Layouts For Oil and Gas Installations: Oisd - STD - 118
Layouts For Oil and Gas Installations: Oisd - STD - 118
Layouts For Oil and Gas Installations: Oisd - STD - 118
in, ongc
Sr. Number : OISD/DOC/2018/01
OISD – STD – 118 Page No. 23
LAYOUTS FOR OIL AND GAS INSTALLATIONS
TABLE– 7
SEPARATION DISTANCES BETWEEN LPG STORAGE VESSELS AND BOUNDARY WALL / GROUP OF BUILDINGS NOT
ASSOCIATED WITH LPG FACILITIES
Capacity of Each vessel in Cum of water 10 - 20 21 - 40 41 - 350 351 - 450 451-750 751 - 3800
Distance in meters 15 20 30 40 60 90
SD
General Notes to Table-6 & Table-7;
c) “x “indicates suitable distance as per good engineering practices to meet construction, operational and maintenance requirements
OI
d) T7 indicates Table –7;
Note–1: The distance shall be 2 meters or 1/4 of the sum of the diameters of the adjacent vessels or half the diameter of the larger of the
two adjacent vessels in the same group whichever is greater.