ROBINSONS LAND CORPORATION

CORPORATE PROJECT ENGINEERING DEPARTMENT

Schedule of Loads

Current (Amperes) Size of Wire


Item Description Power(Watts) CB Rating Size of Conduit
AN BN CN ABC (THHN,Phelps Dodge Brand)
1 Tenant A 9,139.2 13.19 40AT,3P 4 - 8.0mm² + 1 - 3.5mm² 32mmØ
2 Tenant B 9,139.2 13.19 40AT,3P 4 - 8.0mm² + 1 - 3.5mm² 32mmØ
3 Tenant C 9,139.2 13.19 40AT,3P 4 - 8.0mm² + 1 - 3.5mm² 32mmØ
4 Tenant D 9,139.2 13.19 40AT,3P 4 - 8.0mm² + 1 - 3.5mm² 32mmØ
5 3 - 400W Floodlight 1,245 5.41 20AT,1P 2 - 5.5mm² 20mmØ
6 SPARE 1,150 5 20AT,1P
7 28 - 2x18W CFL + 6 - 1x40W LB MH 2,178 9.46 20AT,1P 2 - 5.5mm² 15mmØ
8 SPARE 1,150 5 20AT,1P
9 25 - 2x18W CFL + 6 - 1x40W LB MH + 2-200W exhaust 2,380 10.34 20AT,1P 2 - 5.5mm² 15mmØ
TOTAL 10.41 14.46 10.34 52.76

Itotal = [(3x14.46x230)/(1.732x380)] + 52.76 `


Itotal = 67.91 Amperes

Feederline: 4 - 38mm² + 8.0mm² THHN wire, Phelps Dodge Brand in 40mmØ IMC pipe
Main Circuit Breaker: 100AT, 3P, 480V Squre D Brand