Pages From SMACNA - HVAC Duct Construction Standards - 284 Pages
Pages From SMACNA - HVAC Duct Construction Standards - 284 Pages
MAXIMUM Pair at 3 m Spacing Pair at 2.4 m Spacing Pair at 1.5 m Spacing Pair at 1.2 m Spacing
HALF OF
DUCT WIRE/ WIRE/ WIRE/ WIRE/
PERIMETER STRAP ROD STRAP ROD STRAP ROD STRAP ROD
P/2 = 760 25.4 x 0.85 3.4 25.4 x 0.85 3.4 25.4 x 0.85 2.7 25.4 x 0.85 2.7
P/2 = 1830 25.4 x 1.31 9.5 25.4 x 1.00 6.4 25.4 x 0.85 6.4 25.4 x 0.85 6.4
P/2 = 2440 25.4 x 1.61 9.5 25.4 x 1.31 9.5 25.4 x 1.00 9.5 25.4 x 0.85 6.4
P/2 = 3050 38.1 x 1.61 12.7 25.4 x 1.61 9.5 25.4 x 1.31 9.5 25.4 x 1.00 6.4
P/2 = 4270 38.1 x 1.61 12.7 38.1 x 1.61 12.7 25.4 x 1.61 9.5 25.4 x 1.31 9.5
P/2 = 4880 Not Given 12.7 38.1 x 1.61 12.7 25.4 x 1.61 9.5 25.4 x 1.61 9.5
NOTE:
1. Dimensions other than hanger spacing are in 5. Allowable loads for P/2 assume that ducts
millimeters. are 1.61 mm maximum, excepts that when
maximum duct dimension (w) is over 1520
2. Table allow for duct weight, 4.89 kg/m2 in- mm then p/2 maximum is 1.25w.
sulation weight and normal reinforcement
and trapeze weigh, but no external loads!
6. For upper attachments see Fig. 4- 2.
3. For custom design of hangers, designers my
consult SMACNA' s Rectangular Industrial 7. For upper attachments see Fig. 4- 2.
Duct Standards, the AISI Cold Formed Steel
Design Manual and the AISC Steel
8. For trapeze size see Table 4-3 and Fig. 4- 5.
Construction Manual .
4. Straps are galvanized steel; other materials 9. 2.7, 3.4, and 4.1 mm wire is steel of black
are uncoated steel. annealed, bright basic, or galvanized type.