IAPMO-ER - 0327 (Sika AnchorFix-2)
IAPMO-ER - 0327 (Sika AnchorFix-2)
EVALUATION SUBJECT: and the adhesive, and bond between the adhesive and the
SIKA ANCHORFIX®-2 ADHESIVE concrete.
ANCHORING SYSTEM
3.2 Product Information
REPORT HOLDER:
Sika Services AG The components of the Sika AnchorFix®-2 Adhesive
Tueffenweis 16 Anchoring System, include the Sika AnchorFix®-2
Zurich-8048 Adhesive cartridges, SAF KW static mixing nozzles,
dispensers, and steel anchoring elements. Sika Services
Switzerland AG’s printed installation instructions (MPII), guidelines,
and parameters are included with each adhesive unit
CSI Division: 03 – Concrete package, and are replicated in Figures 5a and 5b of this
CSI Section: 03 15 19 – Cast-in Concrete Anchors report. Installation may occur into dry or water-saturated
normal-weight or lightweight concrete. Installation in
CSI Division: 05 – Metals water-filled holes is outside the scope of this report.
CSI Section: 05 05 19 – Post-Installed Concrete
Anchors Continuously-threaded steel rods or deformed steel
reinforcing bars shall be provided by the installer or a third
1.0 SCOPE OF EVALUATION party according to standard specifications and are not
proprietary.
1.1 Compliance to the following codes & regulations:
2012, 2009, 2006, 2003 International Building 3.3 Material Information
Code® (IBC)
2012, 2009, 2006, 2003 International Residential 3.3.1 Sika AnchorFix®-2 Adhesive: Sika AnchorFix®-2
Code® (IRC) adhesive contains two components: styrene-free epoxy
acrylate resin and benzoyl peroxide catalyst. Shelf life is
1.2 Evaluated in accordance with: 15 months when in unopened cartridges stored at
ICC-ES Acceptance Criteria for Post-Installed temperatures ranging from 41°F (+5°C) to 77°F (+25°C) )
Adhesive Anchors in Concrete Elements in accordance with the MPII.
(AC308), approved June 2015.
3.3.2.2 Sika AnchorFix®-2 CIC cartridges: Sika
1.3 Properties assessed: AnchorFix®-2 CIC are single component cartridges
Structural containing Sika AnchorFix®-2 adhesive and labeled for
volumes shown as CIC 300 – 300 ml (10.14 oz.), or CIC
2.0 PRODUCT USE 850 – 850 ml (28.74 oz.). Figure 3 of this report depicts the
cartridges.
Sika AnchorFix®- 2 Adhesive Anchoring System is used to
resist static, wind, or earthquake (Seismic Design 3.3.3 Mixing nozzles: Figure 4 of this report illustrates the
Categories A or B only) tension and shear loads in mixing nozzle SAF KW.
uncracked normal-weight or lightweight concrete having a
specified compressive strength, f'c, of 2,500 psi to 8,500 psi 3.3.4 Dispensing Tools: Sika AnchorFix®-2 adhesive may
(17.2 MPa to 58.6 MPa). Anchors shall be located in a be dispensed by manual dispensers or pneumatic
region of the concrete member where analysis indicates no dispensers. Figure 2 of this report shows the cartridge size
cracking (uncracked) at service loads in accordance with and corresponding types of appropriate dispensers.
ACI 318 D.5.2.6 and D.6.2.7. The anchor system is an
alternative to cast-in-place anchors described in Sections 3.3.5 Permitted Component Combinations: Table 1 of
1911 and 1912 of the IBC. The anchor systems may also this report contains the allowable combinations of
be used where an engineered design is submitted in cartridges, mixer nozzles, and dispensing tools.
accordance with Section R301.1.3 of the IRC.
3.3.6 Anchors
3.0 PRODUCT DESCRIPTION
3.3.6.1 Threaded Rods: Threaded steel rods shall be
3.1 General: The Sika AnchorFix®- 2 Adhesive Anchoring clean, continuously threaded rods in diameters as described
System are post-installed anchors inserted into a pre-drilled in Table 4 and Figure 1 of this report. Specifications for
hole in hardened normal weight or lightweight concrete carbon and stainless steel rod, nut, and washer are provided
and transfers loads to the concrete by bond between the in Table 4 of this report. Available rod diameters and steel
anchor
The product described in this Uniform Evaluation Service (UES) Report has been evaluated as an alternative material, design or method of construction in order to satisfy and comply with
the intent of the provision of the code, as noted in this report, and for at least equivalence to that prescribed in the code in quality, strength, effectiveness, fire resistance, durability and safely,
as applicable, in accordance with IBC Section 104.11.
Copyright © 2016 by International Association of Plumbing and Mechanical Officials. All rights reserved. Printed in the United States. No part of this publication may be reproduced, stored in
an electronic retrieval system, or transmitted, in any form or by any means, electronic, mechanical, photocopying, recording or otherwise, without the prior written permission of the publisher.
Ph: 1-877-4IESRPT • Fax: 909.472.4171 • web: www.uniform-es.org • 4755 East Philadelphia Street, Ontario, California 91761-2816 – USA
Number: 327
Originally Issued: 12/13/2013 Revised: 12/22/2015 Valid Through: 12/31/2016
design information are detailed in Tables 5 and 6 of this Categories used to determine the strength reduction
report. Carbon steel threaded rods shall be furnished with a factors,, in D4.3 or D.4.4 of ACI 318 are given for each
0.0002-inch-thick (0.005 mm) zinc electroplated coating diameter in Tables 7, 8, and 9 of this report. Anchor
complying with ASTM B 633 SC 1 or shall be hot-dipped designs shall satisfy the requirements of ACI 318 Sections
galvanized complying with ASTM A153, Class C or D. D.4.1.1, D.4.1.2, and D.4.1.3. Anchor group effects shall
Threaded steel rods shall be straight and free of be considered in accordance with ACI Section D.3.1.1.
indentations or other defects along their length. The Design parameters including strength reduction factors,,
embedded portions of the threaded rods shall be free of mill corresponding to each limit state and anchor steel are
scale, rust, mud, oil, and other coatings that may impair the provided in the tables. Strength reduction factors,, as
bond with the adhesive. The tensile strength of the threaded described in ACI 318 D.4.3 and provided in Tables 5 to 9
anchor rods shall not exceed 145,000 psi (1,000 MPa). shall be used for load combinations calculated in
accordance with Section 1605.2 of the IBC and ACI 318
3.3.6.2 Ductility: In accordance with ACI 318 Appendix Section 9.2. Strength reduction factors, ø, described in
D.1, anchor elements are considered ductile if the tested ACI 318 Section D.4.4 shall be used for load
elongation is at least 14 percent and reduction of area at combinations calculated in accordance with Appendix C
least 30 percent. Steel elements not complying with these of ACI 318. In conformance with ACI 318, all equations
criteria are considered brittle. Values for various steel are expressed in inch-pounds units.
specifications are provided in Table 5 and Table 6 of this
report. Where values are nonconforming or unstated, the 4.1.1.1 Static steel strength in tension: Nominal strength
steel shall be considered brittle for the purposes of design. of a single anchor in tension as governed by the steel, Nsa,
Deformed reinforcing bars meeting the requirements of in accordance with ACI 318 D.5.1.2, is given in this report
ASTM A615 or A706 shall be considered as ductile steel for the corresponding anchor steel specification. Tables 4,
elements. 5 and 6 of this report provide nominal strength values and
strength reduction factors,, depending on whether the
3.3.7 Concrete: Normal-weight and lightweight concrete steel is considered brittle or ductile in accordance with ACI
shall comply with Sections 1901 and 1903 of the 2012 IBC 318 Section D.4.4, for computing design strengths of steel
or Sections 1903 and 1905 of the 2009, 2006, and 2003 IBC anchor elements.
and have a compressive strength at the time of anchor
installation of 2,500 psi (17.2 MPa) minimum, but not less 4.1.1.2 Static concrete breakout strength in tension:
than that required by the applicable code requirements, Nominal static concrete breakout strength of a single
including IBC Section 1904 and ACI 318-11 Section 4.3, anchor or group of anchors in tension, Ncb or Ncbg, shall be
or the structural design, nor more than 8,500 psi (58.6 calculated in accordance with ACI 318 D.5.2 with the
MPa). following addition:
3.3.8: Hole Preparation Equipment: Holes shall be Basic concrete breakout strength of a single anchor in
cleaned with hole-cleaning brushes and air nozzles. tension, Nb, shall be calculated in accordance with ACI 318
Brushes shall be the appropriate size brush from the list D.5.2.2 using the values of hef and kc,uncr as described in
shown in Table 11 of this report, and the MPII shown in Table 7 of this report. Corresponding strength reduction
Figures 5a and 5b of this report, which provide additional factors, are given in Table 5 of this report for Condition
information. Air nozzles shall be equipped with an B, as defined in ACI 318 D.4.3. For anchors in lightweight
extension capable of reaching the bottom of the drilled- concrete, the modification factors λ and λa shall be applied
hole and having an inside bore diameter of not less than 1/4 in accordance with ACI 318-11 D.3.6.The value of f′c used
inch (6 mm). Holes shall be prepared in accordance with in design shall be limited to a maximum of 8,000 psi (55
the installation instructions shown in Figures 5a and 5b of MPa) in accordance with ACI 318 D.3.7.
this report.
4.1.1.3 Static bond strength in tension: The nominal
4.0 DESIGN AND INSTALLATION static bond strength of a single adhesive anchor, Nba, or
group of adhesive anchors in tension shall be calculated in
4.1 General: Strength design under the 2012, 2009, 2006 accordance with ACI 318-11 D.5.5 using τk,uncr from Table
and 2003 IBC, as well as the 2012, 2009, 2006 and 2003 8 or 9 of this report in lieu of τcr. Embedment depths shall
IRC shall be in accordance with ACI 318-11 (ACI 318) and comply with ACI 318-11 D.4.2.3 and Tables 8 to 10 of this
Section 4.1.1 of this report. Allowable Stress Design shall report. Bond strength values are a function of concrete
be in accordance with Section 4.1.2 of this report. Anchors conditions (i.e., uncracked), installation conditions (i.e.
shall be located in a region of the concrete member where dry, water saturated), concrete temperature, drilling
analysis indicates no cracking at service load levels. method (i.e., hammer drill), and special inspection level
(i.e., periodic). The Sika AnchorFix®-2 Adhesive system
4.1.1 Strength Design: Design strengths Nn and Vn has been tested at elevated temperatures in uncracked
shall be determined in accordance with ACI 318 concrete using a hammer drill in water saturated concrete
Appendix D and this report. Post-installed Anchor holes. Therefore permitted bond strengths anchor
Page 2 of 19
Number: 327
Originally Issued: 12/13/2013 Revised: 12/22/2015 Valid Through: 12/31/2016
categories, and strength reduction factors, ø, for each interaction of tension and shear shall be calculated in
anchor diameter for installation in normal weight concrete accordance with ACI 318 D.7.
are listed in Tables 8 and 9 of this report. Elevated concrete
temperatures arise from a number of factors, including sun 4.1.1.8 Minimum member thickness hmin, anchor
exposure, proximity to operating machinery, or spacing smin and edge distance cmin: In lieu of ACI 318
containment of liquids or gasses at elevated temperature. D.8.1 and D.8.3, values of cmin and smin described in Table
Permitted installation requirements are uncracked 7 of this report shall be observed for anchor design and
concrete, dry or water-saturated holes prepared using installation. Likewise, in lieu of ACI 318 D.8.5, the
hammer drill bits, under periodic inspection (except for minimum member thickness, hmin, described in Tables 3
conditions as explained in Section 4.3.2 of this report, and 7 of this report shall be observed for anchor design and
where continuous inspection is required). For anchors installation. In determining minimum edge distances, cmin,
installed in lightweight concrete, the value of τuncr shall be the following section shall be added to ACI 318, Appendix
taken from Tables 8 or 9 of this report and the D:
corresponding modification factors, λ and λa, shall be
applied to Eq. (D-22) in accordance with ACI 318-11 D.8.8 – For adhesive anchors that will remain untorqued,
D.3.6. the minimum edge distances shall be based on minimum
cover requirements for reinforcement in 7.7. For adhesive
4.1.1.3.1 Sustained Loads: For anchors designed to resist anchors that will be torqued, the minimum edge distance
sustained tension loads, bond strength shall be calculated and spacing shall be taken as described in Table 7 of this
in accordance with ACI 318-11 D.3.5 and D.4.1.2. In report.
addition to requirements in Section 4.1.1.3 of this report for
the design of a single anchor in tension to resist sustained 4.1.1.9 Critical edge distance cac: In lieu of ACI 318
loads, ACI D.4.1.2 shall apply, using τk,sust,uncr from Table D.8.6, values of cac shall be determined in accordance with
8 or 9 of this report in lieu of τcr. Eq. (4-1) as follows:
4.1.1.4 Static steel strength in shear: The nominal static cac = hef(τk,uncr /1160)0.4 × [3.1 – 0.7(h/hef)] (inches)
strength of a single anchor in shear as governed by the (4-1)
steel, Vsa, in accordance with ACI 318 D.6.1.2, and
corresponding strength reduction factors, ø, for use with cac = hef(τk,uncr /8)0.4 × [3.1 – 0.7(h/hef)] (mm)
load combinations of ACI 318 Section 9.2 in accordance (4-1)
with ACI 318 D.4.3, depending on whether the steel is
considered brittle or ductile, are given in Tables 5 and 6 of where
this report for the anchor steel specification. τk,uncr = the characteristic bond strength in uncracked
concrete. Permitted values are given in Tables 8 and 9 of this
4.1.1.5 Static Concrete breakout strength in shear: The report, psi (MPa)
nominal static concrete breakout strength of a single anchor
or group of anchors in shear in shear, Vcb, or Vcbg, shall be
(h/hef) need not be taken as larger than 2.4.
calculated in accordance with ACI 318 D.6.2 based on
information given in Table 7 of this report for the τk,uncr ≤ kuncr ((hef × f’c)0.5/(π × d)) (4-2)
corresponding anchor steel type. The basic concrete
breakout strength of a single anchor in shear, Vb, shall be
calculated in accordance with ACI 318 D.6.2.2 using the
values of d and hef given in Tables 7 of this report for the h = the member thickness, inches (mm)
corresponding anchor steel in lieu of do and le, respectively. hef = the embedment depth, inches (mm)
In no case shall hef exceed 8d. For anchors in lightweight
concrete, the modification factors λ and λa shall be applied 4.1.2 Allowable Stress Design (ASD)
in accordance with ACI 318-11 D.3.6. The value of f′c shall
be limited to a maximum of 8,000 psi (55 MPa) in 4.1.2.1 ASD Derivation: Design values for use with
accordance with ACI 318 D.3.7. Corresponding strength allowable stress design load combinations shall be
reduction factors, ø,are given in Table 7 of this report for established as follows:
Condition B, as defined in ACI 318 D.4.3.
For anchors designed using load combinations in
4.1.1.6 Static Concrete Pryout Strength in shear: The accordance with IBC Section 1605.3 (Allowable stress
nominal static pryout strength of a single anchor or group design), allowable loads shall be established using Eq. (4-
of anchors in shear, Vcp or Vcpg, shall be calculated in 3) and Eq. (4-4).
accordance with ACI 318 D.6.3.1.
Nn
4.1.1.7 Interaction of tensile and shear forces: For the
designs that include combined tension and shear, the
T allowable, ASD
Page 3 of 19
Number: 327
Originally Issued: 12/13/2013 Revised: 12/22/2015 Valid Through: 12/31/2016
Page 4 of 19
Number: 327
Originally Issued: 12/13/2013 Revised: 12/22/2015 Valid Through: 12/31/2016
performed in the absence of the special inspector. Where Calculations and details shall be prepared by a registered
there is any change in the anchor product being installed or design professional where required by the statutes of the
the personnel performing the installation, another initial jurisdiction in which the project is to be constructed.
inspection is required. For ongoing installations over an
extended period of time the special inspector shall make 5.3. Anchors shall be installed in uncracked, normal-
regular inspections to confirm correct handling and weight or light-weight concrete having a specified
installation of the product. compressive strength fc΄= 2,500 psi to 8,500 psi (17.2 MPa
to 58.6 MPa) only.
As a minimum, the following items shall be verified by the
special inspector: 5.4. Values of fc΄ used for calculation purposes shall not
exceed 8,000 psi (55.1 MPa).
Hole drilling method in accordance with the
manufacturer’s printed installation instructions 5.5. Anchors shall be installed in concrete base
(MPII) shown in Figures 5a and 5b of this report. materials as set forth in Section 4.2 and Figure 5 of this
Hole depth, location, spacing, edge distances and report in holes predrilled with carbide-tipped drill bits
diameter. Hole cleaning in accordance with the complying with ANSI B212.15-1994 for imperial sizes or
manufacturer’s printed installation instructions ISO 5468 for metric sizes.
(MPII) shown Figures 5a and 5b of this report.
Anchor diameter, length, material, and element 5.6. Use of the anchors is limited to installation in concrete
type. that is expected to be uncracked during service life of the
Tightening torque. anchors subject to the conditions in this report.
Concrete type, compressive strength, and
thickness. 5.7. Anchors may be used to resist tension and shear forces
Adhesive installation in accordance with the in floor (downwardly inclined) or wall (horizontally
manufacturer’s printed installation instructions inclined) orientations only if installation is within base
(MPII) shown in Figures 5a and 5b of this report. material having a temperature between 32°F to 95°F (0° C
The adhesive expiration date. to 35°C); or ceiling (upwardly inclined) orientations, if
Product identification in accordance with Section installation is within base material having a temperature
7.0 of this report. between 50°F to 95°F (10° C to 35°C).
4.3.3 Continuous Inspection: Continuous special 5.8. Anchors shall be installed in dry or damp (water-
inspection is required shall be provided in accordance with saturated) holes with dry or saturated concrete. Holes shall
2012 IBC Section 202, 2009 IBC Sections 1704.4 and be free of any standing water.
1704.15 or 2006 IBC Sections 1704.4 and 1704.13 and this
report for all cases where anchors installed horizontally or 5.9. Sika AnchorFix®-2 adhesive anchors are recognized
upwardly inclined and are designed to resist sustained for use to resist short and long-term loads, including wind
tension loads. The special inspector shall observe all and earthquake (Seismic Design Categories A and B only),
aspects of the anchor installation except holes shall be subject to the conditions of this report.
permitted to be drilled in the absence of the special
inspector provided the special inspector examines the drill 5.10. Anchors shall be limited to installation in structures
bits used for the drilling and verifies the hole sizes. The assigned to Seismic Design Category A or B only.
special inspector shall verify the items listed in Section
4.3.1 of this report. 5.11. Strength Design values shall be established in
accordance with Section 4.1.1 of this report. Loads applied
5.0 LIMITATIONS to the anchors shall be adjusted in accordance with Section
1605.2 of the IBC for strength design.
Sika AnchorFix - 2 Adhesive Anchoring System described
in this report complies with the codes specifically listed in 5.12. Allowable Stress Design shall be established in
Section 1.1 of this report, subject to the following accordance with Section 4.1.2 of this report. Loads applied
conditions: to the anchors shall be adjusted in accordance with Section
1605.3 of the IBC.
5.1 Sika AnchorFix®-2 adhesive anchors shall be installed
in accordance with the manufacturer’s pirnted installation 5.13 Use of zinc-plated carbon steel anchors or threaded
instructions included (MPII) in the adhesive packaging and rods is limited to dry, interior locations. Exterior anchor
shown in Figures 5a and 5b of this report. locations and water saturated conditions require the use of
hot-dipped galvanized carbon steel or stainless steel
5.2. Prior to installation, calculations and details anchors or threaded rods. The coating weights for zinc-
demonstrating compliance with this report shall be coated steel shall be in accordance with ASTM A153 Class
submitted to the code official for review and approval. C or D.
Page 5 of 19
Number: 327
Originally Issued: 12/13/2013 Revised: 12/22/2015 Valid Through: 12/31/2016
5.14. Minimum anchor spacing and edge distance, critical 6.0 SUBSTANTIATING DATA
edge distance, critical spacing, and minimum member
thickness shall comply with the values described in this Testing and analysis data in conformance with ICC-ES
report. Acceptance Criteria for Post-Installed Adhesive Anchors in
Concrete Elements, AC308 approved June 2015. Test
5.15. Where not otherwise prohibited in the code, Sika results are from laboratories accredited in accordance with
AnchorFix®-2 adhesive anchors are permitted for use with ISO/IEC 17025.
fire-resistance-rated construction provided that at least one
of the following conditions is fulfilled: 7.0 IDENTIFICATION
i. Anchors are used to resist wind or seismic loads The adhesive material packaging shall be marked with a
only. permanent label bearing the name and address of the
manufacturers, the model number, IAPMO UES Mark of
ii. Anchors that support fire-resistance rated Conformity, evaluation report number (ER-327), lot
construction or gravity load bearing structural number, packing date and shelf life or expiration date, and
elements are within a fire resistance-rated envelope or name or logo of the inspection agency (IAPMO R&T) to
a fire resistance-rated membrane, are protected by identify the products listed in this report.
approved fire-resistance rated materials, or have been
evaluated for resistance to fire exposure in accordance
with recognized standards.
5.17 Sika AnchorFix®-2 adhesive anchors may be used for Brian Gerber, P.E., S.E.
floor (downwardly inclined orientation), wall (horizontally Vice President, Technical Operations
inclined orientation), and ceiling (upwardly inclined Uniform Evaluation Service
orientation) applications. Upwardly inclined orientation
applications are limited to use with the ⅜-, ½-, and ⅝-inch-
diameter (9.5, 12.7, and 15.9, 19.1 mm) threaded rods.
5.18. Since a criteria for evaluating data to determine the Richard Beck, PE, CBO, MCP
performance of adhesive anchors subjected to fatigue or Vice President, Uniform Evaluation Service
shock loading is unavailable at this time, the use of these
anchors under such conditions is beyond the scope of this
report. GP Russ Chaney
CEO, The IAPMO Group
5.19. Periodic special inspection shall be provided in
accordance with Section 4.3.2 of this report. Continuous
special inspection for overhead installations (vertical up)
that are designed to resist sustained tension loads shall be For additional information about this evaluation report please visit
provided in accordance with Section 4.3.3 of this report. www.uniform-es.org or email at info@uniform-es.org
Page 6 of 19
Number: 327
Originally Issued: 12/13/2013 Revised: 12/22/2015 Valid Through: 12/31/2016
C
X
CIC/300/EASF X X
CIC/850/EASF X
Base Material 32°F < T ≤ 50°F 50°F < T ≤ 68°F 68°F < T ≤ 77°F 77°F < T ≤ 86°F 86°F < T ≤ 95°F
Temperature1 (0°C < T ≤ 10°C) (10°C < T ≤ 20°C) (20°C < T ≤ 25°C) (25°C < T ≤ 30°C) (30°C < T ≤ 35°C)
Processing Time 4 min 4 min 3 min 2 min 1 min
Page 7 of 19
Number: 327
Originally Issued: 12/13/2013 Revised: 12/22/2015 Valid Through: 12/31/2016
Minimum
Minimum Minimum
Specified futa Minimum Specification for
Threaded Rod Specified Percent
Ultimate ― Percent Nuts and
Specification Units Yield Reduction of
Strength, fya Elongation Washers
Strength, fya Area
fu,ta
ASTM F1554
psi 58,000 36,000 ASTM A563
Grade 36 1.61 23 40
(MPa) (400) (250) Grade A
(A 307 Gr.C)1
Page 8 of 19
Number: 327
Originally Issued: 12/13/2013 Revised: 12/22/2015 Valid Through: 12/31/2016
Strength
reduction factor ϕ - 0.75
for tension3
Strength
reduction factor ϕ - 0.65
for shear3
Nominal strength Nsa lb 3,144 4,650 8,514 13,560 20,070
as governed by
steel strength Vsa lb 1,886 2,790 5,108 8,136 12,042
ASTM A307
Grade A
Strength
reduction factor ϕ - 0.75
for tension2
Strength
reduction factor ϕ - 0.65
for shear33
Nominal strength Nsa lb 6,550 9,688 17,738 28,250 41,813
as governed by
steel strength Vsa lb 3,930 5,813 10,643 16,950 25,088
ASTM 193
Grade B7
Strength
reduction factor ϕ - 0.75
for tension2
Strength
reduction factor ϕ - 0.65
for shear3
Nominal strength Nsa lb 5,240 7,750 14,190 22,600 28,433
as governed by
ASTM F593, CW
steel strength
Strength
reduction factor ϕ - 0.65
for tension2
Strength
reduction factor ϕ - 0.60
for shear3
For SI: 1 inch = 25.4 mm, 1 in2 = 645 mm2, 1 lb. = 4.448 N
1
Values provided for common rod material types are based on specified strength and calculated in accordance with ACI 318 Eq. (D-3) and
Eq. (D-20). Nuts and washers shall be appropriate for the rod as set forth in Table 4 of this report.
Page 9 of 19
Number: 327
Originally Issued: 12/13/2013 Revised: 12/22/2015 Valid Through: 12/31/2016
2
Effective Area is minimum area applicable for either tension or shear.
3
Tabulated value of ø complies with ACI D.4.3 and applies when load combinations of IBC Section 16.5.2 or ACI 318 Section 9.2 as set
forth in ACI 318 D.4.3. If the load combinations of ACI 318 Appendix C are used, the value of shall be determined in accordance with ACI
318 D.4.4.
Table 6 – STEEL DESIGN INFORMATION FOR METRIC THREADED ROD1
Nominal Rod Diameter
Design Information Symbol Units
M8 M10 M12 M16 M20
Rod outside diameter d
mm 8 10 12 16 20
in. 0.31 0.39 0.47 0.63 0.79
Rod effective cross- mm2 36.6 58.0 84.3 157 245
Ase
sectional area2 in2. 0.057 0.090 0.131 0.243 0.380
Nominal kN 16.90 25.00 45.78 72.91 107.90
Nsa
strength as lb 3,800 5,620 10,291 16,390 24,258
ISO 898-1 Class 5.8
Strength
reduction factor ϕ - 0.65
for tension3
Strength
reduction factor ϕ - 0.60
for shear3
Nominal kN 27.05 40.00 73.24 116.65 172.65
Nsa
strength as lb 6,080 8,992 16,465 26,223 38,813
ISO 3506-1 Class A4-80
Strength
reduction factor ϕ - 0.65
for tension3
Strength
reduction factor ϕ - 0.60
for shear3
1
Values provided for common rod material types are based on specified strength and calculated in accordance with ACI 318 Eq.
(D-3) and Eq. (D-29). Nuts and washers shall be appropriate for the rod as set forth in Table 4 of this report.
2
Effective Area is minimum area applicable for either tension or shear.
3
Tabulated value of ø complies with ACI D.4.3 and applies when load combinations of IBC Section 16.5.2 or ACI 318 Section 9.2 as
set forth in ACI 318 D.4.3. If the load combinations of ACI 318 Appendix C are used, the value of shall be determined in
accordance with ACI 318 D.4.4.
Page 10 of 19
Number: 327
Originally Issued: 12/13/2013 Revised: 12/22/2015 Valid Through: 12/31/2016
Table 7 – CONCRETE BREAKOUT DESIGN INFORMATION
Page 11 of 19
Number: 327
Originally Issued: 12/13/2013 Revised: 12/22/2015 Valid Through: 12/31/2016
Page 12 of 19
Number: 327
Originally Issued: 12/13/2013 Revised: 12/22/2015 Valid Through: 12/31/2016
Temperature Characteristic Bond Tk,uncr psi 1,404 1,337 1,270 1,135 1,000
Category A1 Strength in uncracked MPa 9.68 9.22 8.75 7.83 6.90
Concrete2
Anchor Category - - Anchor Category 2
Page 13 of 19
Number: 327
Originally Issued: 12/13/2013 Revised: 12/22/2015 Valid Through: 12/31/2016
Figure 1a: Standard threaded rod with flat tip end
Figure 1b: Standard threaded rod with one side 45° chamfer
Figure 1c: Standard threaded rod with two side 45° chamfer
Page 14 of 19
Number: 327
Originally Issued: 12/13/2013 Revised: 12/22/2015 Valid Through: 12/31/2016
Figure 2: Allowable Dispenser Tools
Dispenser C- Cox 41004-2T Dispenser D - Cox 41002
FIGURE 3: Sika Anchor Fix®-2 Adhesive Anchoring System
Page 15 of 19
Number: 327
Originally Issued: 12/13/2013 Revised: 12/22/2015 Valid Through: 12/31/2016
Page 16 of 19
Number: 327
Originally Issued: 12/13/2013 Revised: 12/22/2015 Valid Through: 12/31/2016
Page 17 of 19
Number: 327
Originally Issued: 12/13/2013 Revised: 12/22/2015 Valid Through: 12/31/2016
Table 10 – ADHESIVE ANCHOR ALLOWABLE STRESS DESIGN (ASD) TENSION VALUES FOR
ILLUSTRATIVE PURPOSES
Nominal anchor Drill bit diameter, d0 (in.) Effective embedment Allowable tension load,
diameter (in.) depth, hef (in.) φ Nn/α
(lbf)
5/16 3/8 2-3/8 828
3/8 7/16 2-3/8 946
1/2 9/16 2-3/4 1,388
5/8 11/16 3-1/8 1,762
3/4 13/16 3-1/2 2,920
Illustrative Procedure:
¾” Sika AnchorFix®-2 Adhesive Anchor (ASTM A193, Grade B7 Threaded Rod) with an Effective Embedment, hef = 3½”
Step 1: Calculate Static Steel Strength in Tension per ACI 318-11 Section D.5.1 = φsaNsa = 0.75 x 41,813 = 31,360 lbs
Step 2: Calculate Static Concrete Breakout Strength in Tension per ACI 318-11 Section D.5.2 = φcbNcb = 0.55 x 7,857 = 4,321 lbs
Step 3: Calculate Static Pullout Strength in Tension per ACI 318-11 Section D.5.3 = φpNa = 0.55 x 8,247 = 4,535 lbs.
Step 4: The controlling value (from steps 1 -3 above) per ACI 318-11 Section D4.1.2 = 4,321 lbs.
Step 5: Divide the controlling value by the conversion factor α as determined above: Tallowable,ASD = 4,321 / 1.48 = 2,920 lbs
Page 18 of 19
Number: 327
Originally Issued: 12/13/2013 Revised: 12/22/2015 Valid Through: 12/31/2016
Page 19 of 19