Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

INSTALLATION INSTRUCTIONS

PHOTOSWITCHR SOLID STATE PLUG IN LOGIC OUTPUTS


IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE. REPLACEMENT PARTS FOR BASES MANUFACTURED AND SOLD BEFORE 1991.

BULLETIN NUMBER TYPE VOLTAGE SUPPLY CURRENT RATING RESPONSE TIME

63--64 DC Voltage 24 VDC 30 mA Depends upon


or Output Adapter Control Used
63--66 12 VDC 15 mA
63--65 Open Collector 24 VDC 250 mA
or Logic Output
63--67 15 VDC 150 mA
12 VDC 125 mA

63- 64 or 63- 66 63- 65 or 63- 67


SPECIFICATIONS SPECIFICATIONS
No Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 VDC Open Collector Rating as Current Sink . . 250mA for Vce = .25
Load Resistance . . . . . . . . . . . . . . . . . . . . Not less than 550 Ohms Ambient Temperature Range . . --20°F to 135°F (--28°C to 57°C)
Ambient Temperature Range . . --20°F to 135°F (--28°C to 57°C) Relative Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95%
Relative Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95% Reverse Voltage Protection . . . . . . . . . . . . . . . . . . . . Shunt Diode

Note: 63--66 and 63--67 Outputs supersede the 63--64 and 63--65 Out- 3. When these Logic Adapters are used with Model 4003 Versions
puts respectively. The new plug-in Outputs are electrically and of Type 42RL Controls, only DC input power should be ap-
physically interchangeable with the old, but with the following plied. The user must also be certain to add a jumper between
minor exceptions. control terminals L2 and 2C. This ties the negative power sup-
1. The plastic cover on the 63--66 and 63--67 have curved domes ply line terminal to the negative of the output circuit. In placing
to match the curved spring retainers supplied on all Control this jumper and in connecting the power supply leads, the cor-
Bases with date code 8000 and higher. rect polarity must be observed to avoid internal damage.

2. For Series 60--1400 and 60--1600 Control Bases manufactured


and installed prior to January 1980, which included the flat-top
spring retainer, order the 63--66 plus a 63--71 flat--top Adapter
for compatible Control Base mounting.
#63--66 OR #63--64 CONTROL TERMINAL CONNECTIONS

CONTROL TERMINALS
TYPES 13, 22 & 23 TYPE 42RL

-- (A) (9) -- 1C 2C

17 VDC MIN. 1NO 2NO


+ (B) (6) +
1NC 2NC

BASE PINS

#63--67 OR #63--65 #63--66 OR #63--64


CONTROL TERMINAL CONNECTIONS TYPICAL INTERFACING

CONTROL TERMINALS CONTROL TERMINALS


TYPES 13, 22 & 23 TYPE 42RL TYPES 13, 22 & 23 TYPE 42RL

(A) -- -- (7) 2C 1C -- (A) (9) -- 1C 2C


17 VDC
2NO 1NO + (B) (6) + 1NO 2NO MIN.
(B) + + (4)
2NC 1NC 1NC 2NC
#63--66 OPTO-ISOLATOR
BASE PINS #63--64 INTERFACE
RESISTOR
CAUTION: CUSTOMER POWER SUPPLY MUST NEVER BE DIRECTLY CONNECTED 1K Ω, 1W for 20 Ma. Min.
ACROSS OPEN COLLECTOR TERMINALS. 560 Ω, 2W for 30 Ma. Min.

#63--67 OR #63--65 #63--67 OR #63--65


TYPICAL LOGIC INTERFACING TYPICAL COUNTER INTERFACING

CONTROL TERMINALS CONTROL TERMINALS


TYPES 13, 22 & 23 TYPE 42RL TYPES 13, 22 & 23 TYPE 42RL
(7) -- 2C 1C (7) --
-- 2C 1C --
LOGIC INPUT UP TO 24 VDC MAX.
2NO 1NO + 2NO 1NO 250 MA MAX. CURRENT
PULL UP
(4)+ 2NC 1NC RESISTOR (4)+ 2NC 1NC +
+5V (UP TO 30
#63--67 VDC MAX.) #63--67
#63--65 #63--65
CUSTOMER LOGIC CUSTOMER ELECTRO
TTL,R TL, DTL,CMOS MECHANICAL COUNTER

Publication PA--9207(A)