Steam Trap Check List: # Locations Conditions Bypass VV Trap Operation
Steam Trap Check List: # Locations Conditions Bypass VV Trap Operation
HP Steam
IP Steam
LP Steam
Conditions
# Locations
Bypass vv Trap Operation
1 South of RTT-1 P F
2 South of Tower-3 (Cal-1 FT U/S) N/A P
3 South of Tower-3 (Cal-1 FT D/S) P F
4 HP Trap # 34 FMC-3 North P OK
5 Cal-4 HP DB-10 P OK
6 HP 38 N/A F
7 65 ktpa tank farm East DBO P F
8 SC-7 Suction Knock Out East Leaky OK
9 Cal-4 expansion tank west NO NO
10 Cal-4 expansion tank west NO NO
11 DA-2,3 east - south acid tank drain N/A P
1 Ammonia slop tank, NH3 jacket N/A P
2 MCT-1 west N/A F
3 NH3 evaporator P F
4 NH3 evaporator south P F
5 DBO Vessel 3 North N/A F
6 D-3 North N/A F
7 D-3 Flash Vessel North 1 N/A F
8 D-3 Flash Vessel North 2 N/A F
9 MCT-2 west N/A P
10 Abs-1 south N/A NO
11 D-4 south ammonia jacket N/A F,P
12 D-4 south ammonia jacket N/A NO
13 T-8 east N/A NO
14 T-9 North N/A NO
15 T-11 North 1 N/A NO
16 T-11 Nort 2 N/A NO
17 T-12 North N/A NO
18 RTT-3 West N/A NO
19 Room 418 South N/A NO
20 IP Cal-3 expansion tank out NO NO
21 Cal-3 IP line near BB compressors N/A NO
1 FMC-1 west side N/A F
2 D-1 south side N/A F
3 Exp tank-1 north side N/A F
10 FMC-4 south NO NO
11 RTT-3 west NO NO
12 Nizam Din Lute NO NO
Legends: P-Passing, F-Faulty, NO- Not operative, N/A- Not Applicable
Remarks
Attended
Belongs to Plant C
Checked, found OK.
Checked, found OK.
Attended. Trap replaced
Attended. Trap replaced
Attended. Trap cleaned
Attended. Leakage from pipe attended
Attended. Trap cleaned
Attended. Trap repaired
Trap not perpendicular to floor, but working OK.
Attended. Trap replaced
Attended. Trap repaired
Attended. Trap repaired
Attended. Trap cleaned
Attended. Trap repaired
Attended. Trap cleaned
Attended. Trap cleaned
Attended. Trap cleaned
Checked, found OK.
Attended
Attended
Checked, found OK.
Line is blocked from header. Can be unblocked only in
total shutdown
Attended. Trap cleaned
Attended. Trap cleaned
Belongs to Power Services
Belongs to Power Services
Valve next to header is damaged. Can be replaced only
in total shutdown
Belongs to Power Services