Professional Documents
Culture Documents
Bohn Load Calculations: Heatcraft Refrigeration Prod. LLC
Bohn Load Calculations: Heatcraft Refrigeration Prod. LLC
LLC
2175 West Park Place Blvd. Stone Mountain, GA 30087
Phone: 770-465-5600 Fax:: 770-465-5990
Infiltration Data:
Qty Size (m) Entering Air Opening Time Air Curtain Number of
Doors: 1 2 X 1 22.7 ºC DB 0.50 %RH 5 /hr. 6.00 min. .50 % Auxiliary Doors
0 Glass
0 Dock
Product Data:
Type: BLACKBERRIES Packaging: Freeze Point: 30.5ºC
Max. Load: 90 kg SpHt Above Freeze: 0.88
Load Time: 1.0 hrs.
Ent. Temp: 23.0 ºC SpHt Below Freeze: 0.46
Final Temp: 6.0 ºC Pulldown Time: 1.0 hrs. † Lat. Ht. Fusion: 67
Max. Inventory: 0 kg Ht of Respiration: 2.77
Miscellaneous Data:
Occupancy: 0.00 People Motors: 3.00144 Equiv HP
Lighting: 0.00 w/m² Forklift: 0.00 Other: 0.000 kw/day
Calculation Results:
Wall Heat Gains: 277 w 4% Total Load: 7,794 w ‡
Infiltration Load: 2,936 w 38 % Runtime: 24.00 hrs/day
Product Load: 1,718 w 22 %
Misc Loads: 2,862 w 37 %
†) Calculated load is based on pulldown data as provided by user, it is the responsibility of the user to ensure
appropriate product packaging and air flow conditions prevail which will allow pulldown within this time period.
‡) The TOTAL LOAD includes a contingency safety factor of 10% to cover the possibility of unforeseen high load
conditions, excessive ambient temperatures, unexpected increases of business, or product packaging changes.