rate (in kg/s) of the refrigerant and calculate the Coefficient of Performance for the chiller
system. Also assume the refrigerant exits the condenser as saturated liquid.
Choosen T inlet,
T = 15.22 ℃ at V = 4 m/s and Q = 4762.46 Watt
T hg
14 258.37
15.22 h1
16 259.46
15.22−14
h1 = 258.37 +
16−14
(259.46-258.37)
= 259.03 kJ/kg
At state 2 in superheated and S1=S2 due to the isentropic compression,
P2 = 800 kPa
Sg hg
0.9183 267.29
0.92421 h2s
0.9480 276.45
0.92421−0.9183
h2s = 267.29 + (276.45-267.29)
0.9480−0.9183
= 269.11 kJ/kg
When isentropic efficiency of the compressor is 88%,
h 2 s−h 1
ŋ=
h 2−h1
269.11−259.03
0.88 =
h 2−259.03
h2 = 270.48 kJ/kg
4.449 kW
COP = = 14.31