APPENDIX

Table A1.1 Results Obtained from VSC- STATCOM Control

Voltage THD% Current THD%


Before During After Before During After
Disturbance Disturbance Disturbance Disturbance Disturbance Disturbance
Bus 7
12.09 19.25 12.25 24.04 13.41 26.23
(STATCOM)
Bus 8
(WECS gen. 12.98 15.45 27.29 24.06 13.41 26.23
Bus)
Bus 12
12.09 19.25 12.25 12.09 19.25 12.25
Load Bus

Table A1.2 Results Obtained from Hex- STATCOM Control

Voltage THD% Current THD%


Before During After Before During After
Disturbance Disturbance Disturbance Disturbance Disturbance Disturbance
Bus 7 (Hex-
7.68 14.14 8.82 15.51 12.58 16.73
STATCOM)
Bus 8
(WECS gen. 7.22 15.54 19.75 15.51 12.58 16.73
Bus)
Bus 12
7.68 14.14 8.82 7.68 14.14 8.82
Load Bus

Table A1.3 Results Obtained from VSC- UPQC Control

Voltage THD% Current THD%


Before During After Before During After
Disturbance Disturbance Disturbance Disturbance Disturbance Disturbance
Bus 7
12.08 19.46 12.02 23.94 17.08 23.01
(UPQC)
Bus 8
(WECS 25.10 24.68 22.98 11.00 17.74 12.92
gen. Bus)
Bus 12
12.08 19.46 12.02 12.08 19.46 12.02
Load Bus
171

Table A1.4 Results Obtained from Hex- UPQC Control

Voltage THD% Current THD%


Before During After Before During After
Disturbance Disturbance Disturbance Disturbance Disturbance Disturbance
Bus 7
(Hex- 7.68 14.02 8.49 15.55 10.06 15.20
UPQC)
Bus 8
(WECS 12.13 7.00 12.74 12.34 14.96 10.63
gen. Bus)
Bus 12
7.68 14.02 8.49 7.68 14.02 8.49
Load Bus

Table A1.5 Results Obtained from VSC- IPQC Control

Voltage THD% Current THD%


Before During After Before During After
Disturbance Disturbance Disturbance Disturbance Disturbance Disturbance
Bus 7
(VSC- 12.57 19.77 12.69 23.81 13.11 25.82
IPQC)
Bus 8
(WECS 13.17 15.80 28.42 23.82 13.11 25.83
gen. Bus)
Bus 12
12.57 19.77 12.69 12.57 19.77 12.69
Load Bus

Bus 6 12.57 19.77 12.69 13.98 21.22 14.20

Bus 9 12.57 19.77 12.69 25.25 21.62 24.91

Bus 10 11.98 19.54 12.02 14.55 10.22 13.86


172

Table A1.6 Results Obtained from Hex –IPQC Control

Voltage THD% Current THD%


Before During After Before During After
Disturbance Disturbance Disturbance Disturbance Disturbance Disturbance
Bus 7
(Hex- 7.38 13.83 8.50 15.64 12.81 16.74
IPQC)
Bus 8
(WECS 7.08 15.36 20.03 15.64 12.81 16.78
gen. Bus)
Bus 12
7.38 13.83 8.50 7.38 13.83 8.50
Load Bus

Bus 6 7.38 13.38 8.50 6.78 12.97 7.89

Bus 9 7.38 13.83 8.50 13.47 7.13 13.34

Bus 10 7.74 13.96 8.42 14.84 15.77 14.38

Table A1.7 Results Obtained from VSC-STATCOM with FLC Algorithm

Voltage THD% Current THD%


Before During After Before During After
Disturbance Disturbance Disturbance Disturbance Disturbance Disturbance
Bus 7
(STATCO 12.09 19.21 12.14 24.05 13.09 26.64
M)
Bus 8
(WECS 12.95 15.73 16.89 24.05 13.10 26.65
gen. Bus)
Bus 12
12.09 19.21 12.14 12.09 19.21 12.14
Load Bus

Table A1.8 Results Obtained from Hex- STATCOM with FLC Algorithm

Voltage THD% Current THD%


Before During After Before During After
Disturbance Disturbance Disturbance Disturbance Disturbance Disturbance
Bus 7 (Hex-
STATCOM)
3.06 7.10 4.41 8.16 6.14 9.32
Bus 8
(WECS gen. 3.11 8.37 9.38 8.14 6.58 8.72
Bus)
Bus 12
3.06 7.54 4.41 6.76 8.73 7.94
Load Bus
173

Table A1.9 Results Obtained from VSC -UPQC with FLC Algorithm

Voltage THD% Current THD%


Before During After Before During After
Disturbance Disturbance Disturbance Disturbance Disturbance Disturbance
Bus 7
12.08 19.47 12.01 23.94 17.08 23.06
(UPQC)
Bus 8
(WECS 25.09 24.65 22.10 10.99 18.04 13.07
gen. Bus)
Bus 12
12.08 19.47 12.01 12.08 19.47 12.01
Load Bus

Table A1.10 Results Obtained from Hex –UPQC with FLC Algorithm

Voltage THD% Current THD%


Before During After Before During After
Disturbance Disturbance Disturbance Disturbance Disturbance Disturbance
Bus 7
(Hex- 4.23 8.99 5.12 7.89 3.28 8.37
UPQC)
Bus 8
(WECS 7.79 3.72 8.03 5.95 6.03 4.95
gen. Bus)
Bus 12
4.68 10.37 3.91 3.14 5.89 3.92
Load Bus

Table A1.11 Results Obtained from VSC-IPQC with FLC Algorithm

Voltage THD% Current THD%


Before During After Before During After
Disturbance Disturbance Disturbance Disturbance Disturbance Disturbance
Bus 7
(VSC- 12.58 19.72 12.53 23.81 12.82 26.22
IPQC)
Bus 8
(WECS 13.16 16.07 16.88 23.82 12.82 26.23
gen. Bus)
Bus 12
12.58 19.72 12.53 12.58 19.72 12.53
Load Bus
Bus 6 12.58 19.72 12.53 13.83 21.03 13.68

Bus 9 12.58 19.72 12.53 25.25 21.63 24.91

Bus 10 11.98 19.52 11.97 14.55 10.22 13.83


174

Table A1.12 Results Obtained from Hex-IPQC with FLC Algorithm

Voltage THD% Current THD%


Before During After Before During After
Disturbance Disturbance Disturbance Disturbance Disturbance Disturbance
Bus 7
(Hex- 9.26 8.66 9.32 8.37 6.19 9.36
IPQC)
Bus 8
(WECS 9.31 7.87 14.97 8.51 6.43 9.41
gen. Bus)
Bus 12
4.73 7.29 4.76 3.93 5.97 3.16
Load Bus
Bus 6 4.27 7.38 4.76 3.24 6.88 3.87

Bus 9 4.89 8.21 4.76 4.1 3.99 6.01

Bus 10 4.47 7.93 5.37 4.02 7.75 7.94

Table A1.13 Results Obtained from VSC- STATCOM with ANFIS Algorithm

Voltage THD% Current THD%


Before During After Before During After
Disturbance Disturbance Disturbance Disturbance Disturbance Disturbance
Bus 7
6.47 3.39 7.38 5.29 6.68 6.19
(STATCOM)
Bus 8
(WECS gen. 6.24 3.09 10.94 5.29 6.68 6.19
Bus)
Bus 12
6.47 3.39 7.38 3.39 3.39 7.38
Load Bus

Table A1.14 Results Obtained from Hex- STATCOM with ANFIS Algorithm

Voltage THD% Current THD%


Before During After Before During After
Disturbance Disturbance Disturbance Disturbance Disturbance Disturbance
Bus 7 (Hex-
0.04 0.05 1.24 0.14 0.14 2.01
STATCOM)
Bus 8
0.76 1.05 6.60 0.14 0.14 2.01
(WECS gen.
Bus)
Bus 12
0.04 0.05 1.24 0.04 0.05 1.24
Load Bus
175

Table A1.15 Results Obtained from VSC -UPQC with ANFIS Algorithm

Voltage THD% Current THD%


Before During After Before During After
Disturbance Disturbance Disturbance Disturbance Disturbance Disturbance
Bus 7
6.47 3.44 7.20 5.32 7.40 5.18
(UPQC)
Bus 8
3.31 6.98 8.12 7.82 3.27 6.05
(WECS
gen. Bus)
Bus 12
6.47 3.44 7.20 6.47 3.44 7.20
Load Bus

Table A1.16 Results Obtained from Hex -UPQC with ANFIS Algorithm

Voltage THD% Current THD%


Before During After Before During After
Disturbance Disturbance Disturbance Disturbance Disturbance Disturbance
Bus 7
(Hex- 0.02 0.03 0.87 0.04 0.17 0.66
UPQC)
Bus 8
0.37 0.54 7.93 0.09 0.15 2.60
(WECS
gen. Bus)
Bus 12
0.02 0.03 0.87 0.02 0.03 0.87
Load Bus

Table A1.17 Results Obtained from VSC- IPQC with ANFIS Algorithm

Voltage THD% Current THD%


Before During After Before During After
Disturbance Disturbance Disturbance Disturbance Disturbance Disturbance
Bus 7
(VSC- 6.27 3.46 7.18 5.33 6.60 6.22
IPQC)
Bus 8
6.01 3.43 10.60 5.33 6.60 6.22
(WECS
gen. Bus)
Bus 12
6.27 3.46 7.18 6.27 3.46 7.18
Load Bus

Bus 6 6.27 3.46 7.18 5.91 3.77 6.85

Bus 9 6.27 3.46 7.18 3.87 7.87 3.93

Bus 10 6.49 3.45 7.05 7.79 4.62 7.46


176

Table A1.18 Results Obtained from Hex –IPQC with ANFIS Algorithm

Voltage THD% Current THD%


Before During After Before During After
Disturbance Disturbance Disturbance Disturbance Disturbance Disturbance
Bus 7
(Hex- 0.18 0.16 0.57 0.29 0.23 0.73
IPQC)
Bus 8
(WECS 1.41 1.73 8.06 0.29 0.23 0.92
gen. Bus)
Bus 12
0.18 0.16 0.27 0.18 0.16 0.27
Load Bus

Bus 6 0.18 0.16 0.34 0.20 0.17 0.55

Bus 9 0.18 0.16 0.34 0.33 0.30 0.36

Bus 10 0.10 0.08 0.67 0.39 0.41 0.59

Figure A1.1 Matlab Simulink Model


177

Bus 7 Voltage THD (VSC Bus 7 Current THD (VSC


Control) Control)

Bus 12 Voltage THD (VSC Bus 12 Current THD (VSC


Control) Control)

Figure A1.2 Voltage and Current THDs – VSC Based Control without
FACTS Devices
178

Bus 7 Voltage THD (HEX Bus 7 Current THD (HEX


Control) Control)

Bus 12 Voltage THD (HEX Bus 12 Current THD (HEX


Control) Control)

Figure A1.3 Voltage and Current THDs – Hexagram Based Control


without FACTS Devices