Buchholz Relay
Buchholz Relay type eBR

COMEM’s eBR is equipped with a digital


interface for easy connection to the
smart grid and it can be integrated into
a single system via a central control unit.
The eBR can work in standalone mode
or integrated into a single system, which
is compatible with the most common
international communication protocol
standards. COMEM’s eBR provides improved
monitoring of the gas inside the Buchholz
relay and the oil flow speed.

eBR
The continuous gas monitoring of the gas inside the Buchholz relay
allows you to know the gas accumulation level at any time.

The new eBR Electronic Buchholz Relay noticeably improves


the performances, reliability and safety of your transformer. The
reed based standard electro-mechanical features, an electronic
transducer and a dedicated PCB allow you to constantly monitor
the gas accumulation in the Buchholz relay by 4-20mA analog
output or MODBUS RTU protocol. The double flow vanes ensure
the detection of two thresholds of oil flow speed. In particular,
an alarm and a trip signal are independently generated at two
different values of oil flow (e.g. alarm at 1.5m/s and trip at
3m/s).
A based on the use of dedicated reed contacts for the detection
of the oil flow thresholds provides the possibility to immediately
and remotely identify the trip causes (oil flow or oil leakage/gas
accumulation) by means of 4-20mA analog output or MODBUS
RTU protocol. Allows you to remotely control an electrical
contact on the PCB in such a way to command the opening of
valve for the gas discharge.

2
Buchholz Relay testing equipment

Construction Advantages
The new COMEM Buchholz relay with analog and digital output • Continuous gas monitoring of the gas inside the Buchholz
is an assembly of high strength components which ensures a a relay;
perfect oil seal. • Settable alarm and trip thresholds for the oil flow speed;
The main body of the relay is fitted with tempered glass • Double oil flow threshold (alarm and trip);
inspection windows with graduated scale markings in cubic • Thanks to the dedicated and independent contacts for
centimeters to indicate the internal volume. The oil drain plug is both floats and flow vane, in case of failure, there is a clear
located at the bottom of the main body. identification of the main cause;
The top cover hold the frame which contains the moving parts • Contact output for the gas discharge valve opening;
of the relay. The two floats and their associated reed switches • Analog Output and Digital Control.
reed and magnets, two calibrated flow valves.
The cover also: Special features
• A gas discharge valve with G1/8” in male thread with protective Thanks to the constant monitoring you can check in every time
cap the volume of gas collected by the Buchholz relay.
• A valve for pneumatically testing the alarm and insulation By checking the gas accumulation trend.
circuits, with protective cap
• A push rod for mechanical verification of the reed switch with
protective cap
• A terminal box

3
Buchholz Relay type eBR

Flow vane functioning principle If the flow speed increases, but it does not reach the preset
Thanks to the double flow vane design, COMEM eBR have both tripping value, there is an ALARM (V1<V<V2). This patent
alarm and tripping function on oil flow speed monitoring. pending special warning is important in order to prevent
transformer.
During normal operation, the flow speed (V) through the pipe In case of failure the flow speed suddenly increase towards the
towards the conservator is lower than the alarm value (V<V1). conservator activating the tripping switch (V>V2).

1st position: 2nd position: 3rd position:


normal operating conditions alarm conditions trip conditions

Routine tests
High quality and strong performances are ensured by rigorous Diectric contact voltage as specified in the following table:
production control.
The following Routine Tests are carried out on all the relays. Short term Resistance
• Hydraulic seal test in mineral oil at 90 deg C and 100 kpa industrial frequency voltage
pressure for 30 minutes; leakage test per pulse
• Contact operation via mechanical push rod; kV/1 min. (r.m.s.) kV (peak)
• Contact operation by means of; Between circuits and ground 2.5 5
• Rates of oil flow to trip/alarm the contacts;
Across open contacts 1 3
• Electrical withstand test between contacts (as table);
• Electrical withstand test between contacts and (as table);
• Analog output verification;
• Modbus RTU communication verification;
• Pet-cock contact verification.
An individual routine Test Report is shipped with each relay.

4
Overall dimensions eBR

Type
1
eBR-802 3 4 5 6 7 8

-
A A

-
THE MECHANISM FROM THE BODY
MINIMUM CLEARANCE TO REMOVE

B B
328
406

45°

45°
C C

Ø18
22.5°

AGGIUNTA VISTA CON FLANGIA 8 FORI


Ø138

Added view with 8 holes flange

NUOVA EMISSIONE
D D

195
Ø80 Ø80

Issued
Ø160 Ø160
Ø200 Ø200

0
Modifiche
Alterations

E E
Materiale
Material ---
Rives. / Tratt.
Protec. / Treat. --
Dimensioni <=3
>3 >6 >30 >120 >400 >1000 >2000
Dimensions <=6 <=30 <=120 <=400 <=1000 <=2000 <=4000
207

Valori
General Tolerances
Tolleranze Generali

0.05 0.1 0.15 0.2 0.3 0.5 Angolari


30'
0.1 0.2 0.3 0.5 0.8 1.2 2 Angular
Dimensioni in mm Peso Grezzo Peso Netto
Dimensions in mm
Values Gross. Wt. Net. Wt.
0.2 0.3 0.5 0.8 1.2 2 3 4

Scala: Proprietà della COMEM. Senza autorizzazione scritta dalla stessa il presente disegno non potrà essere utilizzato per la costruzione
Scale:
NO dell'oggetto rappresentato né venire comunicato a terzi o riprodotto. La società proprietaria tutela i propri diritti a norma di legge.
All property rights of COMEM. This drawing must not be reproduced in any medium nor utilized for the manufacture of the article
F herein rapresented or disclosed to other parties without our licence. Any infringement will be legally persecuted. F
Data: Riferimenti: Sost.: Disegn.: Contr.:
Date: 07-03-2013 References: AF 546/08 Replaced: NR-341 Operat.: Tonin A. Chkd.: Investigazione 01 2+
Descrizione Description Codice - Part Number Dis. Drwg.

RELE' ELETTRONICO
eBR TAGLIA 80
- NR-341-01
1 2 3 4 5 6 7 8

5
Wiring terminals

Electronic board
- Supply voltage:
24V D.C. +/-10% polarized
POWER RS 485 ANALOG ELECTRO-MECHANICAL
- Power consumption: 0.5W SUPPLY OUTPUT GROUND OUTPUT MICRO SWITCHES

- Analog output signal 4-20mA 1 2 3 4 41 42 11 14 21 24 31 34 32 44

- Digital output RS 485

+ - B A + - LEVEL LEVEL FLOW VANE FLOW VANE


24V DC 4÷20 mA TRIP ALARM TRIP ALARM

The standard possible configurations are:

Scheme Alarm Trip Alarm Trip Analog MODBUS Petcock


level level Speed Speed output RTU control
4-20mA
F NO NO NO NO Available Available On demand
K NO NC NO NO Available Available On demand
Q NC NO NO NO Available Available On demand
R NC NC NO NO Available Available On demand
S NO CO NO NO Available Available On demand
W CO NO NO NO Available Available On demand
X NC CO NO NO Available Available On demand
U CO NC NO NO Available Available On demand
Z CO CO NO NO Available Available On demand

Terminal and electronical board NO: normal open contact; NC: normal close contact; CO: change over contact

6
Order sheet

Number of pieces

Size and Model BR80 BS80

F R X

Electrical contact layout


(see specification at page 4) K S U

Q W Z

NBR HNBR VITON


Seal
-40°C

Alarm: 1.0m/s 1.5m/s 2.0m/s

Flow speed

Trip: 1.0m/s 1.5m/s 2.0m/s 2.5.0m/s 3.0m/s

Contact supply 24/48V AC/DC 110/220V AC/DC

7
Strada Regionale 11, Signolo 22 Due to technical product updates, the information
contained in this catalogue may be subject to change
36054 Montebello Vicentino (VI) - ITALY without notice.
Tel. +39 0444 449311
© Copyright 2013 COMEM.
Fax +39 0444 449352 - 440359 All rights reserved.
E-mail: comem@comem.com
Ed. 05/2013
www.comem.com

You might also like