DETAIL OF CONNECTED LOAD & MAX DEMAND

PROJECT: 4B+G+15 TYP.+ROOF OWNER: MR. ABDULLA ALI HAMAD AREA: AL MAMZAR , DUBAI, U.A.E
(COMMERCIAL & RESIDENTIAL BUILDING) SAEED BUHALEEBA

PLANNED COMPLETION DATE: CONSULTANT: ENGINEERING ASSOCIATES PLOT NO: 134-1040

MDB-01 LOCATION OF MDB: LV ROOM (GROUND FLOOR)

Rating AMPS CABLE SIZE PROPOSED TYPE & No. OF


PVC/ XLPE CONNECTED LOAD - kW
CIRCUIT/ FAULT kWh METERS
ECC SIZE-
SP/TP DUTY REMARKS
FEEDER F/S MCCB MCB 2/4x1C mm2 2/3/4C mm2 1C mm2 TOTAL 1-PH 3-PH 3-PH LV/HV
kA R-PH Y-PH B-PH
SWA/ PVC
DB NO. ISO ACB kW kW kW kW CT

(1) (2) (3) (4)

2500 BY DEWA
INCOMER-1 4P 50 2x1C-150 439.01 438.31 437.94 1315.26 1 2400/5A CT
SET @ 0.85

2500 BY GENERATOR SUPPLIER PROVISION FOR MOBILE GENERATOR WITH ELECTRICAL AND MECHANICAL INTERLOCK
INCOMER-2 4P 50
Set @ 0.85

OUTGOING

2500
BB1-MDB-01 TP 50 2500A TPN+E COPPER BUSBAR RISER 439.0 438.3 437.9 1315.3 100
Set @ 0.8
CAPACITOR BANK TP 1000 50 XLPE/SWA/LSZH 3x4C-240 3x1C-120 400 kVAR CAPACITOR BANK

MDB-01 CONNECTED TO: DEWA

Transf-01

TOTAL CONNECTED LOAD PER PHASE 439.0 438.3 437.9 1315.3 0 100 0 1 TOTAL

SMDB CONNECTED TO:

MDB

MAX DEMAND (3 PH) _______ 1183.7 kW @ 0.9 DIVERSITY TOTAL CONNECTED LOAD (3PH) 1315.3 kW

CONTRACTOR:

Type of Meter (Rating of Incomer): (1) Up to 60A (2) Up to 100A (3) Up to 125-160A (4) LV CT …../5A

( 1 PHASE ) ( 3 PHASE )
DETAIL OF CONNECTED LOAD & MAX DEMAND

PROJECT: 4B+G+15 TYP.+ROOF OWNER: MR. ABDULLA ALI HAMAD AREA: AL MAMZAR, DUBAI, U.A.E
COMMERCIAL & RESIDENTIAL BUILDING SAEED BUHALEEBA

PLANNED COMPLETION DATE: CONSULTANT: ENGINEERING ASSOCIATES PLOT NO: 134-1040

BB1-MDB-01 LOCATION OF LV: LV ROOM (GROUND FLOOR)

Rating AMPS CABLE SIZE PROPOSED TYPE & No. OF


FAULT PVC/ XLPE CONNECTED LOAD - kW
CIRCUIT/ ECC SIZE- kWh METERS
SP/TP DUTY 2/4x1C REMARKS
FEEDER F/S MCCB MCB 2/3/4C mm2 1C mm2 R-PH Y-PH B-PH TOTAL 1-PH 3-PH 3-PH LV/HV
kA SWA/ PVC mm2
DB NO. ISO ACB kW kW kW kW CT
(1) (2) (3) (4)

INCOMER TP 2500 50 2500A TPN+E COPPER BUSBAR RISER 439.01 438.31 437.94 1315.26

OUTGOING

SMDB-1F TP 300 50 XLPE/SWA/LSZH 4C-185 1x1C-95 43.9 43.8 43.8 131.5 10


SMDB-2F TP 300 50 XLPE/SWA/LSZH 4C-185 1x1C-95 43.9 43.8 43.8 131.5 10
SMDB-3F TP 300 50 XLPE/SWA/LSZH 4C-185 1x1C-95 43.9 43.8 43.8 131.5 10
SMDB-4F TP 300 50 XLPE/SWA/LSZH 4C-185 1x1C-95 43.9 43.8 43.8 131.5 10
SMDB-5F TP 300 50 XLPE/SWA/LSZH 4C-185 1x1C-95 43.9 43.8 43.8 131.5 10
SMDB-6F TP 300 50 XLPE/SWA/LSZH 4C-185 1x1C-95 43.9 43.8 43.8 131.5 10
SMDB-7F TP 300 50 XLPE/SWA/LSZH 4C-185 1x1C-95 43.9 43.8 43.8 131.5 10
SMDB-8F TP 300 50 XLPE/SWA/LSZH 4C-185 1x1C-95 43.9 43.8 43.8 131.5 10
SMDB-9F TP 300 50 XLPE/SWA/LSZH 4C-185 1x1C-95 43.9 43.8 43.8 131.5 10
SMDB-10F TP 300 50 XLPE/SWA/LSZH 4C-185 1x1C-95 44.1 43.8 43.6 131.5 10

MDB CONNECTED TO: DEWA


Transf-01
TOTAL CONNECTED LOAD PER PHASE 439.0 438.3 437.9 1315.3 0 100 0 0 TOTAL
SMDB CONNECTED TO:
BB1-MDB-01

MAX DEMAND (3 PH) _______ 1183.7 kW @ 0.9 DIVERSITY TOTAL CONNECTED LOAD (3PH) 1315.3 kW

CONTRACTOR:

Type of Meter (Rating of Incomer): (1) Up to 60A (2) Up to 100A (3) Up to 125-160A (4) LV CT …../5A
( 1 PHASE ) ( 3 PHASE )