: D108337 Substation: SWH38A1
Location: Plot P18, Zayed Military City

Client ADDC Site Ref. 33/11kV PU - 1 / 11kV Switchgear


Contractor Time Electro Feeder No. K01 Incomer feeder
Testing Company Alphapower Date of Test 05.05.2020
SITE ACCEPTANCE TEST REPORT FOR CIRCUIT BREAKER

CIRCUIT BREAKER TEST

1. NAME PLATE DETAILS:

CB Manufacturer ABB Control Voltage 48 Vdc


Short time withstand
Type / Model VD4/P 12.12.25 25 kA
Current
Duration of Short
Rated Current Ir 1250 A 3s
Circuit
Rated Voltage 12 kV Year of Manufacture 2020
Power Frequency Lightning Impulse
28 kV 75 kV
withstand Voltage (Ud) withstand voltage (Up)
Motor Voltage 48 Vdc Duty Cycle O – 0.3s – CO – 15 – CO

Serial No. 1VC1CA00007716

2.VISUAL CHECKS:
2.1 CB correctly connected as per drawing : Yes □ No □
2.2 CB name plate is matching with drawing : Yes □ No □
2.3 All terminals tightly secured : Yes □ No □
2.4 No Physical damage in Circuit Breaker : Yes □ No □
2.5 Counter Operation checked : Yes □ No □

3.MECHANICAL FUNCTION CHECKS:

3.1 Manual (Push Button) Closing/Opening working properly : Yes □ No □


3.2 Manual spring charge is working properly : Yes □ No □

3.3 CB plugs are connected properly. : Yes □ No □

TESTED BY CONTRACTOR WITNESSED /APPROVED BY


COMPANY ALPHAPOWER TIME ELECTRO ADDC
NAME

SIGNATURE

DATE

SAT Report for CB Page 1 of 3


Project: Power supply to Plot P18 at Zayed
Military City
Project no.: D108337 Substation: SWH38A1
Location: Plot P18, Zayed Military City

Client ADDC Site Ref. 33/11kV PU - 1 / 11kV Switchgear


Contractor Time Electro Feeder No. K01 Incomer feeder
Testing Company Alphapower Date of Test 05.05.2020
SITE ACCEPTANCE TEST REPORT FOR CIRCUIT BREAKER

4.CB INSULATION RESISTANCE TEST:

Applied Voltage: 5000 V DC Ambient Temperature: 29˚C


CLOSE CONDITION VALUES OPEN CONDITION VALUES
R- (Y+B+E) 4.95 TΩ R-R 9.13 TΩ
Y- (R+B+E) 4.19 TΩ Y-Y 9.17 TΩ
B- (R+Y+E) 4.62 TΩ B-B 8.10 TΩ

5.CB OPERATING TIMING TEST:


Operating Voltage: 48V DC

Sl no. TEST PHASE CLOSE(ms) OPEN(ms) CO(ms) OCO(ms)

1 R-PH 48.8 40.4 64.8 362.4


2 Y-PH 48.8 40.2 62.6 361.6
3 B-PH 48.8 40.2 64.2 361.8

Sl.No COIL OPERATING CURRENT (A)


1 Closing Coil 8.298
2 Opening Coil 8.530
Note: Refer attached CB Analyzer (EGIL) Test report.

6. CB CONTACT RESISTANCE MEASUREMENT TEST:

Injected Current: 100 A DC Ambient Temperature: 29˚C


PHASE R-R Y-Y B-B
Measured value(µΩ) 31 31 31

TESTED BY CONTRACTOR WITNESSED /APPROVED BY


COMPANY ALPHAPOWER TIME ELECTRO ADDC
NAME

SIGNATURE

DATE

SAT Report for CB Page 2 of 3


Project: Power supply to Plot P18 at Zayed
Military City
Project no.: D108337 Substation: SWH38A1
Location: Plot P18, Zayed Military City

Client ADDC Site Ref. 33/11kV PU - 1 / 11kV Switchgear


Contractor Time Electro Feeder No. K01 Incomer feeder
Testing Company Alphapower Date of Test 05.05.2020
SITE ACCEPTANCE TEST REPORT FOR CIRCUIT BREAKER

7.REMARKS:

8.EQUIPMENT USED FOR TESTING:

Calibration
Description Make Model Serial No.
Due Date
Digital Multimeter Fluke 87 V 36320038 25.01.2021
Circuit Breaker
Megger EGIL 1202487 17.09.2020
Analyzer
Micro Ohm Meter Megger MOM 200A 1202852 28.05.2020

TESTED BY CONTRACTOR WITNESSED /APPROVED BY


COMPANY ALPHAPOWER TIME ELECTRO ADDC
NAME

SIGNATURE

DATE

SAT Report for CB Page 3 of 3