Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 52, NO.

1, JANUARY/FEBRUARY 2016 67

An Effective Approach to Reducing Arc


Flash Hazards in Power Systems
Xiaodong Liang, Senior Member, IEEE, Bagen Bagen, Senior Member, IEEE, and
David Wenzhong Gao, Senior Member, IEEE

Abstract—The arc flash hazard is related to electrical safety in generated during an electrical arc event.” By definition, this
work place and has gained much attention as part of the safety could be due to both the heat radiated by the arc and the
program for many facilities. An effective approach to reducing the associated pressure-wave effects due to the expansion of air and
arc flash hazard in existing industrial and commercial facilities is
proposed in this paper. To illustrate the proposed approach and vaporized metal [3], [4].
provide quantified results, computer simulation is conducted for a In 1985, Lee published the first paper that could be used
large oil field facility and a manufacturing facility in a commercial to assess the hazards associated with the arc flash, where the
building as two case studies. The simulation results from the two thermal event associated with an electric arc and its effects on
case studies show significant reductions on the incident energy the human body were described for the first time [5]–[7]. It was
and the fault clearing time, which verifies the effectiveness of the
proposed approach. mentioned that the extremely high temperature of these arcs can
cause fatal burns at up to a distance of about 5 ft and major
Index Terms—Arc flash hazard analysis, fault clearing time, burns at up to a distance of about 10 ft from the arc. An arc flash
incident energy, personal protective equipment (PPE), protective
device coordination study, safety program. incident could result in serious injuries or death. Injury to bare
skin begins at an incident energy value of 1.2 cal/cm2 , which is
the equivalent heat energy of holding the skin in a candle flame
I. I NTRODUCTION for about 1 s [8].
To protect personnel safety, NFPA 70E 2015 Edition pro-
T HE arc flash hazard has gained much attention in the past
decade as it is related to electrical safety in the work
place [1]–[23]. NFPA 70E 2015 Edition defines the arc flash
vides general requirements for electrical-safety-related work
practice, establishing an electrically safe work condition and
hazard as a dangerous condition associated with the release guideline for working on or near live parts. To protect a worker
of energy caused by an electric arc [1]. An electric arc flash from the arc flash hazard, appropriate personal protective equip-
occurs when the insulation between the conductive components ment (PPE) is required.
can no longer withstand the applied voltage, which causes the The arc flash risk assessment shall be performed and shall de-
passage of current between two electrodes through ionized termine if an arc flash hazard exists [1]. Such assessment can be
gases and vapors. The electrical energy supplied to the arc performed by the arc flash hazard analysis using computer sim-
is converted into other forms of energy, resulting in intense ulation [2], [3]. If the assessment results show that an arc flash
thermal radiation, noise, explosive expansion of surrounding air hazard exists, the risk assessment shall further determine the
due to rapid heating, and melting/vaporization of arc electrodes appropriate safety-related work practices, the arc flash bound-
and metal components in the vicinity of the arc [2]. ary, and the PPE to be used within the arc flash boundary. The
The energy associated with an arc is defined as “incident arc flash risk assessment should be updated when a major mod-
energy” by IEEE Std 1584-2002: “the amount of energy ification and renovation takes place [1]. It is recommended by
impressed on a surface, a certain distance from the source, NFPA 70E 2015 Edition that such assessment should take into
consideration the design of the overcurrent protective device
and its opening time, including its condition and maintenance [1].
Manuscript received May 19, 2014; revised November 9, 2014; accepted The arc flash hazard is primarily found in electric circuits of
December 15, 2014. Date of publication September 8, 2015; date of current 208 V and higher in industrial and commercial facilities [2].
version January 18, 2016. Paper 2014-PSEC-0296.R1, presented at the 2014 These facilities have recognized that the arc flash prevention
IEEE Industry Applications Society Annual Meeting, Vancouver, BC, Canada,
October 5–9, and approved for publication in the IEEE T RANSACTIONS ON is part of a complete safety program. Quantification of the arc
I NDUSTRY A PPLICATIONS by the Power Systems Engineering Committee of flash hazard level and labeling procedures are major portions of
the IEEE Industry Applications Society. this effort [9].
X. Liang is with the Department of Electrical and Computer Engineer-
ing, Faculty of Engineering and Applied Science, Memorial University of The equipment labeling requirement is specified in
Newfoundland, St. John’s, NL A1B 3X5 , Canada (e-mail: xliang@mun.ca). NFPA 70E 2015 Edition [1]. Electrical equipment such as
B. Bagen is with Manitoba Hydro, Winnipeg, MB R3C 0G8, Canada (e-mail: switchboards, panel boards, industrial control panels, and motor
bbagen@hydro.mb.ca).
D. W. Gao is with the Department of Electrical and Computer Engineering, control centers, which are likely to require examination, adjust-
University of Denver, Denver, CO 80208 USA (e-mail: Wenzhong.Gao@ ment, servicing, or maintenance while energized, shall be field
du.edu). marked with a label. The laboratory should show the nominal
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. system voltage, the arc flash boundary, and at least one of the
Digital Object Identifier 10.1109/TIA.2015.2477269 following: 1) available incident energy and the corresponding
0093-9994 © 2015 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
68 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 52, NO. 1, JANUARY/FEBRUARY 2016

The estimated incident energy for an arc in a cubic box


(20 in on each side, open on one end) can be calculated by [1]

EMB = 1038.7DB−1.4738tA (0.0093F 2 −0.3453F +5.9675) (1)

where
EMB maximum 20-in cubic box incident energy in calories
per square centimeter;
DB distance from electrode, in inches (for distances 18 in
or greater);
tA arc duration, in seconds
F short-circuit current, in kiloamperes (for the range of
16–50 kA) [1].
It is found that the incident energy is determined by the short-
Fig. 1. Typical equipment label for arc flash hazard [10]. circuit current, the arc duration, and the distance from electrode.
For existing facilities, when the overcurrent protective device
working distance; 2) minimum arc rating of clothing; and settings are adjusted to clear the fault more quickly, the fault
3) site-specific level of PPE [1]. The label shall be updated clearing time/the arc duration will be reduced, which results in
where the review of the arc flash hazard risk assessment iden- a smaller incident energy.
tifies a change that renders the label inaccurate [1]. A sample
equipment label of the arc flash hazard is shown in Fig. 1 [10]. III. A PPROACH TO R EDUCING A RC F LASH H AZARD
According to NFPA 70E 2015 Edition, to select proper arc
flash PPE, one of the following methods shall be used: incident To reduce injury from the arc flash hazard and improve work
energy analysis method or arc flash PPE categories method. safety on or near electrical equipment in an existing industry
Either, but not both, method shall be permitted to be used on or commercial facility, the following approach is proposed and
the same piece of equipment [1]. can be implemented in two major steps.
In this paper, an effective approach to reducing the arc flash
1) Identify the arc flash hazard level and reduce the incident
hazard for existing industrial and commercial facilities is pro-
energy at specific equipment of interest. This step in-
posed. Although every facility has its own issues or concerns,
volves conducting two types of power system studies us-
this practical approach shall be able to significantly improve
ing the computer simulation software such as ETAP: the
the arc flash safety in existing facilities. This paper is arranged
arc flash hazard analysis and the overcurrent protective
as follows. The incident energy analysis method for arc flash
device coordination study. A few iterations between the
PPE selection recommended by NFPA 20E 2015 Edition is
two studies might be needed to achieve the best results.
presented in Section II; the proposed approach reducing the
2) If the incident energy disposure level cannot be further
arc flash hazard is introduced in Section III; to illustrate the
reduced by adjusting the overcurrent protective device
proposed approach and provide quantified results on the arc
settings for certain equipment, replacing the protective
flash hazard reductions, computer simulation using ETAP is
device might be a good solution. Usually, this protective
conducted for a large oil field facility and a manufacturing
device is the one that holds up the incident energy of
facility in a commercial building as two case studies, and the
all its downstream equipment; thus, finding this critical
simulation results for the two case studies are presented in
protective device is the key step. In this case, the first
Sections IV and V; the conclusions are drawn in Section VI.
effort is to find this critical protective device, then replace
it with a new one, and set up proper protective settings for
II. I NCIDENT E NERGY A NALYSIS M ETHOD FOR A RC it; the reduced incident energy level can be thus achieved.
F LASH PPE S ELECTION IN NFPA 70E 2015 E DITION The arc flash hazard analysis and the protective device
coordination study are needed during the process.
The incident energy analysis method in NFPA 70E 2015
Edition needs to determine the incident energy exposure level, The protective device coordination study is usually not re-
which shall be based on the working distance of the employee’s quested when the arc flash hazard analysis is requested. How-
face and chest areas from a prospective arc source for the ever, for the proposed approach in this paper, both studies
specific task to be performed. Arc-related clothing and other must be conducted at the same time to achieve the goal. The
PPE shall be used by the employee based on the incident ultimate results will be much reduced arc flash hazard and a
exposure associated with the specific task. The “guidance on safer facility for workers. The flowchart for implementing the
selection of arc-rated clothing and other PPE for use when proposed approach is shown in Fig. 2.
incident energy exposure is determined” is shown in Table I, When it comes to Step 2, it involves the replacement of
which is Table H.3(b) in NFPA 70E 2015 Edition [1]. This new a protective device; sometimes, it could be hard due to the
guideline replaces the old arc flash PPE selection criteria in cost. However, it is recommended that the facility management
NFPA 70E 2004. should invest on this for the sake of the workers’ safety.
LIANG et al.: EFFECTIVE APPROACH TO REDUCING ARC FLASH HAZARDS IN POWER SYSTEMS 69

TABLE I
G UIDANCE ON S ELECTION OF A RC -R ATED C LOTHING AND O THER PPE FOR U SE W HEN I NCIDENT
E NERGY E XPOSURE I S D ETERMINED (TABLE H.3( B ) IN NFPA 70E 2015 E DITION ) [1]

The following procedure might be useful for the facility


management to consider arc flash hazard: 1) identifying the
arc flash hazard by conducting the arc flash hazard analysis;
2) adjusting overcurrent protection settings for protective de-
vices and/or replacing the protective device(s) if necessary to
reduce the arc flash hazard; 3) implementing best engineering
practices on safety procedure; 4) implementing administration
reinforcement on safety procedure; and 5) utilizing PPE as the
last line of defense.

IV. C ASE S TUDY 1: A L ARGE O IL F IELD FACILITY


A large oil field facility is 50 years old and powers more
than 1000 electrical submersible pump oil wells. The arc flash
hazard became a concern of the facility management due to
past incidents. The arc flash hazard analysis was requested. The
goal of this analysis is to evaluate the arc flash hazard at major
equipment and provide labels for them.
The electrical single-line diagram of the facility is shown in
Fig. 3. The facility consists of four load groups. Inside each
load group, there are two main transformers stepping down the
voltage from 66 to 4.16 kV; the secondary of the two main trans-
formers is connected to the 4.16-kV switchgears. The power
is further distributed from the 4.16-kV switchgears to multiple
motor control centers downstream. There are medium-voltage
circuit breakers and relays connected between the secondary
of the two main transformers and the 4.16-kV switchgears in
Fig. 2. Proposed approach to reducing arc flash hazard for existing industrial each load group, and the relays serve as the major upstream
and commercial facilities. protection.
70 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 52, NO. 1, JANUARY/FEBRUARY 2016

Fig. 3. Electrical single-line diagram of the oil field facility.

Fig. 4. System configuration of Load Group 1.

The system configuration of Load Group 1 is shown in Fig. 4. From the power systems protection point of view, the pro-
The other three load groups have a similar system configuration. tective device settings are considered appropriate as long as
The 4.16-kV switchgears in Load Group 1 are represented by the upstream and downstream circuits follow the basic zone
the buses, i.e., “SGR#1-1” and “SGR#1-2” and “SGR#2-1” and protection rules. There are no fixed settings for protective
“SGR#2-2” in Fig. 4. devices. i.e., protective settings are allowed to be within a large
The proposed approach to reducing the arc flash hazard is range. That is why, sometimes, people call protection an art.
applied to this facility. The critical protective devices whose The rule to adjust the protective device settings for reducing the
settings affect the arc flash hazard levels significantly are the arc flash hazard is to keep the upstream and downstream circuits
relays Relay 1-1 and Relay 1-2 in Fig. 4, which are connected following the basic zone protection regardless how the settings
between the secondary of the two main transformers and the are changed.
4.16-kV switchgears inside each load group. On the other hand, the calculated fault clearing time, incident
Two terminologies are extensively used in the arc flash haz- energy, and arc flash boundary are determined by the protective
ard analysis: the fault clearing time and the arc flash boundary. device settings. Different protective device settings might result
The arc duration is defined as the fault clearing time, which in significant differences in the arc flash hazard analysis results.
is the calculated time in seconds needed by the protective To quantify the impact of such settings on the arc flash hazard,
device to completely clear the fault and extinguish the arc. The two sets of relay settings, i.e., existing and new overcurrent
arc flash boundary shall be the distance at which the incident protection settings, are applied to Relay 1-1 for each load group
energy is equal to 5 J/cm2 (1.2 cal/cm2 ) [1]. The arc flash in this oil field facility. The overcurrent protection settings for
boundary is determined from the incident energy and the fault the existing and new relay need to be coordinated with that of
clearing time. The unit of the arc flash boundary is in feet. all downstream relays.
LIANG et al.: EFFECTIVE APPROACH TO REDUCING ARC FLASH HAZARDS IN POWER SYSTEMS 71

TABLE II
S IMULATED A RC F LASH H AZARD A NALYSIS R ESULTS AT THE 4.16-kV S WITCHGEARS U SING D IFFERENT R ELAY S ETTINGS FOR F OUR L OAD G ROUPS

The arc flash hazard analysis and the protective device co- to less than 12 cal/cm2 . The arc flash PPE can be selected based
ordination study in this case study are conducted using the on these incident energy values using Table I.
computer simulation software ETAP. The simulated arc flash The “before” (existing) and “after” (new) overcurrent pro-
hazard analysis results at the 4.16-kV switchgears with existing tection settings of Relay 1-1 LG1 in Load Group 1 for reducing
and new overcurrent protection settings for each Relay 1-1 in the arc flash hazard are shown in the time–current characteristic
each load group are shown in Table II. (TCC) curves in Fig. 5. The two sets of settings for this relay
Table II indicates that the simulated incident energy at are coordinated with all downstream relays, which are circled
4.16-kV switchgears can be significantly reduced under the inside the red dashed oval in Fig. 5. The TCC curves for all
same arcing fault current conditions by simply adjusting the downstream relays are also included in the same figure.
relay overcurrent protection settings.
For example, using the existing overcurrent protection set-
tings for Relay 1-1 LG1 in Load Group 1, the simulated
V. C ASE S TUDY 2: A C OMMERCIAL B UILDING
incident energy at the 4.16-kV switchgears in Load Group 1
is 70.79 cal/cm2 . Using the new overcurrent protection settings The arc flash hazard analysis of a manufacturing facility in
for the same relay, the simulated incident energy becomes a commercial building is conducted in this paper to further
9.152 cal/cm2 at the same switchgear. illustrate the proposed approach. In this case study, a protective
Using new relay settings, the calculated incident energy value device must be replaced to reduce the arc flash hazard in panels
at the 4.16-kV main switchgear of each load group is reduced in the shop area of the facility.
72 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 52, NO. 1, JANUARY/FEBRUARY 2016

Fig. 5. (a) System configuration. (b) Settings for Relay 1-1 LG1 in Load Group 1 before and after adjustments for reducing arc flash hazard with coordinated
downstream relays.

The electrical single-line diagram of the manufacturing facil- place arc flash labels at panels, an arc flash hazard analysis was
ity is shown in Fig. 6. The low-voltage circuit breakers are the conducted for the facility.
main protective devices of the facility. The power is supplied The computer simulation of the facility was done by conduct-
through the 1500-kVA utility transformer T1 located outside ing the overcurrent protective device coordination study and the
the building. To improve the electrical safety in the facility and arc flash hazard analysis using ETAP. It is found that the 480-V
LIANG et al.: EFFECTIVE APPROACH TO REDUCING ARC FLASH HAZARDS IN POWER SYSTEMS 73

Fig. 6. Electrical single-line diagram of the manufacturing facility in a commercial building.

main panel “Pnl S4” and all its downstream panels at the “shop” settings can be set up with much more flexibility than the old
area have large incident energy values. The panel Pnl S4 is con- thermal-magnetic-type trip device.
nected to the downstream of the circuit breaker CB-9 and the The new circuit breaker is selected to be a Siemens 0.6-kV
transformer T2 , as shown in Fig. 6. Large incident energy levels LLG model with a 600-A frame size. Its trip device is the solid-
at these panels threaten the safety of the person who works on state trip device ETU 545 (LG frame) model with a sensor of
or near these panels in case the arc flash incidents happen. 600 A (LSIG). The proper protective settings of the new circuit
To reduce the arc flash hazard at the panels in the shop area, breaker CB-9 are set up by conducting the protective device
the overcurrent protection settings for the trip device of the coordination study, and the arc flash hazard analysis is then
circuit breaker CB-9 are adjusted by conducting the protective performed using the new circuit breaker and its new settings.
device coordination study. However, although its settings are The simulated arc flash incident energy at the panel Pnl S4
adjusted to the best that is allowed by protection, the incident using the existing and new circuit breakers CB-9 is shown in
energy level still remains high. The reason is that the circuit Table III. The TCC curves of the existing and new circuit break-
breaker CB-9 is a Siemens 0.6-kV LD6-A model with a 600-A ers CB-9 are shown in Fig. 7. The downstream circuit breaker
frame size, and its trip device is the thermal magnetic type overcurrent protection settings are also shown in the same figure.
with very limited room to make adjustment on settings. Due Based on the TCC curves in Fig. 7, the existing circuit
to this single circuit breaker, many panels in the shop area (the breaker cannot even protect the transformer T2 from the thermal
panel Pnl S4 and all its downstream panels) are exposed to high damage due to its fixed setting. Therefore, from the protection
incident energy levels of the arc flash hazard. point of view, it must be also replaced. By replacing this circuit
The solution is to replace the existing circuit breaker CB-9 by breaker with the proposed new one, the transformer T2 can be
a new one with the solid-state trip device, where the protection protected from thermal damage in case of faults. Meanwhile,
74 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 52, NO. 1, JANUARY/FEBRUARY 2016

TABLE III
S IMULATED A RC F LASH H AZARD A NALYSIS R ESULTS AT THE 480-V M AIN PANEL Pnl S4
AT THE S HOP A REA U SING THE E XISTING AND N EW C IRCUIT B REAKERS CB-9

Fig. 7. Protective settings for the existing (before) and new (after) circuit breakers CB-9.

the incident energy levels at the main panel Pnl S4 and all its is 57.58 cal/cm2 . By replacing the existing circuit breaker
downstream panels are reduced significantly. CB-9 with the proposed new one, the simulated incident energy
As shown in Table III, using the existing circuit breaker at this panel is 13.293 cal/cm2 , with the fault clearing time equal
CB-9, the simulated incident energy at the main panel Pnl S4 to 1.195 s.
LIANG et al.: EFFECTIVE APPROACH TO REDUCING ARC FLASH HAZARDS IN POWER SYSTEMS 75

VI. C ONCLUSION [16] J. Buff and K. Zimmerman, “Application of existing technologies to


reduce arc-flash hazards,” in Proc. Power Syst. Conf.: Adv. Metering,
In this paper, an effective approach to reducing arc flash Protection, Control, Commun., Distributed Resources (PSC’07), 2007,
hazard in existing industrial and commercial facilities has been pp. 8–15.
[17] W. S. Hopper and B. L. Etzel, “Distribution equipment modernization
proposed. This approach will need the computer simulation to reduce arc flash hazards,” IEEE Trans. Ind. Appl., vol. 44, no. 3,
work using two power system studies, namely, an overcurrent pp. 940–948, May/Jun. 2008.
protective device coordination study and an arc flash hazard [18] A. M. Graham, M. Hodder, and G. Gates, “Current methods for conduct-
ing an arc-flash hazard analysis,” IEEE Trans. Ind. Appl., vol. 44, no. 6,
analysis. A few iterations might be needed between the two pp. 1902–1909, Nov./Dec. 2008.
studies in order to obtain optimal results. [19] P. E. Sutherland, “Arc flash and coordination study conflict in an older
When adjusting the protective device settings to reduce the industrial plant,” IEEE Trans. Ind. Appl., vol. 45, no. 2, pp. 569–574,
Mar./Apr. 2009.
arc flash hazard, the upstream and downstream circuits must [20] D. R. Doan, J. K. Slivka, and C. J. Bohrer, “A summary of arc flash hazard
follow the basic zone protection rules for the power system pro- assessments and safety improvements,” IEEE Trans. Ind. Appl., vol. 45,
tection purpose. Once these rules are followed and the equip- no. 4, pp. 1210–1216, Jul./Aug. 2009.
[21] M. D’Mello, M. Noonan, H. Aulakh, and J. Mirabent, “Arc flash en-
ment is protected, the protective device settings can be adjusted ergy reduction? Case studies,” IEEE Trans. Ind. Appl., vol. 49, no. 3,
to bring down the arc flash incident energy level in the facility. pp. 1198–1204, May/Jun. 2013.
In some cases, due to the nature of existing facilities, some [22] G. T. Homce and J. C. Cawley, “Understanding and quantifying arc flash
hazards in the mining industry,” IEEE Trans. Ind. Appl., vol. 47, no. 6,
protective devices could appear to be the major cause of high pp. 2437–2444, Nov./Dec. 2011.
arc flash incident energy levels for certain equipment, which [23] X. Liang and J. Lim, “Power-system protection in an oil-field distribution
are identified as critical protective devices in this paper. If system,” IEEE Trans. Ind. Appl., vol. 46, no. 1, pp. 340–348, Jan./Feb. 2010.
adjusting protective device settings for these critical protective
devices cannot effectively bring down the incident energy, such Xiaodong Liang (M’06–SM’09) was born in
Lingyuan, China. She received the B.Eng. and M.Eng.
protective devices should be replaced to reduce the arc flash degrees from Shenyang Polytechnic University,
hazard and improve work safety in the facility. Shenyang, China, in 1992 and 1995, respectively, the
To reduce the arc flash hazard, research is extensively con- M.Sc. degree from the University of Saskatchewan,
Saskatoon, SK, Canada, in 2004, and the Ph.D. de-
ducted by academia and industry. The zone selective interlock- gree from the University of Alberta, Edmonton, AB,
ing technology, current-limiting fuses, and arc protection relays Canada, in 2013, all in electrical engineering.
with fiber optics are some methods of this effort [11]–[23]. From 1995 to 1999, she was a Lecturer with
Northeastern University, Shenyang. In October 2001,
Exploring more advanced technologies on reducing arc flash she joined Schlumberger, Edmonton. She was a
hazard analysis will be our future work. Principal Power Systems Engineer with this large oil service company before
joining Washington State University, Vancouver, WA, USA, in August 2013,
where she was an Assistant Professor until May 2015. In July 2015, she joined
R EFERENCES Memorial University of Newfoundland, St. John’s, NL, Canada, where she is
[1] Standard for Electrical Safety in the Workplace, NFPA 70E, 2015. currently an Assistant Professor. Her research interests include power system
[2] M. D. Gibbs, “Arc flash boundary calculations using computer software dynamics, power quality, and electric machines.
tools,” in Proc. 39th IEEE IAS Annu. Meeting, 2004, pp. 1731–1736. Dr. Liang is a Registered Professional Engineer in the Provinces of Alberta
[3] IEEE Guide for Performing Arc Flash Hazard Calculations, IEEE Std. and Newfoundland and Labrador, Canada.
1584-2002, 2002.
[4] W. A. Brown and R. Shapiro, “Incident energy reduction techniques:
A comparison using low-voltage power circuit breakers,” IEEE Ind. Appl. Bagen Bagen (M’05–SM’11) received the M.Sc. and
Mag., vol. 15, no. 3, pp. 53–61, May/Jun. 2009. Ph.D. degrees from the University of Saskatchewan,
[5] R. H. Lee, “The other electrical hazard: Electric arc blast burns,” IEEE Saskatoon, SK, Canada, in 2002 and 2005, respec-
Trans. Ind. Appl., vol. IA-18, no. 3, pp. 246–251, May/Jun. 1982. tively.
[6] R. H. Lee, “Pressures developed by arcs blast,” IEEE Trans. Ind. Appl., He is currently a Planning Engineer with the
vol. IA-23, no. 4, pp. 760–763, Jul./Aug. 1987. System Planning Department, Manitoba Hydro,
[7] C. Inshaw and R. A. Wilson, “Arc flash hazard analysis and mitigation,” Winnipeg, AB, Canada.
in Proc. 58th Annu. Conf. Protective Relay Eng., 2005, pp. 145–157. Dr. Bagen was a Registered Professional Engineer
[8] D. R. Doan and R. A. Sweigart, “A summary of arc-flash energy calcula- with the Association of Professional Engineers and
tions,” IEEE Trans. Ind. Appl., vol. 39, no. 4, pp. 1200–1204, Jul./Aug. 2003. Geoscientists of the Province of Manitoba, Canada.
[9] M. Hodder, W. Vilcheck, F. Croyle, and D. McCue, “Practical methods in
reducing the dangerous arc flash hazard areas in large industrial facilities,”
in Conf. Rec. 2005 Annu. Pulp Paper Ind. Tech. Conf., pp. 191–198.
[10] G. M. Kemper, W. S. Vilcheck, and D. B. Durocher, “The journey of an en- David Wenzhong Gao (M’02–SM’03) received the
terprise in a process industry toward improved electrical workplace safety,” M.S. and Ph.D. degrees in electrical and computer
IEEE Trans. Ind. Appl., vol. 50, no. 5, pp. 3072–3078, Sep./Oct. 2014. engineering from Georgia Institute of Technology,
[11] D. L. Hodgson, and D. Shipp, “Arc-flash incident energy reduction Atlanta, GA, USA, in 1999 and 2002, respectively,
using zone selective interlocking,” IEEE Trans. Ind. Appl., vol. 46, no. 3, specializing in electric power engineering.
pp. 1243–1251, May/Jun. 2010. He is currently an Associate Professor with the
[12] G. D. Gregory, I. Lyttle, and C. M. Wellman, “Arc flash calculations Department of Electrical and Computer Engineering,
in systems protected by low-voltage circuit breakers,” IEEE Trans. Ind. University of Denver, Denver, CO, USA. His current
Appl., vol. 39, no. 4, pp. 1193–1199, Jul./Aug. 2003. teaching and research interests include renewable
[13] H. W. Tinsley, III and M. Hodder, “A practical approach to arc flash energy and distributed generation, smart grid, power
hazard analysis and reduction,” IEEE Trans. Ind. Appl., vol. 41, no. 1, system protection, power electronics applications in
pp. 144–154, Jan./Feb. 2005. power systems, power system modeling and simulation, and hybrid electric
[14] J. C. Das, “Design aspects of industrial distribution systems to limit arc propulsion systems.
flash hazard,” IEEE Trans. Ind. Appl., vol. 41, no. 6, pp. 1467–1475, Dr. Gao was the General Chair of the 2012 IEEE Symposium on Power
Nov./Dec. 2005. Electronics and Machines in Wind Applications. He is an Editor of the IEEE
[15] F. Nepveux, “Use of instantaneous trip functions and current limiting T RANSACTIONS ON S USTAINABLE E NERGY and an Associate Editor of
fuses to reduce arc flash energy,” in Conf. Rec. IEEE IAS Annu. Meeting, the IEEE J OURNAL OF E MERGING AND S ELECTED T OPICS IN P OWER
2006, pp. 1–5. E LECTRONICS .

You might also like