Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

What’s new in the IEEE 43 insulation resistance testing standard?


It has changed from “IEEE Recom-
mended Practice for Testing Insulation T he f irst change in
Resistance of Rotating Machinery” to th e n e w doc u m e nt i s a
“Recommended Practice for Testing
Insulation Resistance of Electric Ma-
slight change in the ti-
chinery.” The reason for the change was tle. It has changed from
to use the more prevalent IEEE term ‘IEEE Recommended
for motors and generators. Significant P r a c t i c e f o r Te s t i n g
changes to clauses of the standard that Insulation Resistance of
affect service center repairs and testing
are described in this article.
Rotating Machiner y’ to
‘Recommended Practice
Polarization index f o r Te s t i n g I n s ul at i o n
A major change in clause 5.4, titled
By Tom Bishop, P.E.
“Polarization index readings,” affects
R e s i s t a n c e of E l e c t r i c
EASA Senior Technical Support Specialist
random winding tests. The relevant Machinery.’ The reason for
text now states, “This test may not ap- the change was to use the
Editor’s Note: PDFs of this article are
available in English and Spanish in the
ply to small random winding machines more prevalent IEEE term
“Resource Library” of www.easa.com.
since the absorption current IA becomes for motors and genera-
negligible in a matter of seconds (see
l l l l l Annex A for further discussion).” In
tors. Significant changes
Annex A, the standard acknowledges to clauses of the standard
The Institute of Electrical and that in random windings, “the absorp- that affect service center
Electronics Engineers (IEEE) standard tion current may decay to nearly zero repairs and testing are de-


for insulation resistance testing of mo- in 2 min–3 min,” still far short of the
tor and generator windings that was scribed in this article.
10-minute duration prescribed for the
published in 2002 has been revised. polarization index (PI) test. The prior
The 2013 edition was published in edition of the standard focused on form Thus the PI test does not apply to
March 2014. coil windings in this clause and did not conventional armatures.
The first change in the new docu- specifically address random windings. Note: The minimum PI value
ment is a slight change in the title. The significance of the change is that it remains 2.0 for windings with an insu-
makes clear that in many lation system thermal rating of class B
Table 1. Temperature correction factors for (130° C) or higher. Similarly, the 5000
thermosetting insulation systems. if not most cases, the PI
test is not applicable to megohm rule remains unchanged.
random windings. There- That is, a winding with an insulation
fore it would not provide resistance value of 5000 megohms does
Temperature °C (°F) Kt useful information, could not need to be PI tested.
create confusion between Temperature correction
10 (50) 0.66 end users and those per- For well over half a century, the
15 (59) 0.71 forming the test, and insulation resistance (IR) versus tem-
would essentially be a perature characteristic given in IEEE
20 (68) 0.76 time-waster if applied. 43 has followed the simple rule that
25 (77) 0.82 Regarding the PI of the IR value doubles for every 10° C
DC machine armature decrease in winding temperature, and
30 (86) 0.88 windings, a sentence conversely that the IR value is halved
in clause 12.2.1 has the
35 (95) 0.94 for every 10° C increase in winding
following statement: temperature. However, clause 6.3 of
40 (104) 1.00 “A polarization index this new edition provides two tem-
test is not applicable
45 (113) 1.24 to DC armatures that
perature correction factors, one of
which has two distinct formulas for the
50 (122) 1.52 have an exposed cop- correction. Windings are now differen-
per commutator that is tiated as being either “thermoplastic”
55 (131) 1.86 by necessity not encap-
60 (140) 2.25 sulated in insulation.” Continued on Page 2

Electrical Apparatus Service Association, Inc. • Copyright © 2016 • www.easa.com • April 2016 1
What’s new in the IEEE 43 insulation resistance testing standard?
Continued From Page 1

or “thermosetting.” Thermoplastic Table 2. Megohms at various temperatures versus 100 megohms at 40° C.
insulation windings are those with
asphaltic systems and other insulation
systems that were used prior to the
Thermosetting Thermoplastic
early 1960s. Thermosetting insula-
tion windings appeared beginning in Temperature Kt Megohms Kt Megohms
the late 1960s and include epoxy and
polyester based systems. 10 0.66 152 0.125 800
U n f o r t u n a t e l y, t h e p r i o r
“10 degree” rule applies to thermo- 15 0.71 141 0.177 566
plastic windings, which are relatively 20 0.76 132 0.250 400
rare since they date back more than
5 decades. The “rule” for the much
25 0.82 122 0.354 283
more prevalent thermosetting insu- 30 0.88 114 0.500 200
lation systems is expressed by two
35 0.94 106 0.707 141
slightly complicated formulas. One
formula covers insulation tempera- 40 1.00 100 1.000 100
tures from 10° C to less than 40° C, 45 1.24 81 1.414 71
and the other formula addresses in-
sulation temperatures from 40° C to 50 1.52 66 2.000 50
less than 85° C. These formulas are 55 1.86 54 2.828 35
given below.
Formula for temperatures from 60 2.25 44 4.000 25
10° C to less than 40° C:
Kt = exp [-1245 {(1/(T+273) - (1/313)}] Kt = factor to multiply T by to obtain tion for this apparent inconsistency is
(Equation 1) insulation resistance corrected to 40° C. provided in a note in IEEE 43 that reads
as follows: “[Equation 2 above] and
Formula for temperatures from Table 1 illustrates the variation in
[Equation 1 above] are approximations
40° C to less than 85° C: the Kt factor versus a range of tempera-
and could lead to significant errors if
tures. Use of the table is a faster and
used to calculate insulation resistance
Kt = exp [-4230 {(1/(T+273) - (1/313)}] simpler process for estimating Kt than
at temperatures outside the range from
(Equation 2) the exact method of using a formula.
10º C to 60º C.”
Note that Table 1 (on Page 3) has
Where: To illustrate the effect of the tem-
a range from 10° C to 60° C, whereas
T = Temperature (degrees C) at which perature correction factor using the new
the range given in the formulas is from
insulation resistance was measured. 10° C to less than 85° C. The explana- Continued on Page 3

Table 3. Minimum insulation resistance values for various windings at 40° C. Differences in values for armatures are highlighted
in blue text.

Minimum insulation Test specimen [2013 edition] Test specimen [2000 edition]
resistance (megohms)
IR1 min = kV + 1 For most windings made before about For most windings made before about
1970, all field windings, and others not 1970, all field windings, and others not
described below described below
IR1 min = 100 For most ac windings built after about For most dc armature and ac windings
1970 (form wound coils) built after about 1970 (form wound
coils)
IR1 min = 5 For most machines with random-wound For most machines with random-
stator coils and form-wound coils rated wound stator coils and form-wound
below 1kV and dc armatures coils rated below 1 kV

Electrical Apparatus Service Association, Inc. • Copyright © 2016 • www.easa.com • April 2016 2
What’s new in the IEEE 43 insulation resistance testing standard?
Continued From Page 2

standard versus the prior version, here ment temperature is 20° C and from (all values in MΩ).” The significant
is an example. The insulation resistance Table 1 (on Page 4) the conversion change in the table is that the minimum
of a winding is 160 megohms with a factor is 0.76. The measured insulation insulation resistance for armatures
winding temperature of 20° C (68° F). resistance of 160 megohms multiplied has changed from 100 megohms to 5
The base temperature for insulation by 0.76 is equal to 122 megohms. Thus megohms. The rationale for the change
resistance is 40° C (104° F). Using the old the insulation resistance corrected to was recognition that the exposed bare
method, we would halve a lower value 40° C is 122 megohms. Note that this copper of the commutator has a lim-
to obtain the IR value at a temperature value is much higher than the result iting effect on insulation resistance,
that is 10° C higher. In this case we need using the old method. Table 2 (on regardless of winding type. Table 3
to do that twice, halving the 20° C value Page 4) illustrates the difference in (on Page 4) provides a comparison of
to obtain the 30° C value, and halving results from each method based on a the IEEE 43 2013 edition and the 2000
the resulting 30° C value to obtain the final result of 100 megohms at 40° C. edition minimum insulation resistance
value at the 40° C base temperature. For more details on temperature values for various winding types. Note
Mathematically we are multiplying ½ correction, see the July 2013 Currents that the levels for minimum insulation
by ½, meaning that we are multiply- article, “Revisiting insulation resis- resistance listed in the first column are
ing the 20° C value by ¼ to obtain the tance temperature correction.” the same for both editions. Also, the
equivalent 40° C value. Thus the 160 changes related to armatures are further
megohm value at 20° C is equivalent to Minimum insulation resistance illustrated by the use of blue text. l
40 megohms (160/4) at 40° C. Included in clause 12.3 is a table
Next, we convert the measurement labeled “Recommended minimum
using the new standard. The measure- insulation resistance values at 40° C

Electrical Apparatus Service Association, Inc. • Copyright © 2016 • www.easa.com • April 2016 3

You might also like