Professional Documents
Culture Documents
CB Fundamentals
CB Fundamentals
Circuit Breakers
Circuit breakers are some of the most important components in modern electric power
systems. The circuit breaker has to operate within extremely tight tolerances when a
CIRCUIT BREAKERS 1
disturbance is detected in the network to protect sensitive and costly components such
as transformers
1. Definitions:
a) Circuit Breaker:
The rated voltage is equal to the maximum system voltage for which the equipment is
designed. It indicates the maximum value of the "highest system voltage" of networks
for which the equipment may be used.
The rated normal current of switchgear and control gear is the r.m.s. value of the
current which switchgear and control gear shall be able to carry continuously under
specified conditions of use and behavior.
This is the standardized rms value of the maximum permissible short-circuit current
on a network for the rated duration of short-circuit.
The interval of time for which switchgear and control gear can carry, in the closed
position, a current equal to its rated short-time withstand current.
CIRCUIT BREAKERS 2
The rated short-circuit breaking current is the highest short-circuit current which the
circuit breaker shall be capable of breaking under the conditions of use and behavior
prescribed in this standard.
The rated short-circuit breaking current is characterized by two values:
– the r.m.s. value of its a.c. component;
– the d.c. time constant of the rated short-circuit breaking current which results
in a percentage of d.c. component at contact separation.
g) Making Current:
The making current is the maximum value that a circuit breaker is capable of making and
maintaining on an installation in short-circuit. It must be greater than or equal to the rated
short-time withstand peak current.
O – t – CO – t' – CO
i) Rated supply voltage for closing and opening devices and auxiliary circuits:
CIRCUIT BREAKERS 3
a) rated voltage
b) rated insulation level
c) rated frequency
d) rated normal current
e) rated short-time withstand current
f) rated peak withstand current
g) rated duration of short-circuit
h) rated supply voltage of closing and opening devices and of auxiliary circuits
i) rated supply frequency of closing and opening devices and of auxiliary circuits
j) rated pressures of compressed gas supply and/or of hydraulic supply for operation,
interruption and insulation, as applicable
k) rated short-circuit breaking current
l) transient recovery voltage related to the rated short-circuit breaking current
m) rated short-circuit making current
n) rated operating sequence
CIRCUIT BREAKERS 4
CIRCUIT BREAKERS 5
3. Background Perspective:
SF6
OCB
Vacuum
Air
CIRCUIT BREAKERS 6
Fig: SF6 Circuit Breaker
CIRCUIT BREAKERS 7
Fig: OCB
CIRCUIT BREAKERS 8
Fig:VCB
CIRCUIT BREAKERS 9
Fig: ACB
CIRCUIT BREAKERS 10
5. Important CB Parts:
• Main Contacts
The main contact in a circuit breaker is the current carrying
element between the stationary- and the moving part of the
interrupter, and thus, a big surface with very low resistance
(less than 100 mΩ) is vital for a long service lifetime.
• Arching Contacts
Nozzle
Auxiliary Contacts are often used in control and protection scheme for various
purposes.
CIRCUIT BREAKERS 11
CIRCUIT BREAKERS 12
6. Why Test Circuit Breakers:
Some of the most important of the many reasons for testing circuit breakers are to ensure they:
a) Insulation Resistance
b) Contact resistance of Main Contacts (Static / Dynamic)
c) Opening/Closing time of Main Contacts
d) Open/Close Coils DC Resistance
e) Motor Current & Time while spring is being charged.
g) Moisture/Purity of SF6
CIRCUIT BREAKERS 13
Minimum pick-up measurement (minimum voltage to operate circuit breaker):
The objective of this test is to make sure that the breaker can operate at the lowest voltage level
provided by the station battery when the breaker has to operate during a power outage
Standard test voltage is 85% (and 70%) of nominal voltage for close (and open)
CIRCUIT BREAKERS 14
Fig: Opening Time
CIRCUIT BREAKERS 15
Fig: Closing Time
DC Resistance:
CIRCUIT BREAKERS 16
Fig: CB Close/Open Scheme
Key Points:
Resistor is used in series to make sure maximum voltage is dropped across the resistor.
As a result, CB does not trip and a very low current flows through the trip coil. This small
amount of current indicates whether a Trip Coil is healthy.
A trip coil has always a 52a/52b contacts in series because it blocks energizing the coil
when the breaker is already open. Trip coil is not also rated for continuous current. It
needs to be de-energized as soon as it has done its job to trip the breaker.
CIRCUIT BREAKERS 17
9. Auto-Reclosing:
Transient faults are commonly caused by lightning and temporary contact with foreign objects.
The immediate tripping of one or more circuit breakers clears the fault. Subsequent re
energization of the line is usually successful. This automatic energization is known as Auto-
Reclosing.
1. dead time
2. reclaim time
3. single or multi-shot
CIRCUIT BREAKERS 18
Fig: Duty Cycle
CIRCUIT BREAKERS 19
10. Controlled Switching: (Above 362kV)
There are two methods used to achieve substantial reduction in transmission line
energizing overvoltage’s (i.e., Controlled Switching) are
When a discharged capacitor (capacitive load) which has a low resistance is energized,
strong transient balancing processes such as over-voltages and inrush currents will occur
when it is connected near the maximum voltage. To obtain the lowest potential
difference upon energizing, the closing operation must occur near the voltage zero
crossing
When a reactance coil (inductive load) which creates a high resistance is energized,
large current differences in the energizing instant would require a great current increase
and thus cause high overvoltages. It is therefore best to energize near the current zero
crossing, i.e near the maximum voltage
CIRCUIT BREAKERS 20
Pre-Insertion Resistor (PIR):
CIRCUIT BREAKERS 21
Fig: PIR of CB
CIRCUIT BREAKERS 22
The pre-insertion resistors are only used during closing and consist of resistor
blocks that are connected in parallel with the breaking chamber.
The resistor blocks will close the circuit approximately 8-12 ms before the
arcing contacts.
Pre-insertion resistors are mainly used at higher system voltages (≥362 kV).
Pre-insertion resistors should not be mixed up with opening resistors, which
are used for reducing (damping).
CIRCUIT BREAKERS 23
CIRCUIT BREAKERS 24