DG details
DG KVA Capacity DGKVA Calculated 250 KVA
DG rated Voltage DGV Given data 415 V
Rated P.F. of DG DGcosF Given data 0.8
Sinf DGsinF SQRT(1-DGcos2F) 0.60
DG KW Capacity DGKW DGKVA * DGcos F 200 KW
DG KVAR Capacity DGKVAR DGKVA * DGsinF 150 KVAR
DG impedance DGX'd assumed 0.10
Starting of 132KW Motor with VFD
Starting motor current rampup maximum with VFD in per unit
Isspu calculated 1.5 p.u.
Starting current rampup maximum with VFD in Ampere Iss Isspu x Ifl 357 Amps
Starting KVA of motor with VFD KVASS 1.73 * Ifl * Iss * V 256 KVA
Starting KW of motor with VFD KW SS KVASS*cosf 145 KW
Motor starting power factor Cosf1 assumed 0.57
2
Motor starting Sinf Sinf1 SQRT(1-Cosf 1) 0.82
Starting KVAR of motor KVARSS KVASS x Sinf1 211 KVAR
There is no sudden surge on DG while starting motor with VFD ,motor will start with out any over load on DG .