Professional Documents
Culture Documents
OEM User Manual: Integrated Control Solutions & Energy Savings
OEM User Manual: Integrated Control Solutions & Energy Savings
NO POWER
& SIGNAL
CABLES
TOGETHER
READ CAREFULLY IN THE TEXT!
All of the above suggestions likewise apply to the controllers, serial boards,
programming keys or any other accessory in the CAREL product portfolio.
CAREL adopts a policy of continual development. Consequently, CAREL
reserves the right to make changes and improvements to any product
described in this document without prior warning.
The technical specifications shown in the manual may be changed without
prior warning.
The liability of CAREL in relation to its products is specified in the CAREL general
contract conditions, available on the website www.carel.com and/or by
specific agreements with customers; specifically, to the extent where allowed
by applicable legislation, in no case will CAREL, its employees or subsidiaries
be liable for any lost earnings or sales, losses of data and information, costs of
replacement goods or services, damage to things or people, downtime or any
direct, indirect, incidental, actual, punitive, exemplary, special or consequential
damage of any kind whatsoever, whether contractual, extra-contractual or
due to negligence, or any other liabilities deriving from the installation, use or
impossibility to use the product, even if CAREL or its subsidiaries are warned
of the possibility of such damage.
1. INTRODUCTION 7
1.1 Main specifications ......................................................................................... 7
1.2 Components and accessories ...................................................................... 7
2. INSTALLATION 8
2.1 Main board: connector’s description .......................................................... 8
2.2 Inverter 10A Single-pahse ............................................................................. 9
2.3 12-16 A single-phase inverter, three-phase 18-24 A.............................. 10
2.4 Single-pole E2V valves for R744 ................................................................ 11
2.5 Pressure probes (SPKT00**8C0) .............................................................. 11
2.6 Temperature probe....................................................................................... 11
2.7 Wiring connection......................................................................................... 12
2.8 Functional diagrams ..................................................................................... 13
2.9 Installation ...................................................................................................... 15
3. USER INTERFACE 16
3.1 Graphic terminal ........................................................................................... 16
3.2 Description of the display ........................................................................... 16
4. MENU DESCRIPTION 17
4.1 Main menu ......................................................................................................17
5. COMMISSIONING 18
5.1 Guided commissioning procedure ........................................................... 18
6. FUNCTIONS 19
6.1 Unit ON/OFF.................................................................................................. 19
6.2 BLDC compressor ......................................................................................... 19
6.3 Compressor control ......................................................................................22
6.4 Compressor managment on LT units (DSS and independent)..........23
6.5 Fans ..................................................................................................................24
6.6 Oil management ...........................................................................................25
6.7 HPV valve management ..............................................................................26
6.8 RPRV valve management ............................................................................28
6.9 Generic functions ..........................................................................................29
7. FAST COMMISSIONING 30
7.1 MPXPRO configuration (SW version 4.0) .........................................30
7.2 Ultracella configuration (SW version 2.0) .........................................32
7.3 Ultra EVD EVO module commissioning .................................................. 37
7.4 Connecting MPXPRO/Ultracella to Hecu .................................................38
7.5 MPXPRO/Ultracella control ......................................................................39
9. SOFTWARE UPDATE 44
9.1 Uploading/updating the software (Upload) ...........................................44
Supervisor
Fig. 1.a
24Vdc
Rated values
PTC
NO
C
1 2 3 4 5 6 7
The table below shows the rated input and output values, as well as the
specifications for sizing the cables (cross-section, maximum length) and
the fuses. The values refer to an operating temperature of 60 °C and a
switching frequency of 8 kHz, unless otherwise specified.
PSD10102BA
Fig. 2.b Rated input current at 230V 17 A
Fuse or type B circuit breaker 25 A
Power cable cross-section 4 mm2
Description of the terminals: Rated output current 10 A
Ref. Description Rated output power at 230V 3,8 kW
L, N Max. total dissipation 270 W
Single-phase power supply input Max. heatsink dissipation 150 W
earth (*)
U, V, W Minimum motor cable cross-section 2,5 mm2
Motor output Maximum motor cable length 5m
earth (*)
-DC Tab. 2.e
DC bus output
+DC
J1-1 C
J1-2 NO
DC bus output Dimensions
J2-3 0V
J2-4 Tx/Rx+ RS485/ModBus®connection
J2-5 Tx/Rx-
87,1
J3-6 PTC
J3-7 24 Vdc PTC input (black connector)
E PE
POWER (green) drive powered 4,8
6
F (Led) RUN/FAULT (green/red) drive running / drive alarm
78
DATA (yellow) communication active
Tab. 2.c 102,8 39,3
(*) The earth connections inside the drive are electrically connected together and to PE.
138
4,8 88
6,9
Important: before carrying out any maintenance work,
disconnect the drive and the external control circuits from the power
40,9
supply by moving the main system switch to “off ”. Once power has been 7,5
Ø5
209,5
M5
177,6
70
65,7
Technical specifications
Operating temperature -20T60°C
55,8
Humidity <95% U.R. non-condensing
Pollution degree Max 2
Input voltage 200 - 240V ± 10%, 50 - 60Hz, 1~ 12,6 113,4 4
86
Safe Torque Off digital input (**)
10 STOb
E PE
POWER (green) drive powered
12
82
F (Led) RUN/FAULT (green/red) drive running / drive alarm
DATA (yellow) communication active
131
(*) The earth connections inside the drive are electrically connected together and to PE.
(**) To enable the drive for operation, apply a voltage of 24 Vac/Vdc to the Safe
24,6
26 27,9
Torque Off digital input. The polarity is indifferent for direct current power supply.
M5
60
Technical specifications
289,2
190
268
240
70,8
Maximum length 5m
Switching frequency 4, 6, 8 kHz 80
Drive: short-circuit, overcurrent, ground fault, over- 192,3
voltage and undervoltage, overtemperature
Protection functions Motor: overtemperature and overload (150% Inom Fig. 2.e
for 1 minute)
System: Safe Torque OFF input, loss of communication
Frequency resolution 0,1 Hz
1 motor protector input: PTC temp. probe or
Inputs voltage-free contact max source current 10mA, max.
length 25 m
Outputs 1 relay: progr. output, voltage-free contact: 240Vac, 1A
RS485, Modbus® protocol, max trasmission speed
Serial input
19200 bit/s
24 Vdc auxiliary power Double insulation, precision 10%, 50mA max
Maximum length 100m shielded cable
Index of protection IP20
Tab. 2.f
CE conformity:
2006/95/EC
EN 61800-5-1: Adjustable speed electrical power drive systems. Safety requiremen-
ts. Electrical, thermal and energy.
2004/108/EC
EN 61800-3, ed.2.0.: Adjustable speed electrical power drive systems. EMC require-
ments and specific test methods.
EN61000-3-2: Electromagnetic compatibility (EMC) Part 3-2: Limits for harmonic
currents (equipment connected with input current > 16 A per phase).
EN61000-3-12: Electromagnetic compatibility (EMC) Part 3-12: Limits - Limits for harmo-
nic currents (equipment connected with input current > 16 A and <= 75 A per phase).
44.0
Ø 16 43.0
A
G
ØF Out
C
ØF In
D
G
ØE In
ØE Out
Type valve A B C D E F G
E2V**CS1C* 125.8mm (4.95 inch) 82.3 mm (3.24inch) 52.3 mm (2.06 inch) 53.3 mm (2.10 inch) Int.13/ Est.18 mm Int.13/ Est.18 mm 10 mm (0.39 inch)
(in 0.51 out 0.71 inch) (in 0.51 out 0.71 inch)
PE -DC
L +DC
L1/L L2/N L3 U V W GND + - N GND + -
U V W
1 2 3 4 5 6 7 8 9 10 K 1 2 3 4 5 6 7
K PTC Klixon
PE
High press
HP switch switch
M Fuse or M
MCB
Fuse or
MCB
3 PTC Klixon 3
L N L N
PAY ATTENTION 2
TO THE POWER SUPPLY! 1
ON OFF
Vout
HECU configuration RX-/TX-
Power supply G J9 RX+/TX+
DIP2=OFF
- for ECU70*: 230 Vac 50/60 Hz, +10%/-15%;
G0
DIP1=ON
J10 GND
- for ECU80*: 24 Vac +10%/-15% 50/60 Hz, J1 RX-/TX-
28 to 36 Vdc +10%/-15%; J11 RX+/TX+
GND boss
Analog Input
RS485 serial card
to connect J12 HPV valve
U1 supervisory system
Suction temp. probe (CAREL NTC) U2 RX-/TX-
J2
U3
J13 J14 RX+/TX+
GND GND
U4
Discharge temp. probe (CAREL NTC-HT) U5
+Vdc J3
+5VR N01
Gas cooler temp. probe (CAREL NTC)
GND J16 NC1 Alarm
pGDe Terminal pLD PRO
C1
White U6
White U7 Out2
Suction press. probe (*) J17 C2
Black +Vdc J4
Black +5VR Out3
Green GND J18 C2
Gas cooler press. probe (*) U8 Out4
U9 J19 C2 L N
White U10
Black +Vdc J5 J20
Out5
C2
Receiver press. probe (*) +5VR
C2
Digital Output
GND
J21 V-IN (POWERED)
GND
0...10 Vdc Fan N06 Fan 1
(A01) Y1
J6 J22 C6
(A02) Y2
Analog Output (0-10V) (A03) Y3 N07
J23
DI1
J8 C7
Fig. 2.g
(*) The 4-20 mA pressure probes are connected as follows: white to Ux and black to +Vdc, green not used
(**) 230 Vac SSR output, maximum switchable power 15VA
Important: Class A software: the safety devices providing overload and high pressure protection must control the compressor directly, and
consequently need to be wired in series with compressor contactor control signal.
HPV
By-pass
T Technology
P GC
Check OUT, GT
valve
T DIS
L1: PAR
2
T SUC
P SUC
HPV P REC
By-pass 2
Technology
P REC Check 35 barg
valve
RPRV
35 barg P DIS
T DIS
T SUC
P SUC
By-pass
Technology
L2: LT
up to 5 T SUC
P SUC
2
up to 5
Fig. 2.h
11
Supervisory
system
C1 C1
C2 C2
PE
L1/L L2/N L3 U V W
1 2 3 4 5 6 7 8 9 10
max 5 units
Fieldbus - Modbus® RS485
RX+/TX+
RX+/TX+
RX-/TX-
RX-/TX-
GND
GND
Vout
MPXPRO MPXPRO
J9
J11
J12
J14
ON OFF
J16
J17
J18
J19
J20
J21
J22
J23
J24
J10
2
1
High High
voltage voltage
J13
master master
RPRV valve
AUX AUX
12 13 14 15
J8
J2
J3
J4
J5
J6
J7
J1
Fig. 2.j
Important:
• A possible short circuit on the Fieldbus serial line will compromise
operation of the system compressor.
• As there is no software control on the connected device (MPXpro,
Ultracella), make sure during configuration to set these correctly,
based on the physical address selected on the evaporator controller.
Note: The serial connection starts from terminal J10 on Hecu CO2 and
Tipo
AC/A/F runs through the power+ inverter and all the MPXPRO controllers installed
IΔn≥300 mA S on the refrigerated units. The maximum number of MPXPRO controllers is 5,
the limit for this application. The following recommendations must be
heeded:
• connect the two twisted wires to the Tx/Rx+ and Tx/Rx- terminals;
NO • connect the single wire to the GND terminal;
Tipo Tipo • connect the shield to earth at one end only;
AC/A/F B/B+ • use a shielded cable (e.g. Belden 3106A – AWG 22);
kHz
IΔn≤100 mA IΔn≥30 mA • For supervisor serial network connection only: connect a 120 Ω
terminating resistor between the Tx/Rx+ and Tx/Rx- terminals on the
last controller in the network (the one furthest away from Hecu).
Tab. 3.b
3
The mask identifier uniquely identifies the menu branch and the
mask: the first characters indicate the menu branch, while the last two
Main mask alphanumeric digits identify the order of the mask inside the menu, for
The software on board Hecu CO2 automatically returns to the main mask example mask Bab01 is the first mask in menu B.a.b.
5 minutes after the last button was pressed. An example of the main
mask is shown in the figure, highlighting the fields and icons used.
1
2
3 4
5
Fig. 3.a
1 Time and date
2 Main values.
3 Unit status (unit off ) or compressor and fan status (unit on)
4 Active alarm signal and manual operation
5
Access further information masks (menu branch A.a) by pressing ENTER .
Note:
• The information shown on the main mask varies according to the
system configuration and the type of control value used (pressure,
temperature).
I.Info
a.Pre-configuration not available
b.Wizard
c.Advanced config. not available
L.Setup d.Default
Screen Lb92: indicates the type of fans, either ON-OFF, PWM or 0-10V
modulating.
Screen Lb96 Lb97: indicates the type of control and the working set
point and differential for the fans.
Screen Lb04: indicates the type of modulating device associated with
the compressor selected on the previous mask.
Screen Lb99: indicates the type of valve are installed in CO2 management
unit and type
Screen Lb05: indicates the model of BLDC compressor and the serial
address of the power+ inverter (always=1). This is used to understand
whether the inverter is on and connected via serial with Hecu.
Screen Lb3a: indicates the end of the wizard procedure. Press ENTER
to terminate the procedure, and start system configuration using the
chosen settings.
Screen Lb11: indicates whether the connected model of inverter is
compatible and if so automatically downloads some typical compressor
parameters to the inverter. The parameters can also be written manually
by selecting “Yes” for Write default.
On-off from the digital input is equivalent to an enabling signal, that is, if
the digital input is Off the unit cannot be switched on in any other way,
while if it is On, the unit can be switched on or off in any other way, with
the same priority (the most recent has precedence, whatever the origin),
as shown in the figure:
Digital Input
User interface Select YES for Set defaults and press ENTER.
If the model of power+ (as read by power+) is the same model or larger
Supervisor
than the power+ selected based on the type of BLDC compressor, the
default values can be written and Hecu CO2 can control the compressor.
Unit On/Off Otherwise, the message “Not compatible” will be shown.
Fig. 6.a
Note: certain special conditions or functions in the Hecu CO2 Envelope management
software cause the unit to shutdown: Hecu CO2 defines the compressor working zone in the software based
• Configuration of some parameters: e.g. inputs/outputs, configuration on the following measurements:
of compressors, inverter parameters. • Discharge pressure
• Installation of default parameters • Evaporation pressure
• Manual management • Discharge temperature
and compares these with compressor envelope.
The controller manages the demand for capacity sent to the inverter,
in a controlled manner in order to maintain the compressor operating
conditions within the limits of pressure and temperature defined by the
6.2 BLDC compressor manufacturer (zone 1a-1b). The actions to keep the compressor within
One BLDC compressor controlled via Power+ inverter can be selected. the operating zone specified by the manufacturer are:
The type of compressor is chosen in Compressors Configuration • Decrease in acceleration or deceleration, when compressor operation
(Caf15). approaches the limits, until holding the speed when operation is at
the limit.
The BLDC compressor is managed via Modbus and works only if • Speed reduction when operation is beyond the high condensing
connected to a CAREL power+ inverter. If there is no communication pressure or high compression ratio limits, so as to return within the
with the inverter, the compressor will not be able to operate. permitted operating zone.
Below is a list of currently available compressors: When compressor operation remains too long in a zone outside of the
envelope, an alarm is generated (mask Cag55, default 60sec). The zone
Medium and Low temperature (R744) number and description is shown on the alarm mask.
Compressor HPV RPRV Inverter Capacity During start-up, when the compressor operates at a fixed speed for the
unipolar stator E2VSTA0310 Tevap. = -10°C minimum ON time, this alarm is disabled.
TGC = 32°C
TOSHIBA DY30 E2V09CS1C0 E2V11CS1C0 PSD101021A 0,3...2,8 kW
TOSHIBA DY45 E2V11CS1C0 E2V14CS1C0 PSD1012200 0,5...4,2 kW The discharge temperature alarm is always active.
TOSHIBA DY67 E2V14CS1C0 E2V18CS1C0 PSD1016200 0,7...6,3 kW
TOSHIBA RY100 E2V18CS1C0 E2V24CS1C0 PSD1018400 1,0...8,8 kW
Tab. 6.a
Note: go to ksa.carel.com to check the updated list of compressors
available, with reference to "DC compressor availability table" code
+050001835.
Condensing pressure
1b
9 5
6
1a
Evaporation pressure
Fig. 6.b
Start-up
Hecu CO2 manages compressor start-up in the best way possible,
adapting operating speed so as to guarantee that the desired conditions
and excellent lubrication are reached very quickly.
For this reason, when starting the compressor is operated at a settable
fixed speed (Cag52) for the minimum ON time, Fig. 6.c. During this stage,
the out-of-envelope alarm is disabled, but speed control remains active
if approaching or exceeding zone 2 (maximum compression ratio), 3
(maximum condensing pressure) or 4 (current limit). When the pressure differential is below 1 barg – 0.5 barg (fixed value), the
The corresponding parameters are in loop: Compressors Advanced compressor is ready to start.
masks Cag52:
Equalisation
Hecu CO2 allows the pressure across the compressor to be equalised,
simplifying condensing unit start-up. The equalisation mode can be selected
on screen Caf18: either “DELTA PRESSURE” or “TIME”.
rps
Start-up
speed min ON min rps
time
time
Fig. 6.c
Comp
ON
OFF
Regulation request
100%
energy efficiency
Regulation P+I
variable
P Min Set point
time
Setpoint Fig. 6.g
time Proportional + integral control will be used to reach the floating set point,
Fig. 6.f based on parameters that can be set on mask Cab14. The following table
shows the recommended parameters for PI control of the condensing
The integral action depends on time and the deviation from the set point.
unit:
The integral time represents how fast integral control is implemented:
• Low values bring fast actions yet more instability PI K PSP: prop. gain barg 12.0
• High values bring slower actions and more stability Press reg Ti PSI: integral time sec 50
The values should not be set too low, to avoid system instability.
Par. start for high The parallel compressor is forced on in the event of high
rec. pressure: pressure in the receiver even if the LT compressor is switched
off due to no request or alarms (default threshold: 60 barg,
When DSS1 is enabled, the following parameters are hidden on screen Fib04: settable).
• Switch on period: 180s (hidden). During this period, the parallel compressor Env. lim. for LT High pressure prevention based on the LT compressor en-
high dis. velope. Sets the condensing/discharge pressure limit at the
request is forced to 50% to allow it to be started;
pressure: selected value, recommended threshold 45 barg (settable).
• Timeout: 180s (hidden). The LT compressor waits for the parallel compressor When the LT compressor discharge pressure exceeds the set
to start, however is switched on in any case after the set timeout has threshold, the controller begins to reduce compressor speed
elapsed; in order to return to normal operating conditions (i.e. inside
• Force off line 2 if line 1 is off: YES (hidden). The LT compressor (L2) is switched the envelope). If the discharge pressure remains above the
off when the parallel compressor (L1) is switched off. set threshold, the compressor can be switched off due to the
envelope alarm (after the standard timeout for the envelope
When DSS1 is NOT enabled, the following parameters can be modified alarm). Threshold=0 barg function not active.
on screen Fib04: LT cut-off thr. If Cut-off due to LT compressor high pressure. The function is acti-
par. can’t start: vated when the parallel compressor is off due to timing or alarms
(default 50 barg, settable).
Tab. 6.b
• Switch on period: 0-999s (def 180, this is the time that the parallel
compressor request is forced to 50% to allow it to start);
• Timeout: 0-999s (def. 180s; this is the time that the LT compressor waits for
the parallel compressor to start, after the set timeout it is switched on in
any case);
• Force off line 2 if line 1 is off: NO/YES.
• YES forces the LT compressor off if the parallel compressor cannot
start.
• NO forces the LT compressor off if there is an alarm on the parallel
compressor
Fig. 6.j
Cut-off
Hecu CO2 manages a cut-off control function for the fans; the function
can be enabled and the related parameters set in main menu branch
D.a.b/D.b.b. The operating principle of the cut-off function is shown in
the figure:
6.5 Fans
Regulation
Hecu CO2 can manage up to two fans with a speed modulation device, request Max capacity = 100%
which may be an inverter or a PWM phase control device. In the same was Max
output value
as for the compressors, fan control can be proportional or proportional
plus integral, based on pressure or temperature.
Cut-Off value
of request
Fan operation with modulating device
If the fans are controlled by a modulating device, the meaning of the Cut-Off Set point Regulation Set point
Regulation
parameters that associate the minimum and maximum values of the Differential Differential probe value
device’s modulating output and the minimum and maximum capacity
of the modulating device on masks Dag02 and Dbg02 is illustrated in the
Fig. 6.k
following examples.
A percentage of the control request and a cut-off set point can be set.
Example 1: minimum modulating output value 0 V, maximum value 10 V,
When the control request reaches the set cut-off value, this value is kept
minimum modulating device capacity 0 %, maximum value 100 %.
constant until the control value falls below the cut-off set point, after
which it falls to 0 % and remains there until the request exceeds the cut-
Analog output
Max capacity = 100%
off value again.
Max output
value = 10 V
Speed up
Hecu CO2 can manage the fast start function (speed up), used to
Min capacity = 0% overcome the initial inertia of the fans. The function can be enabled and
Min output the related parameters set in main menu branch D.a.g/D.b.g.
value = 0 V
If speed up is enabled, a start time can be set in which the fan speed
Set point
Regulation is forced to 100%. If the outside temperature sensor is used, moreover,
Differential Differential probe value
a threshold can be set (with reset differential) below which speed up is
Fig. 6.h disabled, so as to not drastically lower the condensing pressure at start-up.
Floating
Min output setpoint
value = 0 V Min capacity = 60%
Max
Set point
Regulation
Differential Differential probe value
offset
Fig. 6.i
Min
time
external temperature
Fig. 6.l
advanced 3
standard
oil separator
1 oil separator
(double oil level)
V
BLDC
BLDC compressor
compressor
EEV valve
Fig. 6.a
standard
oil separator
V
BLDC
Min open. valve compressor
Compressor
Speed (lps)
EEV valve
Min Speed Max speed
t
EEV Max opening
EEV position
t
Cabinet SH
Cabinet SH
setpoint OK
t
ON
C1 Washing
OFF
t
ON
C2 Washing
OFF
t
ON
C3 Washing
OFF
t
t1 t2 t1 t2 t1 t2
td td td
rps
Speed Force Legende:
Comp. Speed
Thr diff. t1= time ON t2= time OFF td= Fixing time function
Fig. 6.p
Speed Thr
Washing of individual cabinets can be configured exclusively as sequential
mode.
t
Fig. 6.o
C INTERMEDIATE ZONE
• Maximum percentage variation: the movement of the valve cannot
SUBCRITICAL ZONE exceed the maximum set percentage variation per second.
T₁₀₀%
Tmin
at the limit of the transcritical and subcritical zones. The purpose of this
zone is to avoid discontinuity in passing between the two zones.
• Upper proportional zone, defined by Pmax< Pgc< P100%: the valve works
with only proportional regulation between the opening value reached
at pressure Pmax and the maximum opening value at pressure P100%. If
the pressure decreases, the opening value of the HPV valve remains
constant until it enters the transcritical zone, in which the regulation Pmin Prec min
restarts as previously described.
• Lower proportional zone, defined by T100%< Tgc< Tmin: the valve works Fig. 6.r
with only proportional regulation between the opening value reached
at temperature Tmin and the maximum opening value at temperature On the other hand, if the pressure in the receiver goes above the
T100%. If the pressure increases, the opening value of the HPV valve maximum work pressure set, the dynamic calculated setpoint for the HPV
remains constant until it enters the subcritical zone, in which the valve can be changed in order to decrease the pressure in the receiver.
regulation restarts as previously described. It is possible to disable An offset in proportion to the distance from the maximum threshold is
operation according to this mode by parameter. added to the calculated setpoint so that the lesser opening of the HPV
valve contributes to decreasing the pressure in the receiver.
Calculation of the customized setpoint (custom) The offset is directly proportional to the distance from the maximum
The customized calculation differs from the optimized control due to work threshold, as illustrated in the figure:
the fact that the curve in the subcritical phase is rectilinear and defined
by the user, therefore the definition of the bands and the calculation of Setpoint HPV
the setpoint can be customized by the user. Behaviour in the remaining
bands is as described for the optimized algorithm.
OFFS
HPV valve accessory functions
HPV valve management includes some accessory functions:
• Pre-positioning: entering the unit ON status, the HPV valve remains at
a fixed position that can be set by a parameter for a fixed time, which
is also settable by a parameter, in order to be able to quickly raise the PREC PREC max
pressure in the tank. This procedure is reactivated whenever the unit
goes into the OFF status or the HPV valve moves into the minimum Fig. 6.s
position due to all of the compressors being turned off (optional).
Reverse stage
Loading the Carel default values
The values pre-defined by Carel can be loaded at any time, restoring the
Hecu CO2 default settings, and therefore repeating the start-up procedure
Regulation described previously.
Diff. Diff. variable
Setpoint
Important: the procedure for resetting the Carel default values
Fig. 6.t involves clearing the permanent memory on the Hecu, therefore the
If a variable has been set to enable the function, the output connected to operation is irreversible.
the stage will be active when the enabling variable is active.
For each stage, there is a high alarm threshold and a low alarm threshold, Note: to repeat the wizard procedure, first restore the Carel default
both absolute values. For each alarm, the activation delay and priority can values.
be configured.
Power Supply
AC 115-230 V N
Warning: Before making any operation on
200 mA max L
the control board, turn off the supply mains
L N AUX4 AUX3 AUX1 AUX2
turning off the main switch of the
( ( ( ( ( ( electrical panel.
PWM2 PWM1 12 V
R= 20 mA max totally
AC 115-230 V Expansion board: 470 Ω
MPX PRO
T.U.I. M.S.N.
S1 S2 S3 GND S4/DI1 S5/DI2 S6/DI3 GND S7/DI4 5Vdc DI5 GND VL Tx/Rx Tx/Rx GND Tx/Rx+ Tx/Rx-
Supervisor
RS485
Shield
IR*U* IR*X*
tLAN
AUX AUX
Superheated gas
Probe (tgs)
Saturated evaporation
Pressure/temperature
Probe (peu/teu)
Power Supply
Supply
Power
Rx/Tx
GND
Gnd
Rx/Tx
GND
1 2 3
Supervisor
RS485 CAREL
ExV
Shield
Rx/Tx+
Rx/Tx-
GND
GND
GND
bianco/white
VL
verde/green
48 47 46 45 44 43 30 B3 CAREL NTC, PT1000
31 29 B2 CAREL NTC, PT1000
marrone/brown
32 28 B1 CAREL NTC, PT1000 giallo/yellow
FieldBus BMS 33 27 Y1 analog output (0 to 10 Vdc, PWM)
34 26 B4 CAREL NTC, analog input 0 to 10 Vdc
49 50 51 52 53 54 35 25 B5
36
GND
Rx/Tx-
Rx/Tx+
GND
Rx/Tx-
Rx/Tx+
38 22 + Vdc +V
39 21 DI1 DI1 (**) 24 Vac
40 20 DI2
41 19 DI3
42 Door switch 25 VA
2 AT
COMA
NOA
G0 1 3 2 4
VBAT
G
18
24 Vac
17
UltraCella Control 16
R6
R5 - R6 15
EN60730-1 12 (10) A
250 V 14
UL 873 12 A res. 2HP
12FLA 72 LRA
R5
13
DEF EVD Module
12 cod. WM00ENNI00
FAN
11
R3 - R4 R4
10 A res. 10
EN60730-1 5 (3) A LIGHT
250 V 9
UL 873 10 A res. 5FLA R3
18 LRA 8
R2
7
VREF
GND
R1 - R2
DI1
DI2
S1
S2
S3
S4
2
1
230 V
20 A max NTC
Fig. 7.r
Once the wiring has been completed, simply follow the wizard that is
displayed when the Ultracella devices are switched on for the first time.
Details of this procedure are shown below; for further information see the
Ultracella manual + 0300083EN.
+
H M
E E
L
P
Multifunction menu N
U
ESC
PRG SET
ESC
HACCP
UltraCella
with LED display
UltraCella Service terminal Fig. 7.w
2. To enter programming mode: Press Prg and enter the password: 1234
Fig. 7.s H M
E E
L Parameters Categ. 1/16 N
If the UltraCella controller has never been configured, as soon as the P U
Fig. 7.x
3. Press DOWN until reaching the “Wizard” menu
2
1
H M
E E
L Parameters Categ. 16/16 N
P U
First start - up
H M
E E
When starting for the first time, once the Service Tool is connected, the L
P Wizard N
U
wizard is shown automatically. Select the desired language and then Do you want to use the
answer the questions to set the other parameters. PRG Wizard to configure
SET
the cold room ?
YES
H M ESC
E E
L Wizard N
P U
For probe B4, if configured as a 0 to 10 V input (/P4=2) and for probe B5,
Probes configuration the logical control values corresponding to the physical end scale values
The UltraCella controls have a maximum of 5 analog inputs, of which can be configured.
3 can be configured as temperature probes (NTC probes, NTC high
temperature probes, PT1000), the fourth as temperature probe or input 0 Par. Description Def Min Max U.M.
... 10 V, the fifth can be configured as input 4 ... 20 mA or 0...5 Vrat. /4L Probe 4 minimum value (only for 0...10V 0 -50,0 /4H -
input)
Analogue Inputs Type /4H Probe 4 maximum value (only for 0...10V 100,0 /4L 200,0 -
B1 NTC10 kΩ a 25°C, range -50T90°C, input)
B2 NTC extended range, NTC50 kΩ a 25°C, range 0T150°C; /5L Probe 5 minimum value 0 -50,0 /5H -
B3 PT1000, 1000 Ω a 0°C, range -50T90°C /5H Probe 5 maximum value 100,0 /5L 999 -
B4 NTC10 kΩ a 25°C, range -50T90°C,
NTC extended range, NTC50 kΩ a 25°C, range 0T150°C
Example: if input B5 is connected to a pressure sensor with 4 to 20 mA
0…10 V
B5 4…20 mA output and a range of -1 to 9.3 bars, set
0...5Vrat - /5L = -1.0
0.5...4.5Vrat - /5H = 9.3
Tab. 7.a In this case, when the probe reads a value of 12 mA, the value associated
Below the parameters with the selection. with the reading of B5 will be 4.1 (middle of the scale).
OFF Note:
• if following the start of the defrost, the digital input does not open
ON UNIT 2 before the time dP1 elapses, the defrost will terminate by time and
Defrost alarm Ed1 will be displayed (defrost ended by timeout).
OFF
• opening of the digital input does not start the defrost only if the
UNIT 3 defrost probe (e.g. B2) temperature is greater than dt1 (end defrost
ON
temperature on main evaporator).
Defrost • if a separate defrost is configured on two evaporators (d13=1) and
start/stop defrost from external contact is set, both evaporators are
OFF
defrosted at the same time.
dP(1) dP(2) dP(3) t
17 = Serious alarm
d5(2) Application: external alarm that causes the immediate deactivation of the
d5(3) outputs on UltraCella (except those configured as a light/alarm) so as to
prevent a dangerous situation. This can be used, for example, to stop the
Fig. 7.c compressor following activation of the “Cold room occupied” alarm or to
Key deactivate the heaters if an external protection device is activated.
dP Maximum defrost duration When the alarm is activated:
UNIT 1…3 Unit 1…3
d5 Defrost delay from digital input
• a signal is shown on the display (‘SA’);
t Time • the buzzer is activated, if enabled
• the alarm relay is activated, if selected;
The following actions occur on the actuators:
5 = door switch (see parameter A3) • immediate deactivation of all the outputs (relays), except for those
configured as lights and/or alarms.
6=On/Off remote Note:
The digital input can also be programmed as a remote ON/OFF switch. • if more than one digital input is configured as a serious alarm, the
When the control is set to OFF: alarm is generated when just one of the inputs is open.
• the temperature is displayed alternately with the message “OFF”, the
internal timer relative to the parameter dI is updated. If dI expires when
the unit is OFF, a defrost is performed when the unit is switched on
again; Type of defrost
• the auxiliary relays remain active set as an auxiliary output and light, UltraCella allows you to manage the following types of defrost, depending
the other auxiliary outputs are off ; on parameter d0:
• the buzzer and the alarm relay are off; 0. electric heater defrost by temperature;
• the control does not perform the control functions, defrosts, continuous 1. hot gas defrost by temperature;
cycle, temperature alarm signalling and all the other functions; 2. electric heater defrost by time;
• the compressor protection times are respected. 3 hot gas defrost by time.
At control restart, all functions are reactivated, except: For further explanations please see chap. 6.
• defrost at start-up; Par. Description Def Min Max UoM
• compressor and fan delay at start-up. d0 Type of defrost 0 0 3 -
0 heater by temperature.
Note: The ON/OFF from external digital input has priority over the 1 hot gas by temperature
keypad and the supervisor. 2 heater by time
3 hot gas by time
dt1 End of defrost temperature, main evapo- 4.0 -50.0 200.0 °C/°F
7, 8, 9, 10, 11 = Do not select rator
dP1 Maximum defrost duration 30 1 250 min
12 = Auxiliary output
Setting H1/H5 = 2 the corresponding output AUX1/ AUX2 is activated by
the key AUX1/ AUX2 or from DI if set. In addition, a digital input DI1, DI2
or DI3 (set A11, A5 or A9 = 12) can be used to control AUX1 or AUX2. In
this case the key and the digital input have the same priority as regards
the switch on.
13 = Do not select
Supervisory
4. Download the default parameters
system
C1
C2
C1
C2
Downloading the default parameters involves automatic configuration of
F
max 5 units
• Floating suction pressure set point (Par. 6.3): the default values
Fieldbus - Modbus® RS485
enable compressor control with floating set point on mask Cab01.
RX+/TX+
RX+/TX+
RX-/TX-
RX-/TX-
GND
Vout
MPXPRO MPXPRO
J9
J11
J12
J14
ON OFF
J17
J18
J19
J20
J21
J22
J23
J24
J10
2
1
High High
voltage voltage
J13
master master
RPRV valve
master master
EVDEVO EVDEVO
application selected, together with the proportional gain and integral
time values required by the controller and already shown in paragraph
12 13 14 15
J8
6.3.
J2
J3
J4
J5
J6
J7
J1
Fig. 7.d • Oil Recovery Washing (Par. 6.6): the default values enable the
To subsequently configure the entire system made up of the Hecu evaporator oil recovery washing function on mask Faab15. The
CO2 and MPXPRO/Ultracella controllers, see the Fast Commissioning following parameters manage this function:
procedure described in detail in the following section.
Par. Description Def
tON Washing cycle duration 180sec
tOFF Time between two washing 180min
cycles
Mode Sequential or same time SINGLE CABINET AT TIME
Fast commissioning Fixing time Stabilisation time after washing 120sec
Tab. 7.n
The Fast Commissioning procedure can be accessed from the menu:
Evaporators Configuration mask Eab00/01.
• Evaporator control parameters: the default values enable Smooth
Lines evaporator control and involve the main evaporator control
parameters on masks Eab01, Eab02, Eab03. These values are shown
in the table below:
Fig. 7.ad
Par. Description Def Min Max UOM
P7 LowSH: low superheat threshold 7.0 -10.0 P3 K Key
P8 LowSH: integral time 15.0 0.0 240.0 s
0 = function disabled SH Superheat P7 Low SH protection threshold
P9 LowSH: alarm delay 600 0 999 s LowSH Low superheat protection P9 Alarm delay
0 = alarm disabled ALARM Alarm t time
Tab. 7.p
Differential Pressure
Pressure
Relative threshold
HP by pressostat
Setpoint Alarm
Fig. 8.b
HP by probe
Note: for temperature control, the alarms from probe are managed
based on temperature even when pressure probes are fitted.
The effects of the different pressure alarms from probe are described
below. Prevent
differential
Low suction pressure from probe
The low suction pressure alarm from probe has the effect of stopping all
the compressors without observing the times.
The effect of this prevent-type is force to maximum power all fans and
force the compressor BLDC at the minimum speed.
mode
Meanings of Buttons/Symbols
Flashing: the key is connecting to the pCO. During this phase, which
Fig. 9.a may last a few seconds, the start button is disabled.
start Flashing: The key has detected the pCO and is checking the access
For the operation instruction, see par. 9.1. rights.
On steady: Pressing the start button will start writing the software to
Operating instructions start+ the pCO.
On steady: Pressing the start button will start reading the software
start+ from the pCO.
On steady: Pressing the start button will start reading the logs from
start+ the pCO.
On steady: In case of C or G keys, pressing the button for 1 second
mode
switches from read to write.
start start
Tab. 9.b
mode mode
If the key is type C of G, pressing the “mode” button for 1 second switches
from read to read logs (G only) or to write. The symbols (write to
pCO), (read from pCO), (read logs) reflect the selected status. If
the key is not type “C” or “G”, the “mode” button is disabled and off. The
“start” button starts the read or write operation, indicated by the flashing
of the corresponding symbol ( or ) at a frequency proportional
Fig. 9.b to the progress of the operation. When the operation is completed, the
buzzer will sound intermittently for 2 seconds. Pressing the start button
Programming the Smart Key via Personal Computer again will make the buzzer sound without repeating the operation. To
The operating modes described in the table below can be configured repeat the operation, the key must first be unplugged. In case of error the
using a program on the PC. The program can also load the software to the symbol will light up together with the other LEDs. The following table can
key or transfer logged data from the controller to disk. help you find the cause of the problem.
Type Function Mode button
B Update software from key to pCO (BIOS, Disabled
application, parameters, etc.)
C* Copy software from pCO to pCO (BIOS, Switches the key from write
application, parameters, etc.) mode to read mode
D Read logs Disabled
E Read logged data and software from pCO Disabled
(BIOS, application, parameters, etc.)
F Read logged data Disabled
G Copy from pCO to pCO and read logs Switches the key to write
mode, read mode and read
logs mode
*: Default mode
Tab. 9.a
The key is factory-programmed in read/write mode (type C) so that it can
be used immediately to transfer software from one controller to another.
When the key is connected to the personal computer, the symbols have
the following meanings:
USB
USB
CVSTDUTLF0
Fig. 9.f
power supply
Fig. 9.c
Fig. 9.j
LogEditor: basic concepts
Click on “Salva” [Save] to generate the project’s “.2cw” file.
LogEditor is the module used to configure the log files of pCO devices
(pCO logs). Configuring pCO logs consists in defining a number of sets
Commissioning: basic concepts of variables in which to specify which variables should be logged, the
logging method (by frequency or by event) and the minimum number
of loggings required. Configuration is based on a binary file (.PVT – Public
Note: The following paragraphs are from the online help of pCO Variable Table), which is generated by 1Tool and contains the descriptive
Manager, to which the user is referred for further details. data of the variables that can be logged.
Commissioning is a configuring and real-time monitoring software that All the log configurations so defined are saved in the .LCT (Log
can be used to supervise the performance of an application program Configuration Table) binary file, which must be uploaded to the pCO
installed on a pCO, to start up the pCO and to perform debugging and together with the .PVT file. Log configuration data is also saved in a file
maintenance. With this software the user can set the configuration that can be used only by LogEditor – the .LEF file, which must be saved to
parameters, edit the values of volatile and permanent variables, save on be edited with LogEditor as necessary.
file the trends of the unit’s main quantities, manually manage the unit’s I/O
using simulation files and monitor/reset the alarms of the unit on which LogEditor can be used even when the device is not connected. Once the
the device is installed. files for logging are uploaded to the pCO, the pCO saves the logged data
Work carried out with Commissioning is preceded by configuring the work in the following files:
environment, which is typically done by the project designer. The active • .BIN file containing all the data in binary format;
project in 1Tool is automatically loaded by pCO Manager. • .CSV file containing the same data in a generic format with values
The project designer can use the configuration functions of Commissioning separated by commas;
to decide which variables should be subjected to monitoring, logging, • *_GRAPH.CSV containing the same data to be used for charting
trend-monitoring and event-monitoring, to organize variables into purposes.
categories and to create sets of configuration parameters.
Operators using Commissioning for maintenance will be able to see the
necessary variables and to draw from preset configuration values.
Agenzia / Agency: