3500/23E Transient Data Interface

Bently Nevada* Asset Condition Monitoring


Description
The 3500/23E Transient Data Interface (TDI) is the interface between the 3500
ENCORE monitoring system and GE’s System 1* condition monitoring and
diagnostic software. The TDI combines the capability of a System Monitor with
the data collection capability of a communication processor.

The TDI operates in the System Monitor slot of a 3500 ENCORE rack in
conjunction with the vibration monitors (3500/42E) to continuously collect steady
state and transient waveform data and pass this data through an Ethernet link
to the host software. Static data capture is standard with the TDI, however using
an optional Channel Enabling Disk will allow the TDI to capture dynamic or
transient data as well. The TDI features improvements in several areas over
previous communication processors and incorporates the Communication
Processor function within the 3500 ENCORE rack.
The TDI module provides extensive communication capabilities of all rack
monitored values and statuses for integration with process control and other
automation systems using serial (RS232/RS422/RS485) communications
capabilities.
Every 3500 ENCORE rack requires one TDI, which always occupies Slot 1 (next to
the power supplies).

C US

Specifications and Ordering Information


Part Number 287826-01
Rev. NC (04/11)

Page 1 of 8
detected within the rack. User
Specifications can select either an “OPEN” or
“CLOSED” contact to annunciate a
Inputs
NOT OK condition. This relay
Power always operates as “Normally
Consumption Energized”.
TBD OK Relay:
Data Specifications in 3300/12 or
Front panel: 3300/14 data sheet

Ethernet: Controls
2 Ports: 10Base-T or 100Base-TX Front Panel
Ethernet, autosensing Rack reset
Rear I/O: button:

Serial Communication Clears latched alarms and Timed


OK Channel Defeat in the rack.
115.2 kbaud maximum RS232 or
RS422 serial communications Performs same function as “Rack
Reset” contact on I/O module.
1200 baud minimum rate
supported. Display Control
switches:**
Ethernet
Used to control all of the displays
10Base-T Ethernet, autosensing of the monitors in the rack.
Home:
Used to return all of the monitor
displays to their primary screen.
Outputs
Front Panel Page Up:
LEDs Moves all displays to their next
Rack OK LED: screen.

Indicates when the 3500 ENCORE Page Down:


System is operating properly Moves all displays to their
TDI OK LED: previous screen.

Indicates when the 3500/23E is **Note: The Display Control


operating properly switches are provided to support
a future enhancement to the
TM LED: 3500/23E.
Indicates when the 3500 ENCORE View Set Points
System is in Trip Multiply mode. Tag Names:
CONFIG OK LED: Used to change the displays to
Indicates that the 3500 ENCORE show the setpoints and tag
System has a valid configuration. names for the channels being
monitored.
I/O Module OK
Relay: Configuration
Keylock:
Relay to indicate when the 3500
ENCORE System is operating Used to place 3500 ENCORE
normally or when a fault has been System in either “RUN” mode or
Specifications and Ordering Information
Part Number 287826-01
Rev. NC (04/11)

Page 2 of 8
“PROGRAM” mode. RUN mode • Supports the four 3500
allows for normal operation of the system Keyphasor signals.
rack and locks out configuration
• Supports multiple events per
changes. PROGAM mode allows
revolution speed inputs up to
for normal operation of the rack
20 kHz.
and also allows for local or
remote rack configuration. The Startup /
key can be removed from the Coastdown
rack in either position, allowing Data
the switch to remain in either the
• Data collected from speed
RUN or PROGRAM position.
and time intervals.
Locking the switch in the RUN
position allows you to restrict • Increasing and decreasing
unauthorized rack speed interval independently
reconfiguration. Locking the programmable.
switch in PROGRAM position
• Initiation of transient data
allows remote reconfiguration of
collection based on detecting
a rack at any time.
the machine speed within
I/O Module one of two programmable
System windows.
Contacts
• The number of transient
Trip Multiply: events that can be collected
is only limited by the
Description:
available memory in the
Used to place 3500 rack in Trip module.
Multiply.
Alarm Data
Maximum Collection
Current:
• Pre- and post-alarm data.
<1 mAdc, Dry Contact to Common
• 1 second of static values
Alarm Inhibit: collected for 10 minutes
before the event and 1
Description:
minute after the event.
Used to inhibit all alarms in the
• 100 ms static values
3500 rack.
collected for 20 seconds
Maximum before the event and 10
Current: seconds after the event.
<1 mAdc, Dry Contact to Common • 2.5 minutes of waveform
data at 10-second intervals
Rack Reset:
before the alarm and 1
Description: minute collected at 10-
second intervals after the
Used to clear latched alarms and
alarm.
Timed OK Channel Defeat.
Maximum
Current: Static Values
Data
<1 mAdc, Dry Contact to Common
• TDI will collect the static
Data Collection values including the values
Keyphasor* measured by the monitors.
Inputs:
Specifications and Ordering Information
Part Number 287826-01
Rev. NC (04/11)

Page 3 of 8
• TDI provides four nX static - 5000 Hz,
values for each point.
- 10 kHz,
Amplitude and phase are
returned for each of the - 20 kHz, and
values.
- 30 kHz.
Waveform
• Asynchronous data is anti-
Sampling
alias filtered.
• Collection of waveforms for
• Channel Pairs for providing
48 channels.
Orbit or synchronous full
• DC-coupled waveforms.
spectrum presentations can
• Simultaneous Synchronous
be split among multiple
and Asynchronous data
monitors. For asynchronous
sampled during all
full spectrums the channels
operational modes
must be within a monitor
• User-configurable
channel pair (30 kHz
Synchronous waveform
frequency span data will not
sampling rates:
be phase correlated between
channel pairs).
- 1024 samples/rev for 2 Communications
revolutions,
Protocols
- 512 samples/rev for 4
BN Host
revolutions,
Protocol:
- 256 samples/rev for 8
Communication with 3500
revolutions,
Configuration Software
- 128 samples/rev for 16
BN TDI Protocol:
revolutions,
Communication with GE’s System
- 64 samples/rev for 32
1* Asset Management and Data
revolutions,
Collection Software.
- 32 samples/rev for 64
Modbus®:
revolutions, and
Based on AEG Modicon PI-MBUS-
- 16 samples/rev for 128
300 Reference Manual. Uses
revolutions.
Remote Terminal Unit (RTU)
• Asynchronous data sampled transmission mode. Modbus is a
to support an 800-line registered trademark of Modicon,
spectrum at the following Inc.
frequency spans:
Front Panel
- 10 Hz,
Communications:
- 20 Hz,
Ethernet, 10Base-T and
- 50 Hz, 100Base-TX. Conforms to
IEEE802.3.
- 100 Hz,
Protocol
- 200 Hz,
Supported:
- 500 Hz,
BN Host Protocol and BN TDI
- 1000 Hz, Protocol using Ethernet TCP/IP.
- 2000 Hz, Connection:

Specifications and Ordering Information


Part Number 287826-01
Rev. NC (04/11)

Page 4 of 8
2 ports: RJ-45 (telephone jack Cable Length:
style) for 10Base-T/100Base-TX
1220 metres (4000 feet)
Ethernet cabling.
maximum
Cable Length:
Connector:
100 metres (328 feet) maximum.
9-pin DSUB
Rear Panel
Environmental Limits
TDI Host Operating
Connector Temperature:
Communications: 0 °C to +65 °C (-22 °F to +149 °F)
Ethernet, 10Base-T For operation above +55°C the
Protocol unit requires a minimum 0f
Supported: 300ft/min of moving air across
the rack.
BN Host Protocol and BN TDI
Protocol using Ethernet TCP/IP. Storage
Temperature:
Connection:
-40 °C to +85 °C (-40 °F to +185 °F)
9 Pin DSub
Humidity:
Cable Length:
95%, non-condensing
100 metres (328 feet) maximum.
Battery Life
SDI Host RS-232
Powered TDI:
Communications:
38 years @ 50°C (122 °F)
RS232
Un-powered
Protocol TDI:
Supported:
12 years @ 50°C (122 °F)
BN Host Protocol, Modbus®.
Baud Rate:
CE Mark Directives
EMD Directive
115.2 kbaud maximum
Certificate of
Cable Length: Conformity
30 metres (100 feet) maximum 287885
Connector: EN61000-6-4
9-pin DSUB Radiated
SDI Host RS-422 & SDI Rack Emissions

Communications: EN 55011, Class A

RS422 & RS485 Conducted


Emissions
Protocol
Supported: EN55011, Class A

Modbus®. EN 61000-6-2

Baud Rate: Electrostatic


Discharge
115.2 kbaud maximum
EN 61000-4-2, Criteria B
Specifications and Ordering Information
Part Number 287826-01
Rev. NC (04/11)

Page 5 of 8
Radiated For further certification and approvals information please visit the
following website:
Susceptibility
www.ge-mcs.com/bently
EN 61000-4-3, Criteria A
Physical
Conducted
TDI Module
Susceptibility
Dimensions
EN 61000-4-6, Criteria A
(Height x Width
Electrical Fast x Depth)
Transient
228mm (8.97 in) x 50mm (1.98 in) x
EN 61000-4-4, Criteria B 289mm (11.39 in)
Surge
Capability
Weight
EN 61000-4-5, Criteria B
1.45kg (3.2 lb)
Magnetic
Rack Space
Field
Requirements
EN 61000-4-8, Criteria A
TDI Module
Power Supply
1 full-height front slot.
Dip
EN 61000-4-11, Criteria B Ordering Information
CE Mark Low Transient Data Interface
Voltage
Directives 3500/23E-AXX-BXX
A: I/O Module Type
Certificate of
Conformity
00 none, uses currently
287885 installed 3300 PIM.
EN 61010-1
B: Agency Approval Option
Safety Requirements 00 None
01 CSA/NRTL/C (Class 1, Div 2)
Hazardous Area Approvals
North American Note: For installation as a retrofit monitor for a 3300
System, Agency Approval Option B01 should be
Approval Option (01)
ordered only if the existing 3300 System has the
Class 1, Div 2 same type of approvals. Installation of a retrofit
monitor in a system without approvals will invalidate
Groups A, B, C, D the approvals of the monitor.
T4A @ Ta = -20°C to +60°C
Spares
(-4 ºF to +140 ºF)
285690-01
T4 @ Ta = -20 °C to +65 ºC
3500/23E TDI
(-4 ºF to +150 ºF) 287545-01
3500/23E Monitor Manual
Note: When installed as a retrofit monitor for a 3300
System, hazardous area approval is valid only if the
existing 3300 System has the same type of approval.

Specifications and Ordering Information


Part Number 287826-01
Rev. NC (04/11)

Page 6 of 8
Ethernet Cables Serial Data Interface Cables
Standard 10 Base-T/100 Base-TX Shielded RS232 Cable, Honeywell PLCG to 3500/23E
Category 5 Cable with RJ-45 connectors (solid
conductor)
89968 - AXXXX-BXX-CXX
138131-AXXX Option Descriptions
A: Cable Length: A: Cable Length
006 6 feet (1.8 m) 0010 10 feet (3 meters)
010 10 feet (3.0 m) 0025 25 feet (7.5 meters)
025 25 feet (7.6 m) 0050 50 feet (15 meters)
040 40 feet (12.2 m) 0100 100 feet (30.5 meters)
050 50 feet (15.2 m)
075 75 feet (22.9 m) B: Assembly Instructions
085 85 feet (25.9 m) 0 1 Not Assembled
100 100 feet (30.5 m) 0 2 Assembled
120 120 feet (36.6 m) C: Protection Option
150 150 feet (45.7 m) 0 1 No Surge Protection
200 200 feet (61.0 m) 0 2 Surge Protection Provided
250 250 feet (76.2 m)
320 320 feet (97.5 m)
RS422 Cable, 3500/23E to 3500/23E
Ethernet 9 Pin Dsub to RJ-45 47125-AXXXX-BXX-CXX-DXX
167887-AXXX-BXX A: Cable Length
A: Cable Length 0 0 1 0 10 feet (3 meters)
003 3 feet (1 metres) 0 0 2 5 25 feet (7.5 meters)
010 6 feet (2 metres) 0 0 5 0 50 feet (15 meters)
010 10 feet (3 metres) 0 1 0 0 100 feet (30 meters)
025 25 feet (7.5 metres) 0 2 0 0 200 feet (61 meters)
050 50 feet (15 metres) 0 2 5 0 250 feet (75 meters)
100 100 feet (30 metres) 0 5 0 0 500 feet (150 meters)
250 250 feet (76 metres) 1 0 0 0 1000 feet (305 meters)
320 320 feet (100 metres) 2 0 0 0 2000 feet (610 meters)*
B: Assembly Option 4 0 0 0 4000 feet (1220 meters)*
01 PVC Insulated – Non *Note: Cannot be ordered
Plenum assembled.
02 PVC Insulated – Plenum
B: Assembly Instructions
0 1 Not Assembled
0 2 Assembled
Ethernet 9 Pin Dsub to RJ-45 Crossover C: Insulation Option
167974-AXXX-BXX 0 1 PVC Insulated
0 2 Teflon® Insulated
A: Cable Length D: Protection Option
003 3 feet (1 metres) 0 1 No Surge Protection
010 6 feet (2 metres) 0 2 Surge Protection Provided
010 10 feet (3 metres)
025 25 feet (7.5 metres)
050 50 feet (15 metres) Surge Protector Kit
100 100 feet (30 metres)
250 250 feet (76 metres)
109959-AXX
(Note: Each communication cable requires one device at each end
320 320 feet (100 metres) of the cable).
B: Assembly Option A: Surge Protector Kit
01 PVC Insulated – Non 0 4 For Cable 47125
Plenum 0 9 For Cable 89968
02 PVC Insulated – Plenum
Specifications and Ordering Information
Part Number 287826-01
Rev. NC (04/11)

Page 7 of 8
Graphs and Figures

A. Reset Switch
B. Buffered Transducer Outputs
C. Ethernet Ports
D. Display Control Switches
E. Status LEDs
F. Keylock (Program / Run)

Figure 1: Front view of the Proximitor*/Seismic Monitor

* Denotes a trademark of Bently Nevada, Inc., a wholly owned subsidiary of General Electric Company.

© 2011 Bently Nevada, Inc. All rights reserved.

Printed in USA. Uncontrolled when transmitted electronically.

1631 Bently Parkway South, Minden, Nevada USA 89423


Phone: 775.782.3611 Fax: 775.215.2873
www.ge-mcs.com/bently

Specifications and Ordering Information


Part Number 287826-01
Rev. NC (04/11)

Page 8 of 8

You might also like