Migration module must be used as data access point for R-30iA as I/O Device.
In R-30iA setup screen for PN-IO device : for firmware V2.3.1, enter 0 to “Slot”, 1 to “Subslot”, 13 to “Module ID”, 65537 to
“SubslotID” to define the following module (13 = 0xD, 65535 = 0x10001).
Data access point (Migration) Slot = 0 Subslot = 1
Module ID = 0x0D, subslot ID = 0x10001
Then, setup the next slots as per wishes (IN, OUT, IN-OUT)(1byte, 4bytes, 16bytes). Use Module-ID & Submodule-ID as found
in GSDML. Keep in mind : if, in GSDML you take “IN”, on device you will see “OUT” (and vice-versa).
Now - at startup, “mismatch” error is posted by R-30iA, for device, slot 0 (the DAP).
Because : NCM downloaded V2.1 ID’s; but we had to set initially V2.3 ID’s [i.e.:13 = 0xD to “Module ID”][65537 = 0x10001
to “SubslotID”], in R-30iA device setup screen, in order to have the R-30iA internal database operational.
Set now manually (in slot 0 / subslot 1) the V2.1 ID’s (i.e.: module-ID = 0x5, submodule-ID = 0x1) – and system works.