Professional Documents
Culture Documents
Seismic Design Manual Examples - 2010
Seismic Design Manual Examples - 2010
Floor diaphragm:
3,950 lb
f p floor = = 2.56 psf
1,542 sq ft
Table 1-4. North-south shear walls at roof level (second floor to roof)
Ftot
Wall ∑ Fabove ∑ Fx Ftot b v =
(b )1.4 Sheathing Allowable Edge Nail
(lb) (lb) (lb) (ft) 1 or 2 sides Shear (plf) Spacing (in.)
(plf)
1 0 1,179 1,179 18.0 47 One 510 4
2 0 1,493 1,493 10.0 107 One 510 4
3 0 6,112 6,112 15.0 291 One 510 4
5 0 6,016 6,016 26.0 165 One 510 4
Σ 0 14,800 14,800 69.0
Table1-5. North-south shear walls at floor level (first floor to second floor)
Ftot
Wall ∑ Fabove ∑ Fx Ftot b v=
(b )1.4
Sheathing Allowable Edge Nail
(lb) (lb) (lb) (ft) 1 or 2 sides Shear (plf) Spacing (in)
(plf)
2 1,493 99 1,592 10.0 114 One 510 4
3 6,112 1,779 7,891 22.0 256 One 510 4
5 6,016 2,074 8,090 14.0 413 One 510 4
Σ 13,621 3,952 17,573 46.0
Determination of the rigidities of wood shear walls is often difficult and inexact,
even for design loads. In addition, when walls are loaded substantially beyond their
design limits, as occur under strong earthquake motions, rigidity determination
becomes even more difficult. It is complicated by a number of factors that make
any exact determination, in a general sense, virtually impossible short of full-scale
testing.
There is the well-known expression for shear wall deflection found in UBC
Standard 23-2. This expression, shown below, is used to estimate deflections of
shear walls with fixed bases and free tops for design level forces.
8vh 3 vh h
= + + 0.75hen + d a §23.223, Vol. 3
EAb Gt b
The expression above was developed from static tests of solid wood shear walls,
many typically 8-foot x 8-foot in size. Until recently, there was very little cyclic
testing of wood shear walls (to simulate actual earthquake behavior) or testing of
walls with narrow aspect ratios.
In modern wood frame building construction, shear walls take many forms and
sizes, and these are often penetrated by ducts, windows, and door openings. Also,
many walls in residences are not designed as shear walls, yet have stiffness from
their finish materials (gypsum board, stucco, etc.). In multi-story structures, walls
are stacked on the walls of lower floors, producing indeterminate structural
systems. In general, it is difficult to calculate wall rigidities with the UBC equation
alone. As will be shown in subsequent paragraphs, things like shrinkage can
significantly effect deflection and subsequent stiffness calculations. Further, in
strong earthquake motions, shear walls may see forces and displacements several
times larger than those used in design, and cyclic degradation effects can occur that
significantly change the relative stiffness of shear walls at the same level.
It can be argued that wall rotation of the supporting wall below needs to be
considered when considering shear wall rigidities. However, considering rotation
of the supporting wall below would be similar to measuring the shear wall as the
cumulative height, as opposed to the accepted floor-to-floor clear height. Not
considering rotation of the supporting wall below is appropriate for determining
relative wall rigidities.
At the present time, there are number of ways to estimate shear wall rigidities,
particularly when only relative rigidities are desired (see Blue Book §C805.3).
These include:
1. Rigidity based on estimated nail slip.
2. Rigidity calculated from UBC Standard 23-2 (the four term equation given
above).
3. Rigidity incorporating both UBC Standard 23-2 and shrinkage.
4. Several other procedures.
Only one of these approaches is given in this design example. By using this one
approach, SEAOC does not intend to establish a standard procedure or indicate a
standard of care for calculation of wood shear wall rigidities. It is merely one of the
present-day methods.
F = k∆
or k = F ∆
The basic equation to determine the deflection of a shear wall is the four-term
equation shown below.
8vh 3 vh h
= + + 0.75hen + d a §23.223, Vol. 3
EAb Gt b
The above equation is based on a uniformly nailed, cantilever shear wall with a
horizontal point load at the top, panel edges blocked, and reflects tests conducted
by the American Plywood Association. The deflection is estimated from the
contributions of four distinct parts. The first part of the equation accounts for
cantilever beam action using the moment of inertia of the boundary elements. The
second term accounts for shear deformation of the sheathing. The third term
accounts for nail slippage/bending, and the fourth term accounts for tiedown
assembly displacement (this also should include bolt/nail slip and shrinkage). End
stud elongation due to compression or tension is not considered, nor the end
rotations of the base support. The UBC references this in §2315.1.
Testing on wood shear walls has indicated that the above formula is reasonably
accurate for aspect ratios (h w) lower than or equal to 2:1. For higher aspect ratios,
the wall drift increases significantly, and testing showed that displacements were
not adequately predicted. Use of the new aspect ratio requirement of 2:1 (1997
UBC) makes this formula more accurate for determining shear wall deflection/
stiffness than it was in previous editions of the UBC, subject to the limitations
mentioned above.
Recent testing on wood shear walls has shown that sill plate crushing under the
boundary element can increase the deflection of the shear wall by as much as 20
percent to 30 percent. For a calculation of this crushing effect, see the deflection of
wall frame at line D later in Part 3c.
where:
Many engineers have a concern that if the contractor installs the nails at a different
spacing (too many or too few), then the rigidities will be different than those
calculated. However, nominal changing of the nail spacing in a given wall does not
significantly change the stiffness.
Wood design using the 1997 UBC now means that the engineer must use both
strength-level forces and allowable stress forces. This can create some confusion,
since the code requires drift checks to be strength-level forces. However, all of the
design equations and tables in Chapter 23 are based on allowable stress design.
Drift and shear wall forces will be based on strength-level forces. Remember that
the structural system factor R is based on using strength-level forces.
Table 1-6. Determine tiedown assembly displacements for roof level shear walls1
ASD Strength Design
Wall Uplift/1.4(2) Tiedown(3) Uplift Tiedown(4) Tiedown Assembly Displacement da(8)
(lb) Device (lb) Elongation (in.) Shrink(5) Crush(6) Slip(7) (in.)
A1 5,915 Bolted 8,280 0.13 0.19 0.02 0.04 0.38
A2 5,915 Bolted 8,280 0.13 0.19 0.02 0.04 0.38
B 5,975 Bolted 8,365 0.13 0.19 0.02 0.04 0.38
C 7,430 Bolted 10,400 0.17 0.19 0.04 0.05 0.45
1 0 Not required 0 0 0.02 0.02 0 0.04
2 0 Not required 0 0 0.19 0.02 0 0.21
3 830 Strap 1,160 0.004 0.19 0.02 0.002 0.21
5a 0 Not required 0 0 0.19 0.02 0 0.21
5b 0 Not required 0 0 0.19 0.02 0 0.21
Notes:
1. Tiedown assembly displacement is calculated at the second floor level.
2. Uplift force is determined by using the net overturning force (M OT − M OR ) divided by
the distance between the centroid of the tiedown to the end of the shear wall. With 4x
members at the ends of the wall, this equates to the length of the wall minus 1¾ inches
for straps, or the length of wall minus 5½ inches when using a bolted holdown with
2-inch offset from post to anchor bolt. Using allowable stress design, tiedown devices
need only be sized by using the ASD uplift force. The strength design uplift force is used
to determine tiedown assembly displacement in order to determine strength-level
displacements.
3. Continuous tie rod holdown systems can also be used. See Design Example 2 for method
of calculating tiedown assembly displacement.
4. Tiedown elongation is based on actual uplift force divided by tiedown capacity times
tiedown elongation at capacity (from manufacturer’s catalog). Example for tiedown
elongation at A1: tiedown selected has a 15,000 lb allowable load for a 5½-inch-thick
(net) member. From the manufacturer’s ICBO Evaluation Report, the tiedown deflection
at the highest allowable design load (15,000 lb) is 0.12 inches. Since there are two
tiedown devices (one above and one below the floor), the total elongation is twice the
tiedown deflection of one device. Therefore the total tiedown elongation is
(8,280 15,000)0.12 × 2 = 0.13 inches.
5. Wood shrinkage based on a change from 19 percent moisture content (MC) to 13 percent
MC with 19 percent MC being assumed for S-Dry lumber per project specifications. The
MC of 13 percent is the assumed final MC at equilibrium with ambient humidity for the
project location. The final equilibrium value can be higher in coastal areas and lower in
inland or desert areas. This equates to (0.002 ) (d ) (19-13), where d is the dimension of
the lumber (see Figure 1-10).
Shrinkage:
2 × DBL Top Plate + 2 × sill plate = (0.002 ) (3 × 1.5 in.) (19 − 13) = 0.05
2 × 12 Floor Joist = (0.002)(11.25) (19 − 13) = 0.14
= 0.19 in.
The use of pre-manufactured, dimensionally stable, wood I joists are considered not to
shrink, and would thereby reduce the shrinkage to 0.05 inches.
6. Per 91 NDS 4.2.6, when compression perpendicular to grain ( f c⊥ ) is less than
0.73F ’c⊥ crushing will be approximately 0.02 inches. When f c⊥ = F ’c⊥ crushing is
approximately 0.04 inches. The effect of sill plate crushing is the downward effect with
uplift force at the opposite end of the wall and has the same rotational effect as the
tiedown displacement. Short walls that have no uplift forces will still have a wood
crushing effect and contribute to rotation of the wall.
7. Per 91 NDS 7.3.6γ = (270,000)(1)1.5 = 270,000 lb/in. plus 1/16" oversized hole for bolts.
For nails, values for en can be used. Example for slip at tiedown at A1 (tiedown has five
1-inch diameter bolts to post):
Since there are two tiedown devices (one above and one below the floor), the total slip is
twice the bolt slip. Good detailing practice should specify the tiedown bolts to be
re-tightened just prior to closing in. This can accomplish two things: it takes the slack out
of the oversized bolt hole and compensates for some wood shrinkage. This design
example will assume that about one-half of the bolt hole slack is taken out.
1 1
Therefore, total slip equals (0.006 × 2) + = 0.04 inches.
16 2
8. d a is the total tiedown assembly displacement. This also could include mis-cuts
(short-studs) and lack of square cut ends.
the allowable stress design values. Since there are tiedown assembly displacements, and dead loads that
resist overturning, the factoring up approach of ASD forces is not appropriate.
8. When sheathing is applied to both sides of the wall, the deflection of the shear wall is determined by using
one-half the values from Table 1-2.
9. In-plane shears to walls 5a and 5b are proportioned based on relative lengths (not per §23.223, Volume 3).
( )
Example for wall at line 5a: R = 162 162 + 102 = 72 percent, which is appropriate for two walls in a line,
but not necessarily for three or more walls in line. Attempting to equate deflections is desirable. However,
the calculations are iterative and indeterminate, and the results are very similar.
10. For deflection of shear wall at line D, see the following Part 3c.
Determine deflection of wall frame at line D (with force transfer around openings).
The deflection for the shear wall can be approximated by using an analysis similar
to computing the stiffness for a concrete wall with an opening in it. The deflection
for the solid wall is computed, then a deflection for a horizontal window strip is
subtracted, and the deflection for the wall piers added back in.
8vh 3 vh h
= + + 0.75hen + d a §23.223 Vol. 3
EAb Gt b
Sheathing is on both sides of wall with 10d common nails @ 2 inches o. c. Wall
has 2 × 6 studs with 4 × 6 at ends.
V = 5,198 lb
5,198 lb
v= = 260 plf
(2 )10.0 ft
With a tiedown elongation of 0.05 in., wood shrinkage of 0.13 in., and wood
crushing of .02, it gives a tiedown assembly displacement of 0.20 in.
For crushing: from Part 9e, the strength level overturning moment
M OT = 52,452 ft-lb. Dividing by the distance L = 9.7 ft computes the seismic
downward component of the 4 × 6 post:
fc = P A
∴ crush = 0.02 in
PL
For strap: + strap nail slip = 0.05 in.
AE
V = 5,198 lb (strength)
5,198 lb
v= = 260 plf
(2 )10.0 ft
Since the boundary elements are connected to continuous posts that extend above
and below the opening, the value of d a equals the sheathing nail deformation
value calculated above (boundary element “chord” elongation is neglected):
d a = 0.0001 in.
Note that this deflection is negative because it is subtracted from the sum of the
deflections, as shown later.