Air Handling Unit 1: Total Air Quantity 12800 CFM Duct Velocity 4000 FPM (Recommended)
Air Handling Unit 1: Total Air Quantity 12800 CFM Duct Velocity 4000 FPM (Recommended)
**All data are obtained and calculated from ASHRAE Manual, Friction Chart.
**All data are obtained and calculated from ASHRAE Manual, Friction Chart.
Duct Section Air Quantity CFM Capacity
To A 18600 100%
A-B 13800 74%
B-C 8800 47%
C-D 3800 20%
D-E 3200 17%
A-1 4800 26%
1-2 3200 17%
2-3 1600 9%
B-5 5000 27%
5-6 2500 14%
C-9 5000 27%
9-10 4000 22%
10-11 3200 17%
11-12 1600 9%
D-13 600 3%
E-17 3200 17%
17-18 2000 11%
18-19 800 4%
**All data are obtained and calculated from ASHRAE Manual, Friction Chart.
DIFFUSER SIZING
Computations:
1 ft(2 )
=54.72¿ 2
D=2( 4 ) 78.17 ¿ 2
π
D=9.79∈¿
**All data are obtained and calculated from ASHRAE Manual, Friction Chart.
Use 11.75 in diameter
T – 10 Administration Room:
T – 11 Multimedia Room:
T - 12 Training Room
**All data are obtained and calculated from ASHRAE Manual, Friction Chart.
Use 10 in diameter diffuser
T – 13 AVR
T – 14 Computer Lab
**All data are obtained and calculated from ASHRAE Manual, Friction Chart.
LENGTH OF REDUCERS
Using
Concentric Reducers:
L= ( D −D
1
2 )
2
(7)
Diameter Diameter
Reducer No. Ratio Used: LENGTH TO USE
No.1 No.2
1 28 24.75 7 11.375 11.5
2 24.75 21 7 13.125 13.25
3 21 15.25 7 20.125 20.25
4 15.25 14.25 7 3.5 3.5
6 16.5 14.25 7 7.875 7.9
7 14.25 11 7 11.375 11.5
8 16.75 13 7 13.125 13.25
9 16.75 15.5 7 4.375 4.5
10 15.5 14.25 7 4.375 4.5
**All data are obtained and calculated from ASHRAE Manual, Friction Chart.
11 14.25 11 7 11.375 11.5
12 14.25 12 7 7.875 8
13 12 8.5 7 12.25 12.25
**All data are obtained and calculated from ASHRAE Manual, Friction Chart.