Professional Documents
Culture Documents
Sprinkler Monitoring: Room Temperature Devices
Sprinkler Monitoring: Room Temperature Devices
to start, and lack of fuel, phase reversal, pump running signal, etc.
Gamewell
Silent Knight
IdentiFlex 602 Fire-Lite Alarms MS-9600
5820XL
• Addressable (multiplexed)
24 VDC Filtered
Resettable Power
Basic Fire All 2004-v2.ppt
FIRE
ALARM
CONTROL
PANEL
Basic Fire All 2004-v2.ppt
Z1 Z3
Z2
Basic Fire All 2004-v2.ppt
• Floor-Above/Floor Below
• Elevator Recall
• Smoke Control
• Ring-By-Zone
• Door Locks (Card Access)
• Cross Zoning
Basic Fire All 2004-v2.ppt
alarm events?).
CAUTION!
responders.
Maximum
radius of
Spot detector Typical area
protection
placement is based of room protection
on central mounting 21’
30’
of a detector in a 30’
Smoke
X 30’ room. No area Detector
’
21
may be more than
21’ from the 30’
Basic Fire All 2004-v2.ppt
detector.
Room Maximum
Note that in this radius of
application, two protection
detectors are not Smoke
Detector
required because 41’
all areas within the
room are within 21
21’
feet of the detector.
Basic Fire All 2004-v2.ppt
10’
30’
30’
Basic Fire All 2004-v2.ppt
15’ 15’
90’
12 Detectors
90' / 30' = 3 Rows
29 Honeywell Brands Basic Fire 2005-V4 08-17-05.ppt
120’
90’
12 Detectors
10,800' / 900' = ...
30’
15’
21’
21’
10' x 120' Corridor
21’
When one dimension
falls below the 0.7 of
the listed spacing (21')
employ the 21-foot
rule.
21’
21’
Basic Fire All 2004-v2.ppt
Minimum detector
mounting distance.
Sidewall-mounted
detectors can be as much
as 12" from the ceiling.
Basic Fire All 2004-v2.ppt
3 ft
Basic Fire All 2004-v2.ppt
3 ft
Basic Fire All 2004-v2.ppt
26-28 40
28-30 34
48 Inches
Basic Fire All 2004-v2.ppt
system.
• NFPA: 15 dB above
average ambient sound
level or 5 dB above
maximum 60-second
sound level, whichever is
greater (minimum of 75
dBA), measured at the
pillow.
Basic Fire All 2004-v2.ppt
10 ft 20 ft 30 ft 40 ft
15 dB above = 67 dBA @ 10 ft
67 dbA @ 40 ft
73 dbA @ 20 ft
79 dbA @ 10 ft
Basic Fire All 2004-v2.ppt
40’
Basic Fire All 2004-v2.ppt
40’
79 dB
150’
Basic Fire All 2004-v2.ppt
230’
40’
80’
79 dB
85 dB
150’
Basic Fire All 2004-v2.ppt
@ 10 ft - 95 dbA
@ 20 ft - 89 dbA
@ 40 ft - 83 dbA
@ 80 ft - 77 dbA
@ 160 ft - 71 dbA
@ 320 ft - 65 dbA
150’
Basic Fire All 2004-v2.ppt
NFPA ADA
• Wall mounted devices • The appliance shall be placed
shall have their bottoms at 80 inches above the highest
heights above the finished floor level within the space, or 6
floor of not less than 80 inches from the ceiling,
inches, and not greater whichever is lower.
than 96 inches. • Devices shall be no more than
50 ft. apart.
• Maximum separation of • In large areas without
appliances shall not exceed obstructions 6 ft. above the
100 feet. floor, devices may be spaced a
maximum of 100 feet apart.
Basic Fire All 2004-v2.ppt
ADA ADA
96" 96"
At At
least least
6" 6"
80" 80"
NFPA NFPA
At least 90"
Strobe Horn/Strobe
1 - 15 cd
1 - 15/75 cd
20' x 20’
1 - 34 cd
2 - 15 cd
30' x 30’
1 - 60 cd
2 - 30 cd
4 - 15 cd 40' x 40’
Basic Fire All 2004-v2.ppt
1 - 110 cd
2 - 60 cd
4 - 30 cd 50' x 50’
76 Honeywell Brands Basic Fire 2005-V4 08-17-05.ppt
Dual-Candela Appliances
15/75 cd
15 cd
75 cd
40' x 15’
Basic Fire All 2004-v2.ppt
50’
2500 sq ft x 0.0375
lumens/ sq ft
= 93.75 cd
Basic Fire All 2004-v2.ppt
93.75/4 = 23.44 cd
50’
Basic Fire All 2004-v2.ppt
50’
1 - 60 cd @ 10 ft 1 - 80 cd @ 20 ft
1 - 30 cd @ 10 ft
1 - 15 cd @ 10 ft
1 - 30 cd @ 20 ft
1 - 60 cd @ 30 ft
20' x 20’
1 - 45 cd @ 20 ft
1 - 75 cd @ 30 ft
Basic Fire All 2004-v2.ppt
30' x 30’
1 - 115 cd @ 30 ft 40' x 40’
• Synchronization is effected
via two means - a remote
module or circuitry built into
the fire alarm control panel.
Style B D
Short
From NFPA 72
EoL
Multi-Riser Wiring
IDC (+)
Initiating
Zone
IDC (-)
+24VDC
UL Listed
Power
4-Wire Supervisory
Detector
Basic Fire All 2004-v2.ppt
Relay
Common
Power
separate knockouts.
• Power UP - Connect
AC wiring, turn on
main breaker, then
connect batteries.
Basic Fire All 2004-v2.ppt
Unbroken wire
loops under
teeter connections
Basic Fire All 2004-v2.ppt
Broken wire
loops under
teeter connections
Basic Fire All 2004-v2.ppt
• No branch-tapping allowed.
Style Y Style Z
Alarm Alarm
Condition Trouble Trouble
Capable Capable
Single
Yes N/R Yes Yes
Open
Single Yes
Yes Yes Yes
Ground
Wire
Basic Fire All 2004-v2.ppt
Yes No Yes No
Short
From NFPA 72
116 Honeywell Brands Basic Fire 2005-V4 08-17-05.ppt
NAC Wiring
manufacturers specifications.
FIRE
ALARM
CONTROL
PANEL
Basic Fire All 2004-v2.ppt
output side.
FIRE
ALARM
CONTROL
PANEL
Basic Fire All 2004-v2.ppt
Ground
From NFPA 72
FIRE
ALARM
CONTROL
PANEL
Basic Fire All 2004-v2.ppt
Style
Class IDC NAC SLC
Class B B Y 4
Class A D Z 6, 7
Basic Fire All 2004-v2.ppt
- Voltage spikes
w Lightning
w HVAC or other electrical equipment.
w Radios, walkie talkies, etc.
Basic Fire All 2004-v2.ppt
Short Circuit
ALARM Threshold
Detector Current
Basic Fire All 2004-v2.ppt
Supervisory Level
Open Circuit
• Radio-Frequency Interference
(RFI) can cause false alarms
and troubles to occur on
conventional initiating circuits
and communications
problems on addressable
circuits.
0= Black
Tolerance indicated at
1 = Brown
other end of ELR:
2 = Red
3 = Orange Gold = 5%
4 = Yellow Silver = 10%
5 = Green None = 20%
6 = Blue
Basic Fire All 2004-v2.ppt
7 = Violet
8 = Gray
9 = White
142 Honeywell Brands Basic Fire 2005-V4 08-17-05.ppt
Example
4.7 K W
YELLOW = 4
VIOLET = 7
MULTIPLIER = 2
Basic Fire All 2004-v2.ppt
(number of zeros)
TOLERANCE = 5 %
143 Honeywell Brands Basic Fire 2005-V4 08-17-05.ppt
Alarm Verification
• Used to help prevent nuisance alarms.
• Conventional systems reset the alarmed zone
and then enter a retard (wait) state for a
specified period of time to allow smoke to
escape from the sensing chamber.
• After the reset/retard period, the panel monitors
the zone for a set time period (maximum 120
seconds). Reacquisition during this period is a
verified alarm. Failure to reacquire alarm is
considered an unverified alarm.
Basic Fire All 2004-v2.ppt
0 6 18 120
TIME (seconds)
Basic Fire All 2004-v2.ppt