ABB - Fuse-Links Type CEF - EN - Hi-Res PDF
ABB - Fuse-Links Type CEF - EN - Hi-Res PDF
M E D I U M V O LTA G E P R O D U C T S
Fuse-links type CEF are designed to protect • Outdoor sealing included in standard version, de-
distribution transformers, cables, overhead lines signed and tested for harsh conditions
and other apparatus against thermal and dynamic • Welded current path
effects of short-circuit currents. • Contacts made from silver coated cooper
• Striker 80N (medium type)
Key features: • Equipped with Temperature Control Unit – addi-
• Designed and type tested acc. to IEC 60282-1, tional protection against thermal stresses in small
VDE 0670-T4 and VDE 0670-T402 enclosures
• Low power losses, generating additional savings • Low switching voltages secure safe operation in
during product life-cycle wide working voltage range, from 10kV to 24kV
• Top level breaking performance with currents up marked as 10/24kV.
to 63kA RMS
2 FUSE-LINKS T YPE CEF
Catalogue number Fuse name Rated voltage Un [kV] Rated current In [A] Length e [mm] Diameter D [mm] EAN 13 Code
1YMB712427M5612 CEF 10/24 50 537 65 5908270806344
1YMB712429M5612 CEF 10/24 63 537 65 5908270806351
1YMB712431M5612 CEF 10/24 80 537 65 5908270806368
1YMB712433M5812 CEF 10/24 100 537 87 5908270806375
1YMB712435M5812 CEF 10/24 125 537 87 5908270806382
3000
2000
1000
2500
1600
1250
400
800
500
200
100
250
630
160
125
315
50
25
75
(kV)
Fuse-link In (A)
3 10 20 25 31.5 40 50 50 63 100 125 160 160 200 2503 3153
5 10 16 20 20 25 31.5 31.5 50 50 63 100 100 125 160 200 2503 3153
6 6.3 10 16 20 20 25 31.5 40 50 50 63 100 100 125 160 200 2503 3153
10 42 10 10 16 16 20 20 25 31.5 31.5 50 50 63 80 100 125 160 200
12 41,2
6.3 10 10 16 16 20 20 25 31.5 40 50 50 63 80 100 125 160 200
15 41,2 6.3 10 10 10 16 16 20 20 25 31.5 40 40 50 63 80 100 125
20 21,2 42 6.3 10 10 10 16 16 20 20 25 31.5 31.5 40 50 63 80 100 125
24 21,2 41,2 6.3 6.3 10 10 10 16 16 20 20 25 25 31.5 40 50 63 80 100
27 6.31 6.31 6.3 6.3 6.3 10 10 10 16 16 20 20 25 31.5 40 50 63
30 6.3 1
6.31 6.31 6.3 6.3 6.3 10 10 10 16 20 20 20 25 31.5 40 50 63
36 6.31 6.31 6.31 6.3 6.3 6.3 10 10 10 16 16 20 20 25 31.5 40 50 63 63
1
– fuse is not able to clear independently transformer’s secondary side terminals short-circuit current; 2 – fuse type CEF-VT; 3 – fuse type CMF
Recommended fuse rating is on the crossing of transformer rating and line voltage. For different line voltage level, please use clos-
est smaller value from the table. The table was calculated according to standards IEC 60787 and IEC 62271-105 with following as-
sumptions:
• Maximum long lasting transformer overload – 120%
• Magnetizing transformer inrush current – 12 x In during 100ms (up to 800 kVA) or 10 x In during 100ms (800 kVA and above)
• Transformer short-circuit voltage according to IEC 60076-5
• No fuse derating due to small enclosures assumed
For different working conditions fuse selection has to be recalculated.
FUSE-LINKS T YPE CEF 5
Maximum
striker travel
30
Ø9
90
80
70
Striker nominal force [N]
60
50
40
30
0 5 10 15 20 25 30
1000
100
10
Pre-arcing time [s]
0.1
0.01
10.00 100.00 1000.00 10000.00
Characteristics show the average melting time as a function of the prospective current and are recorded from cold condition of
fuse-link. The tolerance is ± 10% referred to the current.
FUSE-LINKS T YPE CEF 9
CEF 3/7.2 kV; 6/12kV; 10/17.5 kV; 10/24 kV cut-off current characteristics:
100
A
200
A
160
10 A
125
0 A
10
A
80
6 A
3
Maximum cut-off current Ipeak [kA]
A
50
A
40
5A
31.
25A
20A
16A
Ik
10A
2x
x√
1.8
A
1 6.3
0.1
0.1 1 10 100
Characteristics show the cut-off current corresponding to a prospective short circuit current. Characteristics are valid for fre-
quency 50Hz.
10 FUSE-LINKS T YPE CEF
1000
100
10
Pre-arcing time [s]
0.1
0.01
10.00 100.00 1000.00 10000.00
Characteristics show the average melting time as a function of the prospective current and are recorded from cold condition of
fuse-link. The tolerance is ± 10% referred to the current.
FUSE-LINKS T YPE CEF 11
100
10
63A
A
50
Maximum cut-off current Ipeak [kA]
A
40
5A
31.
25A
20A
16A
10A
A
6.3
Ik
1
2x
x√
1.8
0.1
0.1 1 10 100
Characteristics show the cut-off current corresponding to a prospective short circuit current. Characteristics are valid for fre-
quency 50Hz.
Temperature Control Unit:
The Temperature Control Unit (TCU) is tripping de- Safety is significantly increased when fuse are
vice which is integrated with the striker of high-volt- equipped with a TCU. This is especially true in de-
age (HV) fuses. It is activated when the allowable vices where fuses are located inside closed fuse
temperature in the switchgear is exceeded. When compartments, as is the case in SF6 switchgear.
the temperature is to high the TCU activates the However, in gas insulated switchgear fuse canisters
striker by releasing the switch disconnector, which or in the narrow panels of air switchgear the risk of
in turn opens the electric circuit and avoids further overheating is high because cooling is limited. High
temperature increases. The high temperatures in- temperatures in switchgears cause degradation and
side the switchgear interior may be caused by exter- oxidation of the metal contacts, degradation of
nal conditions or by a high current passing through switchgear equipment or enclosures, and insulator
the fuse link. List of possible reasons of too high ageing. Unfavorable effects, i.e. temperature rise in-
temperatures inside fuse compartment: side the switchgear, leads to internal short-circuit
• reduced heat transfer inside the switchgear, and further temperature increases. In case of reach-
• over-heating of degraded conducting contacts, ing to high temperature, TCU will be activated, re-
• long-term fuse overloads, leasing a striker and opening associated switch,
• improper selection of the fuse rating, thus eliminating the threat.
• local melting of fuse elements caused by trans-
former inrush currents, starting currents of mo-
tors etc.
— —
ABB Contact Center We reserve the right to make technical We reserve all rights in this document and
tel.: +48 22 22 37 777 changes or modify the contents of this in the subject matter and illustrations con-
e-mail: kontakt@pl.abb.com document without prior notice. With re- tained therein. Any reproduction, disclo-
gard to purchase orders, the agreed par- sure to third parties or utilization of its
ABB Sp. z o.o. – branch Office in Przasnysz ticulars shall prevail. ABB AG does not ac- contents – in whole or in parts – is forbidden
ul. Leszno 59, 06-300 Przasnysz cept any responsibility whatsoever for without prior written consent of ABB AG.
tel.: +48 22 22 38 900 potential errors or possible lack of infor- Copyright© 2017 ABB
fax: +48 22 22 38 953 mation in this document. All rights reserved
www.abb.pl