The European IP-Code

To help the design engineer identify the degree of protection provided by an enclosure, EN 60.529 (10/91 / IEC 529 (11/89) (International
Electrotechnical Commission) was introduced.
Both harmonised standards classify the extent to which an enclosure will resist the ingress of solid bodies and water under designated tests.
After successful testing the enclosure will be allocated a classification code with the letters IP (International Protection) prefixing that code.

IP 55 W
Code letters
International Protection

First Characteristic numeral


(dust protection, numerals 0-6, or letter X)

Second Characteristic numeral


(water protection, numerals 0-8, or letter X)

Optional letter for application in specified weather conditions (normally agreed


between user and manufacturer, example: Rain hood)

1st numeral: 2nd numeral:


Degree of protection Degree of protection with respect to harmful ingress of water.
with respect to
persons and solid 0 1 2 3 4 5 6 7 8
objects.
Non pro- Protected Protected Protected Protected Protected Protected Protected Protected
tected against drip- against drip- against drip- against against against against against
ping water ping water of ping water of splashing water jets heavy seas immersion sub-mersion
+/- 15° angle +/- 60° angle water
Test time Test time Test time 10mins. Test time Test time 1min/m2 Test time 1min/m2 Test time Test time
10mins. 10mins. max 200 10mins. minimum 3 mins. minimum 3 mins. 30mins. 30mins.
min. 3mm 3m min. 3mm 3m
min. 0.15m
300

300

min. 1m

.5
ø 6.3 ø 12
200

200

30
°

15°

15°
Non protect. 0 IP 00 IP 01 IP 02 10l/min 10l/min 12.5l/min 100l/min
80kN:m2 80kN:m2 30kN:m2 100kN:m2

Protected against IP 10 IP 11 IP 12 IP 13
solid objects greater
than Dia. 50 mm. 1

Protected against
solid objects greater
than Dia. 12 mm. 2 IP 20 IP 21 IP 22 IP 23

Protected against
solid objects greater
than Dia. 2.5 mm. 3 IP 30 IP 31 IP 32 IP 33 IP 34

Protected against
solid objects greater
than Dia. 1.0 mm. 4 IP 40 IP 41 IP 42 IP 43 IP 44 IP 45 IP46

Dust protected. 5 IP 54 IP 55 IP 56

Dust-tight 6 IP 65 IP 66 IP 67 IP 68

128 General Accessories


General Accessories
Thermal Management
www.eldon.com

Page 130

Swing Frames

Page 135

Lighting

Page 137

Mounting Materials

Page
130 Thermal Management
135 Swing Frames
137 Lighting
140 Mounting materials

Page 140

General Accessories 129


Thermal Management

EF, Filter fans EFP, Filter fans, outdoor version


IP 43/54 IP 55

Eldon filter fans and exhaust filters are installed with a time-saving click- Eldon filter fans and exhaust filters are installed with a time-saving click-
in system. Installation requires one cut-out and no screws.All models in system. Installation requires one cut-out and no screws.
are UL approved. 230V, 50/60Hz For outdoor use. UL approved 230V, 50/60Hz

Cut out Air flow Cut out


IP dim. m3/h Filter Power/W Cat.no. dim. m3/h Filter Power/W Cat.no.
43 92 x 92 24 15 12 EF 10 125 x 125 28 20 19 EFP 20
54125 x 125 58 43 19 EF 20 87 55 18 EFP 25
223 x 223 155 108 18 EF 25 223 x 223 134 114 48 EFP 30
255 231 48 EF 30 291 x 291 319 255 63 EFP 50
291 x 291 478 368 63 EF 50 334 264 122 EFP 60
606 437 122 EF 60

EFA, Exhaust filter EFAP, Exhaust filters, outdoor version


IP 43/54 IP 55

For door mounting in accordance with VDE 0113 (EN 60204). UL For door mounting in accordance with VDE 0113 (EN 60204). UL
approved. approved.

Cut out Cut out


IP dim. Cat.no. dim. Cat.no.
43 92 x 92 EFA 10 125 x 125 EFAP 20
54 125 x 125 EFA 20 223 x 223 EFAP 30
223 x 223 EFA 30 291 x 291 EFAP 60
291 x 291 EFA 60

130 General Accessories


Thermal Management

ECR, Fan heater with thermostat DTD, Cooling units, top/roof mounting
IP 20 IP 54

Description: Ozone-friendly refrigerant R 134a


Cooling unit for top-mounting: cools at source of heat
Effectively prevents condensation in enclosures. Sturdy cooling unit for industrial use means: long service life
To be fixed by screws. Seal with protected edge means no extra work on the cutout
Operating voltage: AC 220-230V, 50-60Hz. Every unit is fitted with a fault contact
Heating performance: 350/550W Every unit is fitted with lifting lugs to facilitate installation
Thermostat adjustable 0-60°C 6 x M6 threaded holes in the base plate ensure tight connection bet-
Casing: Plastic (UL 94 V0) ween cabinet and cooling unit
Durability: 50.000 h at 25° ambient temp. Protection: IP 54 against the switch cabinet
Working voltage: 230 V, 50-60 Hz. IP 34 against the ambience (DIN 40050)
Material: Aluminium. Finish: Black. Frequency: 50 Hz
Approvals: VDE, UL File E150057 230V 50/60Hz, 115V 60Hz, 400/440V 50/60Hz, UL approved.

H W D Weight Cat.no. H W D Capacity Volt Cat.no.


120 160 98 1.55 ECR 550 400 600 390 810 W 230 DTD 5101
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ 600 390 1150 W 230 DTD 5201
390 1600 W 230 DTD 5301
Standard filter mat, EFM 465 720 465 3000 W 400/440 DTD 5501
For further specific information, please contact your Eldon dealer.

PWD, Air/Water heat exchanger


IP 54

Temperature resistance: 100 °C. Filter material: EU 3 according to DIN


24185.
IP 43/44
Pack quantity: 5 pieces.
For Cat.no.
EF/EFA 10 EFM 10
EF/EFA 20 EFM 20
EF/EFA 25/30 EFM 25/30
EF/EFA 50/60 EFM 50/60

For horizontal mounting. Water circuit tested for 30 bar pressure.


Sealed with protective edging. No extra work on the installation cutout
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
necessary.
Replacement filter mat, EFMP Temperature regulated by integrated thermostat and solenoid valve.
10 bar max. operating pressure.
For filter fan EFP. IP 55 Tubes and heat exchangers are available in stainless steel (1.4571).
Temperature resistance: 100 °C. Filter material: EU 3 according to DIN Frequency: 50/60 Hz
24185.
Pack quantity: 5 pieces. Roof mounting
H W D Capacity Volt Cat.no.
For Cat.no.
190 720 465 2100 W-3200 W max.230 PWD 5402
EFP 20 EFMP 20 For further specific information, please contact your Eldon dealer.
EFP 25/30 EFMP 25/30
EFP 50/60 EFMP 50/60

General Accessories 131


Thermal Management

DTS, Cooling units, side- and door mounting EGK, Anti condensation heater, small
IP 54

Description: Ozone-friendly refrigerant R 134a


Cooling unit for lateral installation
Seal with protected edge means no extra work on the cutout
Every unit is fitted with a fault contact
Suspension device for easy installation ClIP for 35 mm DIN rail (EN 50022). Vibration proof fixing is fitted as
4/6 x M6 threaded holes for mounting on side panel or door standard.
Protection: IP 54 against the switch cabinet Operating voltage: AC/DC 110-250V max 265V
IP 34 against the ambience (DIN 40050) Approvals: VDE, UL File 150057.
Frequency: 115V 60Hz, 230V 50/60Hz, 400V 50Hz, 440V 60Hz Protection class II.
Supplied with 300 mm silicone cable. Wide 50mm Depth 25mm.

H W D Capacity Volt Cat.no.


1350 390 140 1100 W 230 DTS 7201 Capacity L (mm.) Weight Cat.no.
200 1100 W 230 DTS 7241 10 W 50 0.10 EGK 010
200 1400 W 230 DTS 7341 20 W 60 0.11 EGK 020
140 1400 W 230 DTS 7301 30 W 70 0.12 EGK 030
400 270 1800 W 400/440 DTS 7441 10 W 50 0.10 EGK 010UL
330 375 190 220 W 115/230 DTS 7041 20 W 60 0.12 EGK 020UL
1350 400 270 2500 W 400/440 DTS 7541 30 W 70 0.15 EGK 030UL
445 315 225 350 W 115/230 DTS 7061
580 320 210 470 W 230 DTS 7001
920 390 200 820 W 230 DTS 7101
For further specific information, please contact your Eldon dealer.

PWS, Air/Water cooling unit


IP 55

For vertical installation. Sealed with protective edging. No extra work on


the installation cutout necessary.
Water circuit tested for 30 bar pressure.
Temperature regulated by integrated thermostat.
10 bar operating pressure.
Frequency: 50/60Hz

Side mounting
Side mounting
H W D Capacity Volt Material Cat.no.
587 390 114 2400 W 230 Mild steel PWS 7002
1350 390 140 3200 W 230 Mild steel PWS 7302
140 3200 W 230 Stainless steel PWS 7302S
For further specific information, please contact your Eldon dealer.

132 General Accessories


Thermal Management

EGL, Fan Heater EHG, Anti-condensation heaters, large


IP 20 IP 44

Effectively preventing condensation in enclosures. ClIP for 35 mm DIN rail (EN 50022). Vibration proof fixing is fitted as
Snap-mounting for 35 mm DIN rail. standard.
Capacity: 35m3/h. Operating voltage: AC/DC 110-250V max 265V
Durability: 50.000 hours at 25° C(77° F). Surface temperature: 75°C Approvals: VDE, UL File 150057.
(400W). Protection class II.
Working voltage: 230 V, 50-60 Hz. Width 70 mm Depth 50 mm.
Material: Aluminium. Finish: Black.
Approvals: VDE, UL File E150057
Watt Volt Cat.no. Capacity L (mm.) Weight Cat.no.
250 220-230 EGL 250 15 W 65 0.3 EHG 015
115 EGL 250UL 115 30 W 65 0.3 EHG 030
230 EGL 250UL 230 45 W 65 0.3 EHG 045
400 220-230 EGL 400 160 W 140 0.5 EHG 060
115 EGL 400UL 115 75 W 140 0.5 EHG 075
230 EGL 400UL 230 100 W 140 0.5 EHG 100
Other voltages available on request. 15 W 220 0.8 EHG 150

EHV, Fan Heater ETR200, Thermostat


IP 20 IP 20

High-performance space saving heater with fan prevents formation of ClIP for 35 mm DIN rail (EN 50022).
condensation and provides an evenly distributed interior air temperatu- Normally opened 5A
re in enclosures.Working Voltage: 230V 50/60Hz (AC120V and DC 48V Normally closed: 10A
on request) 10°C - 60°C
Durability: 50.000 hours at 25° C(77° F). 4 x 2.5 mm2
Airflow min.: 35m3/h, free flow (100W, 150W) 250 V
Airflow min.: 108m3/h, free flow (200W, 300W, 400W) Type of contact: Chane-over with quick-acting contact.
Connection heater: 3-pole screw connector 2.5 mm2 Hysteresis: 0.5 K
Connection axial fan: 2-pole screw connection 2.5 mm2 (L2/N2)
Fitting position: ClIP for 35 mm DIN rail EN 50022
Approvals: UL File E187294
Electronic
Weight H W D Cat.no.
with MP 67 50 37 ETR 200
Capacity Dim. (Kg) Cat.no.
100 W 80 x 112 x 22 mm 0.4kg EHV 100
150 W 80 x 112 x 22 mm 0.4kg EHV 150
200 W 119 x 151 x 22 mm 0.5kg EHV 200
300 W 119 x 151 x 22 mm 0.5kg EHV 300
400 W 119 x 151 x 22 mm 0.5kg EHV 400
*) Capacity at 20ºC (68ºF) ambient temperature

General Accessories 133


Thermal Management

ETR, Thermostat ETF, Hygrostat/Thermostat


IP 30

Description: ClIP for 35 mm DIN rail (EN 50022).


Temperature range: 0°C-60°C.
ClIP mounting on 35 mm DIN 46277 and EN 50022 rail. Humidity range: 50-90%.
Radio shielding N according to VDE 0875. Frequenzy: 50/60Hz
Approvals: VDE, UL. Switch capacity: AC 240 V: 8A resistive
Adjustement range: 0°C - 60°C AC 120 V: 8A resistive
Connections: 2 x 2.5 mmV>2 DC 240 V: 0.1A resistive
Swithching capacity: 6A, 250 V/AC DC 48V: 8A resistive
Type of contact: quick-acting contact. Hysteresis: 2K
Hysteresis: 7 K Casing: Plastic UL 94 V0

Description Cat.no. Electronical


Opened 6A ETR 201 H W D Cat.no.
Closed 6A ETR 202 67 50 49 ETF 3000

ETR203, Dual Thermostat ETF2000, Hygrostat


IP 20 IP 20 (DIN 40050)

Description: ClIP for 35 mm DIN rail (EN 50022).


Ambient temperature: 0°C-60°C.
Adjustment range: 35-95%.
Approvals: UL pending Freaquenzy: 50/60Hz
Description: One casing - two thermostats. Switch capacity: 230V AC 5A resistive load
Thermostat (normally closed) for regulating heaters. 230V AC 0.2 Incudtive load at cos = 0.6
Thermostat (normally open) for regulating fileter fans and heat exchan- up to DC 50V 1A, up to DC 75V 0.5A
gers. Maximum load
ClIP for 35 mm DIN rail (EN 50022). 5A 250V
Normally opened 5A 0,2A AC 250V
Normally closed: 10A 1A-DC 50V, 0.5A-DC 75V
10°C - 60°C Minimum load:
100mA, DC/AC 20V

H W D Cat.no. Mecanical
67 50 46 ETR 203 H W D Cat.no.
67 50 38 ETF 2000

134 General Accessories


Swing Frames

MDC MDM

b
h

Swing frame centered


Swing frame

For 600/800/1000 mm wide enclosures For 600 mm wide enclosures


For Max. For 800/1000 mm wide enclosures
enclosure H U loading Cat.no. For Max.
MAS 600 3 40 MDC 036 enclosure H U loading Cat.no.
6 50 MDC 066 MAS 600 3 40 MDM 038
10 60 MDC 106 6 50 MDM 068
12 60 MDC 126 10 60 MDM 108
800 14 60 MDC 146 12 60 MDM 128
1000 19 120 MDC 196 800 14 60 MDM 148
1200 23 145 MDC 236 1000 19 120 MDM 198
MKS/MCI 1600 31 170 MDC 316 1200 23 145 MDM 238
MCS/MKS 1800 35 195 MDC 356 MKS/MCI 1600 31 170 MDM 318
MCI 2000 40 195 MDC 406 MCS/MKS 1800 35 195 MDM 358
MCS/MCI 2200 44 195 MDC 446 MCI 2000 40 195 MDM 408
All swing frames require the transversal mounting kit kit SFT(A) (see swingframe MCSMCS/MCI 2200 44 195 MDM 448
accessories) All swing frames require the transversal mounting kit SFT(A) (see swingframe
accessories)

■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

180° Hinges, MH Chassis support, MSLT

Pack quantity: 1 kit. To relieve pressure on heavy chassis applications.


Only usable in 800 mm width and above. Material: 1.5 mm zinc plated steel.
Pack quantity: 1 pair.
U Cat.no. Cat.no.
3-14 MH 14 MSLT 100
19-44 MH 44

General Accessories 135


Swing Frames

MDS Swing frame stop, MSTD

Locking in any position up to maximum opening.

Cat.no.
MSTD 200

■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

Transversal mounting kit, MDTE

Swinf frame, side mounted For EDR racks

W Cat.no.
800 MDTE 800

For 800/1000 mm wide enclosures


For Max.
enclosure H U loading Cat.no. ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
MAS 600 3 40 MDS 038
6 50 MDS 068 Transversal mounting kit, SFT
10 60 MDS 108
12 60 MDS 128
800 14 60 MDS 148
1000 19 120 MDS 198
1200 23 145 MDS 238
MKS/MCI 1600 31 170 MDS 318
MCS/MKS 1800 35 195 MDS 358
MCI 2000 40 195 MDS 408
MCS/MCI 2200 44 195 MDS 448
All swing frames require the transversal mounting kit (see swingframe accesso-
ries)

For floor standing Multi-Flex enclosures.


Material: 3 mm zinc plated steel.
Pack quantity: 1 piece with mounting material

W Cat.no.
600 SFT 600
800 SFT 800
1000 SFT 1000

136 General Accessories


Lighting

Transversal mounting kit, SFTA Side mounting brackets, MDL

Allow the mounting of a swing frame in the full height of a double door
floor standing enclosure without the use of MTD accessory. Material:
3 mm steel plate.
Painted in RAL 7032.

Cat.no.
MDL 01

For wall mounting Multi-Mount enclosures.


W Cat.no.
600 SFTA 600
800 SFTA 800
1000 SFTA 1000

LTC, Enclosure light LTCF, Enclosure light


IP 20

Description: Magnetic fixing or by using a DIN profile. Provided with


protection cap, electronic quick start, switch and 3 m cable. An inte-
Silicone free. Provided with DIN fixing screws (no magnetic fixing).
grated socket permits operation of additional electric appliances.
Otherwise identical to the LTC lamp.
Operating voltage: 230V/50 Hz.
Power: 11 W (±75W bulb), lamp included.
Socket: AC Max 230V Description Cat.no.
16A Schuko, earthed. Schuko LTCF 75
Connection: Terminal 3 x 2.5 mm2 with cable clamp.
Housing: Plastic, impact resistant, UL94VO.
Cap: transparent plastic
Weight 1 kg.
Approvals: Radio interference suppression level:
VDE 0712, IEC 82.
VDE, EMC.
H x W x D = 60 x 63 x 342 mm

Description Cat.no. ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
Schuko N LTC 75
France LTC 75FR Enclosure lamp, LTCL
Switzerland LTC 75CH
England LTC 75UK
USA/Canada LTC 75USA Spare lamp for LTC. 11 Watt economy lamp,
LTC 75USA is UL approved providing light equivalent to a 75 Watt bulb.

Cat.no.
LTCL 75

General Accessories 137


Lighting

LTH, Dual light LTHM, Dual light with movement sensor


IP 20 IP 20

Description: For fixed use or with the addition of the accessory LTHC
as a removable hand lamp for more precise illumination. Self-adhesive
or screw fixing support. Provided with a PIR movement sensor. Appr. 3
Description: For fixed use or with the addition of the accessory LTHC min. fixed switch-on-duration.
as a removable hand lamp for more precise illumination. Self-adhesive Operating voltage: 230V, 50Hz.
or screw fixing support, provided with a press button on/off switch. Power: 20 W (± 100W bulb), lamp included.
Operating voltage: 230V, 50Hz. DC 120V on request. Lamp: Energy-saving, E27 socket. 10000h live time.
Power: 20 W (± 100W bulb), lamp included. Connection: 6 pole screw connector 2.5 mm2, for power, second lamp
Lamp: Energy-saving, E27 socket. 10000h live time. in parallel and external door switch. For power, second lamp in parallel
Connection: 6 pole screw connector 2.5 mm2, for power, second lamp and external door switch.
in parallel and external door switch. Housing: Plastic, impact resistant, UL94VO.
For power, second lamp in parallel and external door switch.
Housing: Plastic, impact resistant, UL94VO. Cat.no.
LTHM
Cat.no.
LTH

■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
LTL, Enclosure light
Hand lamp cable, LTHC
IP 20

Mains cable to transform the LTH to an hand lamp. Provided with wall
holder. Cable length: 2 m.

Cat.no.
LTHC 02 Description: Fluorescent lamp, equipped with switch, electronic star-
ter, integrated socket and a protection cap. A male GST 18/3 connec-
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ tor is provided for the connection to the power on one side and by a
pass-through circuit a female connector allows a further connection on
Door switch leads, DSWC the other side. An additional connector ST 17/2 allows the command
of the lamp by a doorswitch.
Standard socket:120/230 V/ 50/60Hz / 16A Schuko. Other country
specific sockets available on request.
Pack quantity: 1 piece with tube and fixing devices.
Size: 14W 38 x 97 x 400 mm
18W 38 x 97 x 630 mm

Watt Frequency Cat.no.


14W 120V 50 Hz LTL 1415
60 Hz LTL 1416
14W 230V 50 Hz LTL 1425
Door switch connecting cable for LTL:
60 Hz LTL 1426
Pack quantity: 5 pieces.
18W 120V 50 Hz LTL 1815
60 Hz LTL 1816
Cat.no. 18W 230V 50 Hz LTL 1825
DSWC 1005 60 Hz LTL 1826

138 General Accessories


Mains leads, CLF Female connectors, COF

Cable (3 x 1.5 mm2) with female GST 18/3 connector at one end for the Pack of 5 female GST 18/3 connectors.
connection to mains power. Length: 3 m.
Pack quantity: 5 pieces.
Cat.no.
Cat.no. COF 05
CLF 3005

■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

Connection leads, CLM Male connectors, COM

Cable (3 x 1.5 mm2) with male GST 18/3 connector at one end for the Pack of 5 male GST 18/3 connectors.
connection to power outlet of any device or further enclosure circuit.
Length: 1 m.
Cat.no.
Pack quantity: 5 pieces.
COM 05

Cat.no.
CLM 1005

■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

Door switch, DSW Power socket, LPS

Fixed (without screws) on the inside hole pattern of the enclosure


frame.
Cable entry M 20, UL-CSA approved.
Switching load 6A-230V.
Pack quantity: 1 piece with mounting material ClIP for 35 mm DIN rail mounting. Pressure clamp connections for
easy and quick wiring. 10A, 250V.
92 x 62 x 48 mm, weight appr. 120g.
Material: Plastic, light grey.
Cat.no. Pack quantity: 1 piece
DSW 01

Description Cat.no.
Schuko LPS 10
France LPS 10 FR
Switzerland LPS 10 CH
England LPS 10 UK
USA/Canada LPS 10 USA

General Accessories 139


Mounting Material

Quick fixing, PQF Extrudetite screws, CNT

Torx extrudetite screws for the fitting of accessories, click in profiles,


earthing etc.
Pack quantity: 250 pieces
Self-adhesive plastic unit bears continuously load up to 500g (after
24h), and can be placed on any clean surfaces except polyethylene, Thread Cat.no.
polypropylene and rubber. Holes for screws fixing are provided for M5 CNT 05
heavy applications. M6 CNT 06
Pack quantity: 5 pieces with screws.

Cat.no.
PQF 05 Screws for cage nuts, CNS
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

Sliding nuts for mounting rails, GLM

Socket head screws M6x12 for cage nuts


Pack quantity: 250 pieces
Electrogalvanized steel. Pack quantity: 50.
Thread Cat.no.
Thread For Cat.no. M6 CNS 612
M6 CP 1020/U GLM 20-6
M8 CP 1020/U GLM 20-8
M6 CP 1040/U GLM 40-6
M8 CP 1040/U GLM 40-8 ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ Cage nuts, CNM


Pressure compensation plug, PVD

Cage nuts M 6 designed for universal use on the enclosure frame pro-
files and the profile system.
Pack quantity: 50 pcs.

Thread Cat.no.
M6 CNM 615
M6 CNM 620
For optimal pressure, it is recommended that 2 plugs are installed dia- M8 CNM 815
gonal to each other. M8 CNM 820
Mounting: PG 29 thread with union nut. Diameter 65,5 x 30,5 mm.
IP 45.
Material: ABS/PC, grey.
Pack quantity: 2 pieces.

Cat.no.
PVD 02

140 General Accessories


Mounting Material

Appliance cover, ventilated, PLA Paint can, BFP

Protective hood for ventilation openings. Material: Plastic ASA,


light grey. High resistance to UV and weather. Airdrying paint, for repairs and touch-up of powder coated or wet pain-
IP 20 ted surfaces. Contents: 400 ml.

Cat.no. Colour Colour Cat.no.


PLA 01 RAL 7022 black BFP 7022
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ RAL 7030 mid grey BFP 7030
RAL 7032 pebble grey BFP 7032
DIN rails, PP RAL 7035 light grey BFP 7035
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

Mounting rails, CP

Galvanised steel. Environmental friendly at 15-20 microns.


DIN rail according to EN 60715. Hole pattern 18 x 5.2 mm
Pack quantity: 2 m x 15. Galvanised steel with 25 mm hole pattern.
Pack quantity: 10 profiles 3 m long
Hole
Dim. pattern Cat.no. DIM Cat.no.
5 x 15 10 PP 0515 H 10 x 20 CP 1020
7 x 35 10 PP 0735 10 x 20 CP 1020 U
7 x 35 25 PP 0735 H 20 x 20 CP 2020
15 x 32 25 PP 1532 20 x 20 CP 2020 U
15 x 32 25 PP 1532 H 20 x 40 CP 2040
15 x 35 25 PP 1535 20 x 40 CP 2040 U
15 x 35 25 PP 1535 H
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

Drawing pocket, DRB Document pocket, DRA

A large steeel document pocket fixed directly onto the door frame. Self adhesive, for DIN A4 format.
Usable depth: 68 mm. Usable depth: 30 mm.
Material: 1.5 mm steel plate. Colour: grey
Finish: structure powder paint, RAL 7032. Material: Thermoplastic
Pack quantity: 1 piece with mounting material.
Cat.no.
W Cat.no. DRA 04
1000 (double door x 2) DRB 500
600 DRB 600
800 DRB 800
1000 DRB 1000

General Accessories 141


Mounting Material

Mounting kits, MSA Glazed doors, ADA

23.5

31

With this kit the glazed doors ADA can be used as viewing windows on To replace the standard steel door. Can be used in combination with
any enclosure surface, to provide protection for displays and other swing frame, modular chassis or inner door. The 3 mm DIN lock can be
control elements. replaced by any optional insert or handle.
Material: Anodised aluminium.
Protection: IP 54. Acrylic glass 3 mm.
Depth Cat.no. Pack quantity: 1 piece with mounting material.
23,5 mm MSA
H W Cat.no.
300 300 ADA 03030
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
400 300 ADA 04030
400 ADA 04040
Mounting kits, MSB 600 ADA 04060
500 300 ADA 05030
400 ADA 05040

■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

Glazed doors, ADAB


57.5
50

With This kit the glazed doors ADAB can be used as viewing windows
on any enclosure surface, to provide protection for displays and other
control elements.

Depth Cat.no.
50 mm MSB

To replace the standard steel door. Can be used in combination with


swing frame, modular chassis or inner door. The 3 mm DIN lock can be
replaced by any optional insert or handle.
Material: Anodized aluminium.
Protection: IP 54. Acrylic glass 3 mm.
Pack quantity: 1 piece with mounting material.

H W h w Cat.no.
600 400 522 322 ADAB 06040
600 522 522 ADAB 06060
800 522 722 ADAB 06080
700 500 622 422 ADAB 07050
800 600 722 522 ADAB 08060

142 General Accessories


SL, Signal towers Acoustic module, SL-AM

IP 54/65

Volt Cat.no.
24V SL50 AM24
115V SL50 AM115
230V SL50 AM230

■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

Ambient temperature: +45°C to -25°C. Light bulbs, SL-L


Storage temperature: +60°C to -30°C (with LED)
Description: Modular design with a sturdy enclosure for all indoorand
outdoor applications where the going gets rough. In six different globe
colours can be plugged together. Up to as many as five modules with
a choise of six different globe colours can simply plugged
together.Versatility in installation: Stand, tube or direct mounting com-
ply with DIN ISO 14000.
Four different modules:
- Module with continuous beam max. 7 W
- Blinking-light module max. 7 W
- Flashing-light module max. 0,6 joules LED bulbs available on request.
- Acoustic module 85 dB (A) Watt Volt Cat.no.
7 24V SL50 L7W24
H Cat.no.
115V SL50 L7W115
50 mm Base and end module SL 50
230V SL50 L7W230
5 24V SL50 L5W24
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ 115V SL50 L5W115
230V SL50 L5W230
Blinking light module, SL-230

230 V ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
Colour Cat.no.
Transparent SL50 BCL 230 Led bulbs, SL-LED
Yellow SL50 BYE 230
Amber SL50 BAM 230
Red SL50 BRE 230
Green SL50 BGR 230
Blue SL50 BBL 230

■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

Blinking light module, SL-24


Colour Volt Cat.no.
transparent 24V SL50 LED-WH 24
24 V yellow 24V SL50 LED-YE 24
Colour Cat.no. red 24V SL50 LED-RE 24
Transparent SL50 BCL 24 green 24V SL50 LED-GR 24
Yellow SL50 BYE 24 blue 24V SL50 LED-BL 24
Amber SL50 BAM 24 transparent 115V SL50 LED-WH 115
Red SL50 BRE 24 yellow 115V SL50 LED-YE 115
Green SL50 BGR 24 red 115V SL50 LED-RE 115
Blue SL50 BBL 24 green 115V SL50 LED-GR 115
blue 115V SL50 LED-BL 115
transparent 230V SL50 LED-WH 230V
yellow 230V SL50 LED-YE 230V
red 230V SL50 LED-RE 230V
green 230V SL50 LED-GR 230V
blue 230V SL50 LED-BL 230V

General Accessories 143


Continious beam module, SL-C Tubular stand, SL-S

Angle of beam: 360°. Max mounting of 5 modules.

Colour Cat.no. With plinth


Transparent SL50 CCL H Cat.no.
Yellow SL50 CYE 100 SL50 S100
Amber SL50 CAM 250 SL50 S250
Red SL50 CRE 400 SL50 S400
Green SL50 CGR
Blue SL50 CBL ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
Tubular stand, SL-T

Mounting kit, SL-BG

Mounting kit with gasket for direct mounting IP 65.

Cat.no.
SL50 BG
With bracket
H Cat.no.
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ 100 SL50 T100
250 SL50 T250
Tube gasket, SL-TG 400 SL50 T400

■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

Wall bracket, SL-W

For IP 65
Package quantity: 5 pieces

Cat.no.
SL50 TG

■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

Gasket, SL-MG With hood for mounting stand.

Cat.no.
SL50 W

Gasket for light and base module IP 65.


Pack. quantity: 5 pieces

Cat.no.
SL50 MG

144 General Accessories


ESS, Software ELCAE

ELDON Computer Aided Engineering – ELCAE


The computerised system ELCAE helps the design process of electri-
cal and electronic engineering automating enclosure and component
selection and implementation and deleting many repetitive and tedious
tasks.
The power and versatility of this system allows the user to create virtual
cabinets in a realistic fashion, as well as documenting these objects
and calculating labour costs and thermal management requirements.
ELCAE can create a Microsoft Excel spreadsheet with the parts list,
cost calculations for the enclosure and it’s accessories, components,
labour, and thermal calculations, whilst allowing you to quickly update
the prices if required.
ELCAE can create basic geometrical figures (line, circle and rectangles),
either manually or using parameters to show the position of holes for
component accessories, which can be output to a drawing. You can
also write short text, insert dimensions and carry out enlargements of
the drawing using the zoom functions.
enlargements of the drawing using the zoom functions.