Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 7

Relief System Piping

Design Basis

1 of 7
pressure relief device will adversely affect the system
relieving capacity and can cause valve instability. This
CONTENT may also cause rapid opening and closing of the valve (or

1. RELIEF SYSTEM INLET PIPING chattering) which, in return, may cause a decrease in the
relief capacity and damage the seating surfaces.
2. RELIEF SYSTEM DISCHARGE PIPING Vibrations. Vibrations in the inlet piping may cause
leakage at the seat of a pressure relief valve, premature
opening, or premature fatigue failure of certain valve
parts, inlet and outlet piping, or both. Vibration in inlet
Terminology piping to a rupture disk may adversely affect the burst
pressure and life of the rupture disk.
Set Pressure: the inlet pressure at which the relief
device is set to open (burst) 1.1 Inlet Piping
Pressure losses can be reduced materially by rounding
Back Pressure: the static pressure existing at the
outlet of a pressure relief device as a result of the the entrance of the inlet piping, by reducing the inlet line
pressure in the discharge system. It is the sum of
length, or by enlarging the inlet line size. However,
the superimposed and build-up back pressure.
during FEED stage of design, the length may still not be
Built-Up Back Pressure: pressure existing at the
known until the pipe route and equipment location are
outlet of a pressure relief device caused by flow
through that particular device into a discharge established. For the purpose of hydraulic calculation, a
system.
50m straight pipe length may be used.
Superimposed Back Pressure: the static pressure The nominal size of the inlet piping must be same or
existing at the outlet of a pressure relief device at
larger than the nominal size of PSV (Pressure Safety
the time the device is required to operate. It is the
result of pressure in the discharge system from Valve) inlet flange connection.
other sources.
1.2 Relieving Capacity
For sizing the inlet and outlet line of the PSV, the relief
valve’s rated capacity which is based on the actual orifice
Srinivas Valle area should be used instead of the normal capacity (as
Process Engineer
specifield in relief load summary)
L&T-Chiyoda Limited
1.2.1 Single PSV: The design flowrate for single valve
installation is the same throughout the line and is equal to
the rated relief valve capacity.
A selected (Eq’n. 1-1)
WH  W valve x
A required

where: WH = rated relief valve capacity


1. RELIEF SYSTEM INLET PIPING
Wvalve = normal relief valve capacity
Adequate inlet piping for pressure relief valve should be
Aselected = actual orifice area
provided for proper system performance. This requires
Arequired = calculated orifice area
design consideration of the following aspect:
1.2.2 Multiple PSV: In case of multiple valves installation,
Excessive pressure losses. Too much pressure losses in
the flowrate at the lead is equal to the rated relief capacity
the piping system between the protected vessel and a
divided by the number of the PSV excluding spare. In the

2 of 7
case of lateral and subheader, the flowrate is equal to the normal relief capacity.

MAIN HEADER TO FLARE STACK


SUBHEADER

W
Equipment
V

LATERAL
WH / n
LEAD

LEAD
LEAD

WH / n

LATERAL

W
V

PROCESS LINE

Equipment
WH = Rated relief rate ; WV =Normal relief rate

n = working number of PSV (without spare)

Fig. 1-1 Typical Flare System Configuration

3 of 7
pressure. Take note that the fluid properties should be
based on relieving conditions.
1.3 Design Criteria 2. RELIEF SYSTEM DISCHARGE PIPING
In sizing the inlet pipe of a pressure relief valve installed Improper design or construction of the discharge piping

3% Limit PROCESS LINE

3% Limit
Equipment
Equipment

Fig. 1-2A Direct Installation Fig. 1-2B Process Line Installation


on a line directly connected to a vessel, the total non- from a pressure relief device can set up stresses that will
recoverable pressure loss between the protected be transferred to the pressure relief device and its inlet
equipment and the pressure relief valve should not piping. The discharge piping system should be designed
exceed 3 percent of the PSV set pressure. When a to provide proper relief performance of the valve,
pressure relief valve is installed on a process line, the 3 adequate drainage, and give a back pressure that does
percent limit should be applied to the sum of the loss in not exceed an acceptable value for any pressure relief
the normally non-flowing pressure relief valve inlet pipe valve in the system.
and the incremental pressure loss in the process line 2.1 Piping
caused by the flow through the pressure relief valve. In case of an early design stage (FEED stage), when pipe
When a rupture disk is used in combination with a routes and lengths are not yet established, the piping
pressure relief valve, the pressure drop calculation must discharge length may be estimated by considering the
include the additional pressure drop developed by the location of the equipment where the relief valve is
disk. installed. Pipe length from the relief valve directly
Refer to Fig. 2-1 for the profile and relationship of the discharging to the main header may be taken as
pressure at relieving condition and pressure drop at the minimum of 15m. For relief valve discharging to a lateral
inlet and outlet line of the pressure relief device. line and subheader, the length may differ depending on
1.4 Calculation Method the location of the equipment where the relief valve is
For the inlet line sizing calculation, the use of Inhouse installed. It is therefore advisable to use a plot plan for a
hydraulic program (Excel based or Prodraw) is sound pipe length approximation.
recommended. Anchor pressure at the upstream of the
inlet pipe may be fixed at the relief valve’s relieving
P < 0.03PS
Accumulated Pressure:*1
110% of Set Pressure : Single PSV (Non-fire Case)
116% of Set Pressure: Multiple PSV (Non-fire Case)
121% of Set Pressure: Single or Multiple PSV (Fire Case)

Set Pressure for second valve and on multiple PSV


105%
Set Pressure = Equipment Design Pressure
(110% of Maximum Operating Pressure)
100%
(Upstream) (Downstream)

Built-up Pressure < 30% of Set Pressure

Velocity < 0.50 Mach


P < 0.10PS
Back Pressure at Header

*1: Calculate relieving capacity at this condition.

Fig. 2-1 Pressure Profile and Design Constraints for Pressure Relief Valves
2.2 Relief Capacity to verify acceptable back pressure at each pressure relief
In general, laterals and leads from individual devices are device.The isothermal flow equation based on inlet
sized based on the rated relief capacity of the device, pressure is as follows:
which is consistent with the value used to size the inlet
piping. In case of multiple valves, the flowrate at the lead
is equal to the rated relief capacity divided by the number
of the PSV excluding spare and in the case of lateral and
subheader, the flowrate is equal to the normal relief
capacity. ƒ = friction factor L = equivalent length of pipe, in meter
Mw =Molecular weight D = pipe inside diameter, in meter
Main headers, flare headers and flare stacks shall be R = Gas constant A = Area, in square meter
sized for the maximum emergency relief load which is the W = mass flow rate, P = Absolute pressure
maximum unit relief load or simultaneous unit relief loads in Kg/hr 1= pipe inlet ; 2 = pipe exit
that are generated within the plant as a result of a single Note that the relief contingency that sets pressure relief
failure, whichever is greater. valve size does not always result in the maximum
It should be noted that header sizing might not always be pressure drop in the discharge line. This is particularly
governed by the maximum individual relief load. Relief true if contingencies result in the relief of different phases
load from a pressure relief valve that has low back or different molecular weight / specific gravity. Therefore,
pressure may set the size of the header. relief load other than the one which sets pressure relief
2.3 Design Criteria valve size should also be checked for line pressure drop
When discharge piping for pressure relief valves is and back pressure limitation.
designed, the combined effect of the superimposed back When rupture disk are used as sole relieving device and
pressure and built-up back pressure on the operating discharge into a closed system, the effect of the
characteristics of the PSV should be considered. superimposed back pressure on the bursting pressure for
2.3.1 Sonic velocity limitation the disk must be considered.
The lead lines of the relief valve or flaring lines 2.3.3 Noise level limitation
downstream of control valves shall be sized for a The noise level (or sound power level – measured in dB)
maximum velocity of not more than 75% of sonic velocity should also be considered. This criteria may vary
(Mach number = 0.75) under the rated relief load . The according to the type of flare being used in the disposal
main headers and sub-headers shall be sized for a system but for the purpose of a conservative design, 105
maximum velocity of not more than 50% of sonic velocity dB may be considered (for ground flare is 107 dB and
(Mach number = 0.5) under normal relief rate. 117 dB for elevated flare).
2.4 Calculation Method
For a simple and preliminary tailpipe sizing calculation,
2.3.2 Pressure drop limitation the use of Inhouse hydraulic program(Excel based or
The maximum allowable back pressure (MABP) should Prodraw) may be adequate. The pressure at downstream
be limited to 10% of set pressure for conventional type of the tailpipe may be fixed at the expected maximum
relief valve or 30% of the set pressure for balanced type. system back pressure.
The sizing of relief discharge piping can usually be For a complete and detailed design calculation of the
simplified by starting at the system outlet, where the discharge piping system, the use of Aspen Flarenet
pressure is known, and working back through the system
hydraulic program is suggested. This program has been
designed for rating flare and vent system.
As a general guidelines, the calculation options

Fluid Type VLE Method Enthalpy Method


Hydrocarbon Peng Robinson Peng Robinson
Nitrogen Compressible Gas Ideal Gas
Steam Vapor Pressure Ideal Gas

Vapor flow in relief discharge piping is characterized by


rapid changes in density and velocity; consequently, the
flow should be treated as compressible. Actual flow
conditions in relief systems will normally be somewhere
between isothermal and adiabatic conditions. For most
cases, the slightly more conserverative isothermal
equations are recommended;however, the adiabatic flow
equation are recommended for cryogenic kind of
applications.
For two phase flow, Beggs & Brill equations are
recommeded.

Literature Cited.
1.Chiyoda Design Practice, “Flare hydraulic calculation”,
CDP P 2547 ER0
2. API Recommended Practice (RP) 520
3. API Recommended Practice (RP) 521
4. Leung, J.C., “Easily size relief devices and piping for
two phase flow”, Chemical Engineering Progress, P.28
(Dec.1996)
5. Flarenet, User manual.

You might also like