Professional Documents
Culture Documents
A Solid-State Current Limiting Switch For The Application of DC Power Network
A Solid-State Current Limiting Switch For The Application of DC Power Network
Abstract—when designing a large distributed dc power control of the systems, and individual load on the systems.
network, special attention must be placed on the electrical In order to prevent the fault propagation, provide protection
stability, control of the systems, and individual load on the against overload and fault, and isolate the faulty load and
systems. In order to prevent the fault propagation, provide equipment in a dc power network, an overcurrent protection
protection against overload and fault, and isolate the faulty device must be applied to the switch gear for electric power
load and equipment in a dc power network, an overcurrent management and control of the systems [2], [3], [6].
protection device must be applied to the switch gear for the
electric power management and control of the systems [1]. Overcurrent protection devices such as circuit breakers
Overcurrent protection devices such as circuit breakers in the in the primary and secondary distribution systems protect all
primary and secondary distribution systems protect all branch branch circuits on the load side of the discharge bus. A
circuits on the load side of the discharge bus. A circuit breaker circuit breaker is electromechanical devices that may be
is electromechanical devices that may be reset and reused after reset and reused after an overload or low-value short circuit,
an overload or low-value short circuit, but most manufactures but most manufactures recommend replacement if the
recommend replacement if the device ever interrupts a short device ever interrupts a short circuit with a fault current
circuit with a fault current close to its interrupt rating. close to its interrupt rating. Furthermore, circuit breaker has
Furthermore, circuit breaker has the conflicting of time delay the conflicting of time delay characteristics that trip delays
characteristics that trip delays must be long enough to open the
must be long enough to open the circuit when a real fault
circuit when a real fault exists [4]. A solid state type of power
exists [4].
switching circuit has been developed as a new power protection
technique for dc power network instead of electromechanical We are now developing a solid state type of power
circuit breaker. The candidate for these switching devices switching circuit as a new power protection technique for dc
should be Si Power MOSFET, IGBT, and SiC MOSFET. As an power network instead of electromechanical circuit breaker.
example of an electromechanical circuit breaker delay curve The candidate for these switching devices should be Si
application, consider a 50 A circuit breaker and fault that Power MOSFET, IGBT, and SiC MOSFET. As an example
draws 200 A (400% of circuit breaker rating).The opening of a circuit breaker delay curve application, consider a 50 A
mechanism in circuit breaker will not completely open until as
circuit breaker and fault that draws 200 A (400% of circuit
much as 0.2 s has elapsed [1]. While on the other hand, solid-
breaker rating). The opening mechanism in a circuit will not
state current limiting switch will open within 20 μs and this
elapsed time and current rating can be adjusted freely [2]. completely open until as much as 0.2 s has elapsed [4], [5].
From the stand point of the dc network stability, when the While on the other hand, our prototype switching circuit will
transient over current caused by fault and or short circuit will open within 20 µs and we can freely adjust this elapsed time
be observed, a solid-state current limiting switch will act as and current rating [8], [10]. To avoid nuisance tripping, we
over current suppression as a secondary role in the dc power successfully performed current limiting function by extend
network. In this paper, we describe the performance of these the elapsed time using same control circuit [10].
solid state type of power switching circuit in DC power
In this paper, we describe the performance of these solid
network and result of stability analysis using Power
Electronics Circuit Simulator, PSIM.
state type of power switching circuit in DC power network
and result of stability analysis using Power Electronics
Keywords—Powe Semiconductor; dc circuit breaker; current Circuit Simulator, PSIM.
limiting; overcurrent protection; Power MOSFET; IGBT; SiC
MOSFET, Stability, Small signal stability II. A SOLID –STATE CURRENT LIMITING SWITCH
FOR THE APPLICATION OF DC POWERNETWORK
I. INTRODUCTION We are now developing a solid state type of power
The future electricity grid for the electric power switching circuit as a new power protection technique for
distribution network is slowly moving in the direction of dc low voltage dc power network instead of magnetic
transmission for several reasons, including lower electromechanical circuit breaker [8]. The candidate for
distribution losses as compared with ac distribution and these switching devices should be Si Power MOSFET,
more efficient integration of renewables to substantially IGBT, and SiC MOSFET.
increase the mix of clean energy source with the standard The environment of the development of dc grids
grid in the next ten-plus years. Medium-voltage dc grids and protection, new power devices are now improved. In these
in-house dc distribution grids will further improve cost environment, focusing on the application for the low and
savings and reliability with less maintenance [1]. medium voltage dc grid, fast-acting switching function and
When designing a large distributed dc power network, current limiting features are brought up the idea to apply Si
special attention must be placed on the electrical stability, Power MOSFET, IGBT, and SiC MOSFET to the dc circuit
breaker. The very basic evaluation for this fast-acting
switching and current limiting function for the dc circuit
breaker using Power Semiconductor are shown by
experiment in this paper [8], [10].
fault trip off time should be less than 20 µs. 10 Short Circuit
Trip off
5
B. Design for Transient overcurrent protection Load Current
Our prototype of switching device using Si Power 0
capacitor and over current sensing resistance [8], [10]. Time [μsec]
region to saturation region. The gate threshold voltage (Vth) 4 Load Current
Trip off
10 region to saturation region in I-V curve [2], [3], [7], [8], [10].
8 For the trip off evaluation in the previous section, the
6 sequence of the trip off action was completed approximately
Short Circuit
4 Trip off for 12 μs. This timing will be determined by the capacitor
CE shown in Fig. 3. In this block diagram, when the output
2
stage switches to linear mode due to an overcurrent status at
0 Load Current CS, the input of CE voltage is set to drive a 100 μA charging
-2 current into the capacitor CE. This charging current will be
-40 -30 -20 -10 0 10 20 30 40 50 60 terminated if the CS voltage disappears, and the driver turns
Time [μsec]
to the “normal switching mode”. However if the fault
Fig. 4. Zoom of Fault trip off waveform, Power MOSFET, 100 V, 1 A condition remains at CS and CE is charged to above 1.8 V,
load voltage and load current. then ERR trip comparator will be triggered and output is
turned off.
16
This function can be applied to the overcurrent limiting
Power MOSFET 100V, 2A design using this capacitor CE.
14 Gate Voltage
12
Fig. 7 shows 2.0 A circuit breaker output current to the
Current [A] / Volt [V]
12
series. The source network has an input-to-output transfer
10
function of TS, and load network has an input-to-output
8 transfer function of TL. The transfer function is described as
6 Current limiting follows.
4
Short Circuit
Trip off
2
Load Current
𝑉 𝑇 ∙𝑇 1
𝑇 = = =𝑇 ∙𝑇
0 𝑉 𝑉 ⁄𝑉 1 + (𝑍 ⁄𝑍 )
-2
-10 0 10 20 30 =𝑇 ∙𝑇 (1)
Time [msec]
Fig. 7. 10 ms Current limiting and fault trip off waveform, Power With 𝑇 = 𝑍 ⁄𝑍
MOSFET, 100 V, 2 A load voltage and load current.
Where, Tsys is the input-to-output transfer function of the
integrated DC power network.
Considering a feedback control system, closed-loop
16 transfer function is also described by equation (1). The
Power MOSFET 100V, 2A
14 Gate Voltage
characteristics equation of this system is simply
Current Limiting: 20msec
1+𝑇 =0 (2)
Current [A] / Volt [V]
12
Power
MOSFET 0.1µF
Snubber
0.1~0.5µH
Circuit
Small Inductance
56 Ω
RCS
15
Total Current
Current [A]
10
0 1 2 3
Time [ms]
Total Current
20 100
Phase [deg] & Gain [V]
15 Adjacent Load 50
Current [A]
10
Gain
Inductive Load 0
5 Fault Load
-50
0
-100
Phase
-5
-150
0 1 2 3
Time [ms] -200
100 1k Frequency [Hz] 10k 100k
Gain
REFERENCES
100
[1] Ashok Bindra, “Projecting the Evolution of Power Electronics,” IEEE
50
Power Electronics Magazine, vol. 3, No.1, pp. 32-44, March. 2016.
- Diode insertion - [2] Ishikawa, Ide, Yanabu, Komatsu, “Study of the Solid State Current
0 Limiting Switch for a lage scale Space Power Systems”, WSEAS
Transaction on Power Systems, Issue 1, Vol. 1, pp.151-156, 2006.
-50 [3] Masaaki Komatsu, Naotaka Ide, Satoru Yanabu, “A Solid-State
Phase
Current Limiting Switch for Application of Large-scale Space Power
-100 Systems” IEEE Power Electronics Specialist Conference, pp.1471-
100 1k
Frequency [Hz] 10k 100k 1476, 2007.
[4] Whitham D. Reeve, DC Power System Design for
Telecommumication, John Wiley & Sons, Inc., 2007.
Fig. 19. Bode plot with current limiting switch
[5] AIRPAX, IAL/CEL/LEL Series, Magnetic Circuit Protection, Delay
Curves; Retrieved from http://airpax.sensata.com/pdfs/ial.pdf.
Nyquist Plot [6] Atif Maqsood and Keith Corzine, “DC Microgrid Protection,” IEEE
[dB] 90
2.5 Electrification Magazine, vol. 4, No.2, pp. 58-64, June 2016.
120 60
[7] Edwin S. Oxner, “Power FETs and their applications”, Prentice-Hall,
2.0
Inc., 1982.
150 30
1.5 [8] Masaaki Komatsu, “Approach and Basic Evaluation for the DC
Circuit Breaker with Fault Current Limiting Feature”, in Proc. IEEE
1.0
INTELEC2016 Conference, Oct. 23-27, 2016, TS15A.2, pp. 1-5
0.5 180 0 [9] Fei Liu, Wenjun Liu, Xiaoming Zha, Hua Yang, and Kun Feng,
“Solid-State Circuit Breaker Snubber Design for Transient
1.0
Overvoltage Suppression at Bus Fault Interruotion in Low-Voltage
1.5 DC Microgrid,” IEEE Trans. Power Electronics, vol. 32,no. 4, pp.
210 330
3007-3021, April 2017.
2.0 Nyquist Plot [10] Masaaki Komatsu, “Basic Evaluation for the DC Circuit Breaker
2.5
240 300 Using Power Semiconductor with Fault Current Limiting Feature”, in
270 Proc. IEEE INTELEC2017 Conference, Oct. 22-26, 2017, 29.1, pp.
113-120
[11] Benjamin C. Kuo, “Automatic Control System”, Prentice-Hall, 1967
Fig. 20. Nyquist plot with current limiting switch