Seismic 01 PDF

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

5.

6 Seismic Loads
5.6.1 Base Shear
Based on ASCE/SEI 7-16 Chapters 11 to Chapter 17 - Seismic Load on Buildings and CBC-16
Seismic Design Data:
Site Yokota AFB, Japan
Spectral Response Acceleration Parameter at Short Periods, S s 2.10 Structural Data Tools for UFC 3-301-01
Spectral Response Acceleration Parameter at 1-Second Periods, S 1 0.99 Structural Data Tools for UFC 3-301-01
Risk Category III Table 1.5-1, page 4
Importance Factor, Ie 1.25 Table 1.5-2, page 5
Soil Site Class D Stiff Soil Table 20.3-1, page 204
Seismic Resisting System, Table 12.2-1, page 94 A1 Special reinforced concrete shear walls
Site Coefficients:
Short Period Site Coeffient at 0.20 Second, Fa 1.000 Table 11.4-1, page 84
Long Period Site Coeffient at 1.0 Second, Fv 1.700 Table 11.4-2, page 84
MCER5%Damped Structural Response Acceleration, Short Period, S MS 2.100 FaSS, Eqn. 11.4-1, page 84
MCER5%Damped Structural Response Acceleration, 1 Sec Period, S M1 1.683 FvS1, Eqn. 11.4-2, page 84
Design 5% Damped at Short Period, SDS 1.400 (2/3)SMS, Eqn. 11.4-3, page 84
Design 5% Damped at 1 Second Period, SD1 1.122 (2/3)SM1, Eqn. 11.4-4, page 84
Seismic Design Category:
Based on Short Period, SDS E Table 11.6-1, page 85
Based on 1-Second Period, SD1 E Table 11.6-2, page 85
Use Category, Section 11.6, page 85 E Most Critical of Either Category Case
Approximate Fundamental Period:
Structure Height, hn 12.680 feet , Section 11.2, Table 12.2-1
Structure Type, Section 11.6, page 67 5 All Other Structural Systems
Period Coefficient, CT 0.02 Table 12.8-1, page 109
Period Exponent, x 0.750 Table 12.8-2, page 109
(x)
Approximate Period, Ta 0.134 second, Ta = CThn , Eqn. 12.8-7
Upper Limit Coefficient, Cu 1.400 Table 12.8-1, page 109
Period max., T(max) 0.188 second, CuTa ,Section 12.8.2, page 109
Long-Period Transition Period, TL 8.00 second, USGS Figures. 22-15 to 22-20
Actual Calculated Period, Tc second, From independent analysis
Fundamental Period, T Section 12.8.2, page 90 0.134 second, T = Ta < Tmax, and < Tc
Seismic Loads Coefficient:
Response Modification Coefficient, R 5 Table 12.2-1, pages 90-92
Overstrength Factor, Wo 2.50 Table 12.2-1, pages 90-92
Deflection Amplification Factor, Cd 5.00 Table 12.2-1, pages 90-92
Seismic Response Coefficient, Cs 0.350 SDS / (R / Ie ) , Eqn. 12.8-2 / 12.8-3
Csmax 2.087 T < T, long-period, Eqn. 12.4-3 / 12.8-4
Csmin 0.077 0.044SDSIe > 0.01 , Eqn. 12.8-5
or Csmin 0.124 0.50S1 / (R / Ie), when S1 > 0.60g
Therefore, CS 0.350 CS(min) < CS < CS(max), Par. 12.8.1.1
Redundancy Factor, r 1.30 Section 12.3.4.2
Horizontal Seismic Effect Coefficient, Eh 0.46 rCs , Section 12.4.2.1, Eqn. 12.4-3
Vertical Seismic Effect Coefficient, Ev 0.28 0.2SDS, Section 12.4.2.2, Eqn. 12.4-4a

Note: Seismic Loads Also Auto Computed by ETABS V18

00 Filter Building 95% Preliminary Calculation - May 25 2020 JII / ESI - 6/10/2020