Professional Documents
Culture Documents
Duct Leakage Testing - SUPPLY SYSTEM: Troubleshooting
Duct Leakage Testing - SUPPLY SYSTEM: Troubleshooting
To perform a proper duct leakage test using an ORIFLOW duct leakage tester, perform the following
steps:
1. Use the orifice plate with the recommended leakage range for your job. Use our online
program to help determine which plate(s) you can use with our testers.
2. Make sure you have adequate electrical power for the fan. DO NOT OVERLOAD extension
cords. Make sure you use one with the proper gauge.
3. Cover all outlets with plastic bags and seal with duct tape.
4. Allow all joints and seams that were sealed with duct sealer to cure for at least 24 hours or the
required cure time by the manufacturer, whichever is greater.
5. If possible, position the ORIFLOW duct leakage tester in a location where there will be a
straight path from the orifice tube outlet to the location where you will feed air into the system.
6. Drill a 3/8" diameter hole no closer than two or three feet away from the flexible duct to system
joint.
7. Place the pressure tubing into the previously drilled hole; extend 6 to 12 inches into the duct.
8. Seal the tubing penetration joint with putty or tape.
9. Zero both gauges. Locate adjusting screw on center front of gauge. Use a small slotted
screwdriver. Turning clockwise increases the pressure reading, counter-clockwise decreases
it.
10. Close the fan's inlet damper so the duct system does not get overpressurized by the tester.
11. Turn on the tester blower.
12. Adjust inlet damper until the reading on the gauge marked "Duct System" is at the system
pressure required for performing the leakage test.
13. Once the duct system pressure has been reached and stabilized, note the reading on the
gauge marked "Orifice Tube". This pressure drop reading will correspond to the amount of air
you're feeding into the duct system, which is the amount of air that is leaking out.
14. Refer to the calibration table that came with your test rig. Find the pressure reading and note
the corresponding leakage rate.
Troubleshooting:
If the "Orifice Tube" gauge exceeds the maximum range, the system is probably leaking too much air.
Investigate system for missed outlets or unsealed joints. You can also use a larger orifice or a gauge
with a larger range.
If you cannot obtain any pressure (or very little pressure) with the blower on and the inlet damper wide
open, it could be due to one of the following problems: