Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Data sheet

Actuators for three point control


AMV 56K
Description / Application The actuator AMV 56K is used with VK3
valves from DN 15 up to DN 50 diameter.

The actuator automatically adapts its stroke to


valve end positions which reduces
commisioning time. Optional auxiliary
switches and feedback potentiometers are
available.

Main data:
• The advanced design incorporates load
related 'switch-off' to ensure that actuator
and valve are not exposed to overload.
• Digitale feedback end position indication
signal for valve end position is available by
terminal 4 or 5.
• Manual override.
• Low weight and robust

Ordering Type Power supply Code No.


AMV 56K 24 V~ 082H3010
AMV 56K 230 V~ 082H3011

Accessories
(only one potentiometer or additional
switches can be added)
Type Code No.
Potentiometer (10 kOhm/15 mm) 082H7034
Potentiometer (10 kOhm/40 mm) 082H7036
Potentiometer (1 kOhm/40 mm) 082H7039
Additional switches (2x) 082H7037

Technical data Power supply 24 V~, 230 V~


Power consumption 9 VA
Frequency 50 Hz
Control input 3-point
Max. stroke 40 mm
Close of force 1500 N
Speed 4 s/mm
Ambient temperature –15 to +50 °C
Storage and transport temp. –40 to +70 °C
Protection code IP 54
Weight 3.8 kg
- marking EMC Directive 89/336/EEC, 92/31/EEC, 93/68/EEC,
in accordance with EN 50081-1 and EN 50082-1
the standards Low Voltage Directive 73/23/EEC and 93/68/EEC, EN 60730/2/14

SIBC VD.AB.W1.02 © Danfoss 12/02 1


Data sheet Actuators for three point control AMV 56K

Installation
Note that the actuator should be mounted
horizontally at media temperatures over 150 oC.

Lmin=500
Mechanical Electrical
The actuator should be mounted with the Electrical connections can be accessed by
valve stem in either horizontal position or removing the cover. Two Pg11 cable entries
pointing upwards. Use a 4 mm Allen key (not are provided. Both entries are provided with a
supplied) to fit the actuator to the valve body. rubber grommet for use with flexible cable.
Allow for necessary clearance for Note that in order to maintain the enclosure IP
maintenance purposes. rating, appropriate cable glands must be
The valve has position indication rings which used.
should be pushed together before
commissioning; after stroking they indicate
the ends of the stroke.

Disposal The actuator must be dismantled and the


elements sorted into various material groups
before disposal.

Wiring Terminals 2, 3:
Control voltage input from the controller.
Power supply 24 V~, 230 V~ (dependent on
type)

Terminals 4, 5:
Output used for position indication or
230 Vac version: monitoring.
Do not touch anything on
the PCB! Lethal voltage!
Terminal 1
Neutral / common (0 V)

2 VD.AB.W1.02 © Danfoss 12/02 SIBC


Data sheet Actuators for three point control AMV 56K

Wiring - accessories

Two additional switches 2S Potentiometer P

Commissioning Complete the mechanical and electrical


installation and perform the necessary
checks and tests:
- Turn on the power.
- Set the appropriate control signal and
check the valve stem direction is correct for
the application.
The unit is now fully commissioned.

Manual override The manual override is applied by rotating the


4 mm Allen key (not supplied) to the required
position. Observe the direction of the rotation
symbol.

• Disconnect control signals


• Adjust valve position by using a 4 mm
Allen key
• Set valve to closed position
• Restore control signals

Dimensions

Ø 47

SIBC VD.AB.W1.02 © Danfoss 12/02 3