Transmission Line Protection - End To End Testing: Hands On Relay School, March 15, 2018
Transmission Line Protection - End To End Testing: Hands On Relay School, March 15, 2018
Transmission Line Protection - End To End Testing: Hands On Relay School, March 15, 2018
– System Stability
– Thermal Damage
– Protection Limitations
Line Protection without Communication
• Step Distance using impedance (21), definite time delayed (67)
overcurrent, and time overcurrent (51) elements.
Zone 2
Time
Zone 1
Substation B
Substation A
Zone 1
Time
Zone 2
Zone 3
Line Protection without Communication
51G
Time
67G1
Substation B
Substation A
67G1
Time
51G
How to build a Communication
Aided/Based Protection Scheme?
100% High speed clearing - Option 1
• Utilize existing (single end) protection elements
– Impedance/Distance, Phase and/or Ground
– Definite and Time Overcurrent, Phase and/or Ground
– Traveling Wave / Rate of change (dV/dt, dI/dt)
• Assign specific elements to bit(s)/tone(s) and
transmit to the remote terminal
• Use local protection elements, bits/tones
received from the remote end(s), and logic to
either trip or restrain trip with little to no intended
time delay.
Directional Under-reaching Transfer Trip
(DUTT)
• Uses instantaneous elements (e.g. Zone 1, inst
50/67) to send a bit/tone to trip remote
terminal(s) of the line.
Substation A Substation B
Zone 1 DTR
DTT
Inst Overcurrent Trip Breaker
…..
…..
Directional Under-reaching Transfer Trip
(DUTT)
Zone 3
Zone 2
Time
Zone 1
DTR
Substation B
Substation A
DTR
Zone 1
Time
Zone 2
Zone 3
Directional Under-reaching Transfer Trip
(DUTT)
51G
Time
67G1 DTR
Substation B
Substation A
DTR
67G1
Time
51G
Permissive Over-reaching Transfer Trip
(POTT)
• Uses overreaching elements (e.g. Zone 2,
67G2) to send a bit/tone giving permission to the
remote terminal(s) of the line that it may trip if it
too sees a fault.
Substation A Substation B
Zone 2 PTR
PTT
Def Time Overcurrent
Trip Breaker
…..
…..
Permissive Over-reaching Transfer Trip
(POTT)
• Simplified POTT Scheme
Time
Substation B
Substation A
Time
Permissive Over-reaching Transfer Trip
(POTT)
• Simplified POTT Scheme
Time
Substation B
Substation A
Time
Permissive Over-reaching Transfer Trip
(POTT)
• Scheme is enhanced with a reversed element
(Zone 3, 67G3) to block the POTT scheme and
prevent false tripping during a current reversal.
Substation A Substation B
Zone 2 PTR
PTT
Def Time Overcurrent
…..
Trip Breaker
Zone 3 (Reverse)
Zone 3 (Reverse)
Trip Breaker PTR PTT Zone 2
Def Time Overcurrent
…..
Permissive Over-reaching Transfer Trip
(POTT)
• Additional enhancements:
– Echo back
– ‘b’ repeat
Directional Comparison Blocking (DCB)
Substation A Substation B
Zone 2 Zone 2
PU PU
Def Time Overcurrent Def Time Overcurrent
DO DO
…..
…..
Trip Breaker Trip Breaker
Block
Zone 3 (Reverse)
Block Zone 3 (Reverse)
Directional Comparison Blocking (DCB)
Time
Substation B
Substation A
Time
Directional Comparison Blocking (DCB)
Time
Substation B
Substation A
Time
Additional Schemes
• Drive to lockout
– Used to signal to the remote end not to attempt a
reclose
– Avoids reclosing into damaged equipment from the
remote terminal
– Typically used for breaker failure, transformer
terminated lines, or series capacitors
100% High speed clearing - Option 2
• No PTs required
Substation A Substation B
Line Differential
Line Differential
Communication Systems
• Verifies:
– Communication channel and addressing
– Comm Aided/Based Protection Logic
– Engineers protection settings
– Breaker trip and close circuits (if tripping to breaker)
End to End Testing
http://www.nerc.com/files/glossary_of_terms.pdf
Typical Line
Substation A Substation B
Trip Trip
Substation A Substation B
Breaker Breaker
Sim Sim
Trip Trip
• No-op Faults
– Parallel Line fault and clear (current reversal)
– Slow clearing faults on lines “behind” relay
– Tapped loads
• Pay attention to 3 phase PT location
• Reclosing requirements
• Pre-fault
Results – Sequence of Events
Results – Oscillography
What can go wrong?
DC Circuits and Logic
• Comm Circuits
– Transmit / Receive Rolled
– Circuit is looped back in comm equipment
– Circuit was never commissioned
• Wrong equipment
– Multimode vs Single mode fiber
– Fiber optic transceivers
• Addressing
• Bad circuit – Bit error, noise, corrupting data
Questions??
LAB – Initial Wiring
• Power (AC plug)
• AC Input into Relay from Test Set
– 3 Phase Voltage
– 3 Phase Current
• Relay DC Inputs
– Breaker Status
• Relay AC Outputs
– Trip and Close
• Communications
– Fiber - Differential Channel
– Copper RS232 – POTT / DUTT bit channel
LAB – Initial Wiring