4 Measurement functions Generator protection with machine differential protection

Measurements P3U10/20 P3U30 P3x3x Measurement Inaccuracy


Specification range

Minimum demand values — ■ ■ ±1 % for range 0.3-1.5xPN, QN, SN


over the last 31 days and 12
±3 % for range 0.1-0.3xPN, QN, SN
months: active, reactive
power

Max and min values: ■ ■ ■ 0.025-50 x IN I ≤ 1.5 x IN: ±0.5 % of value or ±15
currents mA

I > 1.5 x IN ±3 % of value

Max and min values: — ■ ■ 0.005-1.7 x UN ±0.5 % or ±0.3 V


voltages

Max and min values: ■ ■ ■ 16 Hz-75 Hz ±10 mHz


frequency

Max andmin values: active, — ■ ■ ±0.1-1.5 x PN, QN, SN ±1 % for range 0.3-1.5xPN, QN, SN
reactive, apparent power
±3 % for range 0.1-0.3xPN, QN, SN
and power factor
±2° or ±0.02 for PF > 0.5

Harmonic values of phase ■ ■ ■ 2nd-15th


current and THD

Harmonic values of voltage — ■ ■ 2nd-15th


and THD

Voltage sags and swells — ■ ■ 0.005-1.7 x UN ±2° or ±0.02 for PF > 0.5

NOTE: Measurement display's refresh rate is 0.2 s.

4.1 Primary, secondary and per unit scaling


Many measurement values are shown as primary values although the relay is
connected to secondary signals. Some measurement values are shown as
relative values - per unit or percent. Almost all start setting values use relative
scaling.
Table 17 - Phase current and earth fault overcurrent scaling parameters

Parameter Description

CT' primary Primary current value of the CT at I’L side (only


P3x32 relays)

CT' secondary Secondary current value of the CT at I’L side (only


P3x32 relays)

Nominal input (IL side) Rated value of the phase current input. The given
thermal withstand, burden and impedance are
based on this value.

See Table 161 - Measuring circuits on page 349 for


details.

P3G/en M/F006 45