Professional Documents
Culture Documents
Flow Rate Static Balancing Valves For Radiators
Flow Rate Static Balancing Valves For Radiators
The valves for radiators equipped with pre-setting device play a very important role in balancing the heating
systems circuits. In fact they allow, by means of static balancing, to adjust each heating body with the right flow
rate and thus to obtain the right amount of heat. This performance, as further detailed below, can not be obtained
with conventional valves.
STATIC BALANCING
Fixed orifice They are adjusted operating Manual valve with They are adjusted operating
manual valve on a knob that controls the flow meter on a stem that controls a ball
movement of an obturator. obturator.
Piezometric connections The flow rates can be directly
are placed upstream of the checked on the flowmeter
obturator, on a Venturi section. installed on the device.
Therefore, the obturator It is not necessary to calculate
position does not affect the flow the setting position at the
rate determination. design stage.
Manual valve with They are adjusted operating Pre-settable They are adjusted acting on
variable orifice on a knob that controls the radiator valves the locking nut that changes
movement of an obturator. the medium flow cross section,
The piezometric connections creating a "throttle", specifically,
are located upstream and a medium flow resistance.
downstream of the obturator. It is not possible to determine
To determine the flow rate, it is the actual flow rate by acting
necessary to know the obturator directly on the valve.
adjustment position.
Generic secondary circuit
SECONDARY CIRCUIT WITH RADIATORS
RT
Too often mistakenly it is thought that the presence of the thermostatic control head alone Lockshield valve to balance
is sufficient
Balancing valve
the flow rates of the individual terminals, since their operation is to reduce the heat output emitted by the radiator
(and consequently the flow rate), depending on the ambient temperatureSecondary
measured by the
circuit withcontrol. This could be
radiators
true in the only condition of steady-state system, or when the ambient temperatures are close to those set on the
thermostatic control heads: it could be stated that the hydraulic and thermal balancing is automatically obtained
Secondary circuit with radiators
by the action of the thermostatic heads. Secondary circuit withThermostatic
radiators valve
The steady-state operation condition does not occur easily without a proper balancing operation. This is mainly
with pre-setting
due to the transient operation phases of the systems: especially during start-ups, the thermostatic
Thermostatic valve controls
Thermostatic valve
generate the maximum opening of the radiator valves obturator (situation in which the ambient is cold).
with pre-setting
Without
any balancing operation, the typical hydraulic resistance of conventional radiator valves is not sufficient to limit the
circulating flow rates in the radiators in this condition, with the consequent result of generating an unbalancing
phenomenon, commonly known as “hydraulic short circuit”; in essence, there are substantial (and useless)
overflow-rates in the most favoured radiators and lack of flow-rate in the most disadvantaged ones. The steady-
state situation will then be reached in a very long time or, worse, it may also never be reached for some heating
bodies. Lockshield valve
This problem can easily be solved by means of radiator valves with pre-setting, whose purpose is to limit the
maximum opening cross section of the radiator valves to prevent the occurrence of hydraulic short-circuits,
making it possible to achieve the steady-state condition in a short time.
The Kv value is varied by modifying the passage cross section through fixed windows
corresponding to discrete values.
Setting Kv
Position [m3/h]
Pressure drop diagram for pre-setting valve with thermostatic control head
BALANCING OF SECONDARY CIRCUIT WITH RADIATORS
The available head H (10 kPa) is equal to the sum of the load losses KvMAX= of
2,29the radiator valve (ΔP ) and of the
VT
lockshield valve (ΔPDET). Explaining these load losses according to the formula that binds the flow rate, the flow
1800 W
coefficient and the load loss (see box below) it is possible to calculate the G526 flow rate, known the Kv2K (0,57
2K l/h
10 kPa
m3/h) values of the traditional radiator valve with thermostatic control head installed,
+ 410% the Kv (2,42 m3/h) value of
TA
the fully opened lockshield valve.
H = ΔPVT + ΔPDET
Relationship between flow rate, flow coefficient
( )
G2K
( ) G2K
2
4,7and load loss [kPa]
H = 10-4 ⋅ Kv2K + 10-4 ⋅ KvRT G = 100 ⋅ Kv ⋅ √ ΔP G: [l/h]
TRADITIONAL LOCKSHIELD VALVE
(
1 1
) Kv: [m3/h]
-0,5
G2K = 100 ⋅ Kv 2 + Kv 2 ⋅ √H WITHOUT SETTING
ΔP: [kPa]
2K RT
With only thermostatic control head, it is not possible to obtain the design flow rate for 2K design deviation.
Kv = 0,57
2K
1800 W
START-UP PHASE 175 l/h
10 kPa + 70%
The critical condition originates in the transient phase of start-up with cold system when the thermostatic control
head generates the maximum opening of the obturator. In this condition the radiator valve characteristic is equal to
KvMAX = 2,29 m3/h. With this value the circulating flow rate at start-up can be estimated with the same relationship
that binds the flow rate, flow coefficient and load loss (see box above): 0,5 [kPa]
( 1 1
)
-0,5
GMAX = 100 ⋅ Kv 2 + Kv 2 ⋅ √H 5,3
MAX RT
KvMAX= 2,29
GMAX=526 l/h +410% compared to the design flow rate
1800 W
This excess flow rate represents a strong hydraulic 526 l/h
10 kPa + 410%
unbalancing, which clearly highlights the reason
for which the “hydraulic short circuit” problems
described occur and the reason for the need to
intervene on the radiator circuit balancing.
4,7 [kPa]
Start-up phase
Traditional and lockshield valve with setting
Thermostatic radiator valvewith pre-setting and lockshield valve without setting
Through the formula or simply through the graph, the pre-setting position of the valve is obtained: considering the
available head H = 10 kPa (for pre-setting it is reasonable to neglect the load loads of the fully open lockshield
valve) and the design flow rate GPR = 103 l/h, the adjustment position 4 is obtained, closest to the point found.
In this position the valve has a value of Kv2K,(4) = 0,35 m3/h.
Calculation using the formulas Calculation using the graph: Flow rate-ΔP
Dp [kPa]
Setting Kv
Position [m3/h]
G2K = WITHOUT
10 kPa
( 1
2K,(4)
+
100 ⋅ Kv 2 SETTING
175 l/h
1 -0,5
⋅ √ HW
Kv 2TA 1800 ) 10 kPa
LOCKSHIELD VALVE WITHOUT
110 l/h
1800 W
+ 70% + 6%
G2K=110 l/h 9,5
+6% compared to the design flow rate 9,8
Thanks to the balancing carried out with the pre-
Kv2K= 0,57
setting, in the proportional 2K bandwidth design Kv2K= 0,35 POS. 4
0,5 0,2
condition, it is possible to actually obtain[kPa]
1800 W
a flow rate 1800 W
[kPa]
526 l/h
1800 W START-UP PHASE 170
1800 W
10 kPa 0,5 [kPa] 10 kPa 0,2 l/h [kPa]
+ 410% + 64%
During the transient start-up phase, the maximum
opening cross 5,3section is the result of the pre-setting 9,5
position set.
KvMAX= 2,29at the adjustment position 4, the Kv
Therefore, KvMAX= 0,55 POS. 4
MAX (4)
value equal to 4,70,55 m3/h limits the circulating
[kPa] flow 0,5 [kPa]
rate in the radiator to a value 1800 Wto:
equal 1800 W
526 l/h 170 l/h
10 kPa + 410% 10 kPa + 64%
( 1 1
)
-0,5
GMAX = 100 ⋅ + ⋅ √H
Kv 2
MAX,(4)
Kv 2TA
GMAX=170 l/h +64% compared to the design flow rate
4,7 [kPa] 0,5 [kPa]
Thanks to the limitation introduced, the excesses
Dimensioning to 2K
over-flow rates in the most favoured radiators can Valve with pre-setting and lockshield valve without setting
efficiently be eliminated.
The starting phases are therefore shorter and uniform for all the radiators of the systems, which are therefore in
the best condition to effectively reach the steady-state operating condition.
Thermostatic radiator valve and lockshield valve with setting
The balancing operation of heating bodies equipped with conventional valves can be carried out by means of
appropriate setting of the lockshield valve. From a hydraulic point of view, since the lockshield valve represents an
additional load loss in series to the radiator valve, it is possible to adjust its Kv value in order to obtain the desired
flow rate in the design conditions. However, this operation has a series of limitations and disadvantages (see
lockshield valve box already done):
• the lockshield valves do not have graduated scales and therefore the curves refer to the number of revolutions
to be made with a Allen key from the "all closed" position.
• the setting operations are complicated and subject to errors;
• during testing or abnormal operation of the system, the setting operations checks are demanding;
• the setting “memory” is lost during maintenance work.
Obturator
that the lockshield valve 200 2
100 1
must introduce into the 50 0,5
secondary circuit to make it
20 0,2
balanced. 10 0,1
G (l/h)
1000
2000
100
200
500
10
20
50
VALVE WITH PRE-SETTING
Lockshield valve type cross section
TRADITIONAL LOCKSHIELD VALVE
Angled connections lockshield valve elbow (1/2”)
LOCKSHIELD VALVE WITHOUT WITH SETTING
It is necessary first to establish the ΔPDET theoretical
load loss that the lockshield
9,8 valve must generate as 4
the difference between the available head H and the
radiator valve load loss at the GPR design flow rate:
Kv2K= 0,35 POS. 4 Kv2K= 0,57
ΔPDET = H - ΔPV
( )
1800 W 1800 W
G 2
ΔPDET = H - 10 ⋅
10 kPa -4 110PRl/h = 10 - 3,3 = 6,7 kPa 10 kPa 115 l/h
Kv+ 6%
2K
+ 11%
G
number
2K
= 100
of (
With this value, 1the graph
⋅
revolutions
Kv 2K
valve, in this case 1/2,
2 + to
1 is -0,5
Kv 1/2 ⋅ on
be
2 made )
used to search the
√ Hthe lockshield
0,2 which corresponds to a Kv [kPa]
1/2
1/2 turn
G
ΔP
value =115
= H - l/h
ΔP 3+11% compared to the design flow rate
DET of 0,47 Vm /h (value calculated from the graph).
MAX
6
( )
The actual flow rate with
2 2K bandwidth is therefore [kPa]
GPR9,5
ΔP = H - as: Kv 2K = 10 - 3,3 = 6,7 kPa
10 -4
calculated
DET
⋅ Dimensioning to 2K
KvMAX= 0,55 POS. 4 Traditional and lockshield valve with setting
( 1 1
)
-0,5
G2K = 100 ⋅ + ⋅ √H
Kv 22K Kv 21/2 1800 W
170 l/h
GMAX10 kPa l/h +11% compared
=115 + 64% to the design flow rate
For these difficulties and disadvantages, the lockshield valves are often not adjusted but act only as
shut-off valves for maintenance of the radiator.
0,5 [kPa]
0851817GB
WE RESERVE THE RIGHT TO MAKE CHANGES AND IMPROVEMENTS TO THE Caleffi S.p.A. · S.R. 229 n. 25 · 28010 Fontaneto d’Agogna (NO) · Italy
PRODUCTS AND RELATED DATA IN THIS PUBLICATION, AT ANY TIME AND Tel. +39 0322 8491 · Fax +39 0322 863723
WITHOUT PRIOR NOTICE. info@caleffi.com · www.caleffi.com · © Copyright 2017 Caleffi