Outdoor Vacuum Circuit-Breaker 3AF
Description 4
Circuit-Breaker 3AF
1
General 5
Equipment Selection 9
2
Ordering data 10
Configuration example 10
Selection 11
Technical Data 16
3
Electrical data 17
Dimensions 17
Weights 17
Annex 18
4
Inquiry form 19
3
Description Outdoor Vacuum Circuit-Breaker 3AF
Contents
Contents Page
Description 5
General 5
Construction 6
1 Pole assembly
Mode of operation
Operating mechanism 7
Releases 7
Closing 7
Standards 7
Ambient conditions 8
Dielectric strength 8
4
Outdoor Vacuum Circuit-Breaker 3AF Description
General
5
Description Outdoor Vacuum Circuit-Breaker 3AF
Construction
1
3AF outdoor vacuum circuit-breakers consist of the pole
assembly (1), the operating mechanism box (2) and a
steel structure (3) to accommodate all components. In 3AF
circuit-breakers, the pole assemblies are mounted on a base
frame (4) equipped with a common operating shaft. 4
3
1 Pole assembly
2 Operating
mechanism box
3 Steel structure
4 Base frame
3AF circuit-breaker
7
Pole assembly
The pole assembly consists of the vacuum interrupter (5), 6
porcelain insulators (6) and the terminal connectors (7
and 8). The vacuum interrupter is mounted in a porcelain
insulator. At the upper end it is rigidly fixed to the terminal
connector (7). The lower part allows free axial movement
5
and is connected to the lower terminal connector (8) via
8
flexible connectors (9).
Another porcelain insulator, which separates the terminals 9
from the steel structure and the operating mechanism 5 Vacuum interrupter
box, contains the switching rod (10), which transmits the 6 Porcelain insulator
switching movement from the operating mechanism box to 7 Upper terminal connector
10
the vacuum interrupter. 8 Lower terminal connector
9 Flexible connector
10 Switching rod
6
Outdoor Vacuum Circuit-Breaker 3AF Description
Mode of operation, standards
1
Instead of this “manual mechanical closing”, “manual
rods.
electrical closing” is also available. In this version, the
To close the breaker, the closing spring can be unlatched closing circuit of the circuit-breaker is controlled electrically
either mechanically by means of the local “ON” pushbutton by a pushbutton instead of the mechanical button.
or electrically by remote control. The closing spring charges
If constant CLOSE and OPEN commands are present at
the opening or contact pressure springs as the breaker
the vacuum circuit-breaker at the same time, the vacuum
closes. The now discharged closing spring will be charged
circuit-breaker will return to the open position after closing.
again automatically by the mechanism motor or manually.
It remains in this position until a new CLOSE command
Then the operating sequence OPEN-CLOSE-OPEN is stored in
is given. In this manner, continuous closing and opening
the springs.
(=“pumping”) is prevented.
Releases
Test / Standards
A release is a device which transfers electrical commands
3AF outdoor vacuum circuit-breakers have been fully tested
from an external source, such as a control room, to the
and confirm to latest IEC standards.
latching mechanism of the vacuum circuit-breaker so that it
can be opened or closed. The maximum possible equipment IEC 62271-100 : High voltage switchgear and controlgear –
is one shunt release and two other releases. Part 100 : High voltage alternating current circuit-breakers.
IEC 62271-1 : Common specfication for high voltage
• The closing solenoid unlatches the charged closing spring
switchgear and controlgear.
of the vacuum circuit-breaker, closing it by electrical means.
3AF outdoor vacuum circuit-breakers confirms to endurance
• Shunt releases are used for automatic tripping of vacuum classes E2, M2, C2.
circuit-breakers by suitable protection relays and for
deliberate tripping by electrical means. They are intended Siesmic Capacity
for connection to an external power supply (DC or AC 3AF outdoor vacuum circuit-breakers are designed in
voltage) but, in special cases, may also be connected to a accordance with internationally accepted requirements for
voltage transformer for manual operation. Siesmic type tests. Specific confirmation on request.
• Current-transformer operated releases comprise a
stored-energy mechanism, an unlatching mechanism and
an electromagnetic system. They are used when there is
no external source of auxiliary power (battery). Tripping is
effected by means of a protection relay (e.g. overcurrent-
time protection) acting on the currenttransformer operated
release.
• Undervoltage releases comprise a stored-energy
mechanism, an unlatching mechanism and an
electromagnetic system which is permanently connected to
the secondary or auxiliary voltage while the vacuum circuit-
breaker is closed. If the voltage falls below a predetermined
value, unlatching of the release is enabled and the vacuum
circuit-breaker is opened via the stored-energy mechanism.
The deliberate tripping of the undervoltage release
generally takes place via an NC contact in the tripping circuit
or via an NO contact by short-circuiting the magnet coil.
With this type of tripping, the short-circuit current is limited
by the built-in resistors. Under-voltage releases can also be
connected to voltage transformers. When the operating
voltage drops to impermissibly low levels, the circuit-breaker
is tripped automatically.
7
Description Outdoor Vacuum Circuit-Breaker 3AF
Ambient conditions and dielectric strength
Ambient conditions
The outdoor vacuum circuit-breakers are designed for the
normal operating conditions defined in IEC 62271-100.
Condensation can occasionally occur under the ambient
conditions shown opposite.
Dielectric strength
The dielectric strength of air insulation decreases with
increasing altitude due to low air density. According to IEC
62271-1, the rated lightning impulse withstand voltage
values specified in the chapter “Technical Data” apply to
a site altitude of 1000 m above sea level. For an altitude
above 1000 m, the insulation level must be corrected
according to the opposite diagram.
The characteristic shown applies to the rated short-duration
power-frequency withstand voltage and the rated lightning
impulse withstand voltage.
To select the devices, the following applies:
U ≥ U0 x Ka
U Rated withstand voltage under standard reference atmosphere
U0 Rated lightning impulse withstand voltage requested for the
place of installation
Ka Altitude correction factor according to the opposite diagram
Example
For a requested rated lightning impulse withstand voltage
of 75 kV at an altitude of 2500 m, an insulation level of 90
kV under standard reference atmosphere is required as a
minimum:
90 kV ≥ 75 kV x 1.2
8
Outdoor Vacuum Circuit-Breaker 3AF Equipment Selection
Contents
Contents Page
Equipment Selection 10
Ordering data and configuration example 10
Voltage level 11
9
Equipment Selection Outdoor Vacuum Circuit-Breaker 3AF
Ordering data and configuration example
a: alphabetical n: numerical
2
Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order Codes
Order No.: a/n a a n n n n – n a a n n – n a a n –
Primary part
1st position Superior group
Switching devices
Secondary part
8th to 16th position Secondary equipment
Operating mechanism, releases, operating
voltages and further auxiliary equipment
Order codes
Group of 3 after the Order No.
Format: a n a
Configuration example
In order to simplify the selection of the correct order part, always the last example of the primary part was taken
number for the requested circuit-breaker type, you will over and continued, so that at the end of the equipment
find a configuration example on each page of the chapter selection a completely configured circuit-breaker results as
“Equipment Selection”. For the selection of the secondary an example.
10
Outdoor Vacuum Circuit-Breaker 3AF Equipment Selection
Selection of basic type
stand voltage
(at50 / 60Hz)
See page 12
See page 12
See page 12
See page 13
See page 13
See page 14
See page 14
See page 14
See page 14
Ur Up Ud Isc Ima Ir
kV kV kV kA kA A
36 170 70 25/26.3 refer pg.17 1600 3 A F 0 1 4 1
2000 3 A F 0 1 4 2
2
2500 3 A F 0 1 4 8
Special versions
Up = 200kV Ud = 95 kV Z V 1 3
Configuration example
3AF outdoor vacuum circuit-breaker 3 A F
Rated voltage Ur = 40.5kV; 200kV / 95kV
Rated short-circuit breaking current Isc = 31.5 kA
Rated normal current Ir = 2000 A 0 1 5 2
11
Equipment Selection Outdoor Vacuum Circuit-Breaker 3AF
Selection of secondary equipment
8th position
Closing Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes
Order No.: 3 A – – –
13
13
14
14
14
14
See page
See page
See page
See page
See page
See page
Option
2
Without A
24 V DC B
48 V DC C
60 V DC D
110 V DC E
220 V DC F
100 V DC G
110 V AC 50/60 Hz 1) H
230 V AC 50/60 Hz 1) J
30 V DC Z J 1 A
32 V DC Z J 1 B
120 V DC Z J 1 C
125 V DC Z J 1 D
127 V DC Z J 1 E
240 V DC Z J 1 F
120 V AC 50/60 Hz 1) Z J 1 K
125 V AC 50/60 Hz 1) Z J 1 L
240 V AC 50/60 Hz 1) Z J 1 M
1) The AC frequency 50 or 60 Hz is selected at the 15th and 16th position (see
page 14)
10th position
Release combination
Under voltage
solenoid (Y9)
c.t.-operated
Release (Y1)
release (Y2)
release (Y3)
release (Y4)
release (Y7)
2nd shunt
2nd shunt
1st shunt
Closing
A
C
D
E
N
P
R
Configuration example
3AF outdoor vacuum circuit-breaker 3 A F
(Ur = 40.5 kV, Isc = 31.5 kA, Ir =2000 A), 200kV / 95kV 0 1 5 2 –
Manual electrical closing 4
Operating voltage of the motor operating mechanism 125 V DC Z
Release combination: Closing solenoid, 1st shunt release
2nd shunt release C
12
Outdoor Vacuum Circuit-Breaker 3AF Equipment Selection
Selection of secondary equipment
11th position
Operating voltage of the closing solenoid (Y9) Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes
and 1st shunt release (Y1) Order No.: 3 A – – –
See page 18
See page 18
See page 18
See page 18
See page 19
See page 19
Standard voltages Special voltages
24 V DC 1
48 V DC 2
60 V DC 3
110 V DC 4
220 V DC 5
100 V AC 50/60 Hz 1) 6
110 V AC 50/60 Hz 1) 7
230 V AC 50/60 Hz 1) 8
30 V DC 9 L 1 A
32 V DC
120 V DC
125 V DC
127 V DC
9
9
9
9
L
L
L
L
1
1
1
1
B
C
D
E
2
240 V DC 9 L 1 F
120 V AC 50/60 Hz 1) 9 L 1 K
125 V AC 50/60 Hz 1) 9 L 1 L
240 V AC 50/60 Hz 1) 9 L 1 M
12th position
Operating voltage of the 2nd release
Release as shunt release (Y2) or (Y3), c.t.-operated release (Y4) or
undervoltage release (Y7)
Configuration example
3AF outdoor vacuum circuit-breaker 3 A F
(Ur = 40.5 kV, Isc = 31.5 kA, Ir = 2000 A), 200kV / 95kV 0 1 5 2 – 4 Z C
Operating voltage of the closing solenoid and
1st shunt release 125 V DC 9
Operating voltage of 2nd shunt release 125 V AC 9
13
Equipment Selection Outdoor Vacuum Circuit-Breaker 3AF
Selection of secondary equipment
13th/14th position
Auxiliary switch, circuit-breaker tripping signal Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes
Order No.: 3 A – – –
Circuit-breaker closing
Operations counter
Auxiliary switch
Auxiliary switch
spring charged
12NO+12NC
See page 15
6NO+6NC
2 T
2 W
2 15th/16th position
Frequency of operating voltages
Frequency
50 Hz A 2
60 Hz A 3
Configuration example
3AF outdoor vacuum circuit-breaker 3 A F
(Ur = 40.5 kV, Isc = 31.5 kA, Ir = 2000 A), 200kV / 95kV 0 1 5 2 – 4 C Z C 9 9
With auxiliary switch 6 NO + 6 NC and circuit-breaker tripping signal 2 T
Frequency of operating voltages 50 Hz A 2
14
Outdoor Vacuum Circuit-Breaker 3AF Equipment Selection
Selection of secondary equipment
Additional equipment
Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes
Order No.: 3 A – – –
Available for
Options
3AF1
Insulator creepage distance 1320 mm – Z V 1 1
Rated voltage 40.5 kV – Z V 1 2
Up = 200 kV Ud = 95 kV – Z V 1 3
Circuit-breaker application upto – 60 °C ambient air – Z V 6 1
temperature
Electrical Indications (ON/OFF/Spring charge) – Z V 6 3
With terminal connectors – Z V 6 4
Configuration example
3AF outdoor vacuum circuit-breaker 3 A F
Rated voltage Ur = 40.5 kV – Z V 1 2
Rated short-circuit breaking current Isc = 31.5 kA
Rated normal current Ir = 2000 A 0 1 5 2 –
Up = 200kV Ud = 95kV – Z V 1 3
Manual electrical closing 4
Operating voltage of the motor operating mechanism 125 V DC Z J I D
Release combination: Closing solenoid, 1st shunt release, 2nd shunt release C
Operating voltage of the closing solenoid and 1st shunt release 125 V DC 9 L Y D
Operating voltage of 2nd shunt release 125 V AC 9 – M I L
With auxiliary switch 6 NO + 6 NC 2 T
Frequency of operating voltages 50 Hz A 2
15
Technical Data Outdoor Vacuum Circuit-Breaker 3AF
Contents
Contents Page
Technical Data 17
Electrical data, dimensions and weights
Voltage level 17
Operating cycles 17
Dimension drawings 17
Operating times 17
16
Outdoor Vacuum Circuit-Breaker 3AF Technical Data
Electrical data, dimensions and weights
Type 3AF01
Rated voltage, frequency 36kV/40.5kV, 50Hz /60Hz
Rated current 1600/2000/2500A
3
Approx. total weight 570kg
1) 95kV available on request 2) 200kVp available on request 3) -60°C available on request
Item Description
Front view Side view
A Top Insulator
B Vacuum interrupter
C Bottom Insulator
D Base frame
E Top terminal
F Bottom terminal
Front
G Mechanism Housing
H Structure
J PlexiGlass on door for -
- Mechanical ON-OFF indicator
- Mechanical spring charged indicator
- Mechanical operation counter
K Control Cable Gland Plate
L Earthing terminal
M Facility for Padlock
Top/Bottom terminal
Foundation Plan Foundation detail pad aluminium (E,F)
Note: Extended structure for mounting instrument transformers can be provided as an option.
17
Annex Outdoor Vacuum Circuit-Breaker 3AF
Contents
Contents Page
Annex 19
Inquiry form 19
18
Outdoor Vacuum Circuit-Breaker 3AF Annex
Inquiry form
Inquiry concerning
Technical data Other values
Current-transformer 0.5 A 1A
Street operated release
Phone
Fax
E-mail
4
Dept.
Name
Street
Postal code/city
Fax
_ _ _ Please fill in
19
Notes