Section Length Flow Pressure Duct size velocity Velocity Fitting Pressure loss Total

m rate drop pressure pressure pressure


m3/s Pa/m loss loss pa
factor
zeta Fitting pa Straight
duct

A 5 2 0.6 500by700 5.17 20 0.04 0.04*20=0.8 0.6*5=3 3.8

B 10 1.8 0.6 500by650 5.9 21 0.09 1.89 0.6*10=6 7.89

C 5 1.6 0.6 50by 600 5.7 19.4 0.04 0.77 0.6*5=3 3.77

D 3 1.4 0.6 500 by 5.5 19.4 0.6 11.64 0.6*3=1.8 13.44


525

Total pressure loss 28.9