Design Class Detail Paco Project Date: Pump/Fin Fan Control Shall Be Local Only
Design Class Detail Paco Project Date: Pump/Fin Fan Control Shall Be Local Only
Design Class Detail Paco Project Date: Pump/Fin Fan Control Shall Be Local Only
Expandability
Design Design Class
Item
Class 1 Class 2 Class 3
Spare DCS I/O No spare DCS I/O or No spare DCS I/O shall be provided. Space for future
space for expansion expansion shall be provided as defined by project.
shall be provided. TIC is 0.02% greater than Class 1.
Reducer Location Reducers shall be located outside globe valve Reducers shall be located
manifolds. outside globe valve
manifolds except on
applications where future
expansion is known.
TIC is 0.001% greater
than Class 1 per
application.
Capacity Utilization
Design Design Class
Item
Class 1 Class 2 Class 3
Pump Fin/Fan Pump/Fin Fan control Select the appropriate:
Control shall be local only. Pumps/Fin Fans running continuously have local
Start/Stop and no Run indication
Pumps/Fin Fans that require start/stop more than
once a day require remote operation. Provide
remote run indications only when no other input that
would indicate operation is provided.
Pumps that require immediate action to start the
spare require auto-start
Pumps, valves and other equipment that are
manipulated by a batch or sequence control require
remote operation
TIC is 0.1% greater than Class 1.
Redundant Only one transmitter per One year or less pay-out Two year or less pay-out
Control application. required for installation of required for installation of
a redundant transmitter. a redundant transmitter.
Transmitters
UPS/Back-Up No UPS or back-up UPS and back-up power supply shall be provided in
Power power supply shall be accordance with the EGGS.
provided. (Potential Loss TIC is 0.05% greater than Class 1.
of view once every 5
years)