Design Class Detail Overpressure Protection Project Date Capacity Design Item Design Class Class 1 Class 2 Class 3

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 1

Design Class Detail

Overpressure Protection PROJECT Date

Capacity
Design Design Class
Item
Class 1 Class 2 Class 3
PRV Sizing Sizing of pressure relief valves (PRVs) shall be based Sizing of PRVs shall be
on unit nameplate capacity. Note: Operating units based on 110% of unit
more than 10% above nameplate requires validation nameplate capacity.
of relief system capacity.
TIC is .05% greater than
Class 1 or 2. After
construction TIC is 0.25%
to 0.30% greater than
Class 1 or 2.
Specifying Design When designing equipment for containment (vs. relief), design pressures shall be
Pressure based on the installed impeller. For preliminary estimates, the pump deadhead
pressure will be expected pump suction pressure plus a specified multiplier of the
rated total differential head (TDH). The specified multiplier is intended to estimate
the pump deadhead, provide limited turndown capability, and cover pump
manufacturing tolerances. In the event, the actual deadhead of the pump exceeds
the estimate, Shell will accept up to 16% overpressure.
Pump Deadhead 1.1 1.2 1.3
Multiplier TIC is 0.5% greater than TIC is 1% greater than
Class 1. Class 1.
Operability and Maintainability
Design Design Class
Item
Class 1 Class 2 Class 3
PRV Outlet Block No PRV outlet block PRV outlet block valves: and PRV bypass valves shall
Valves/PRV Bypass valves or PRV bypass conform to 12 GS-1
Valves valves shall be provided.
TIC is 0.1% greater than Class 1.
Option requires equipment shutdown and flare system entries.

DEP 00.00.07.84-Gen. Page 1 of 1