1.

ALL DIMENSIONS ARE IN MILLIMETERS AND ELEVATIONS ARE IN


METER UNLESS OTHERWISE NOTED.
2. AREA CLASSIFICATION BASED ON IP MODEL CODE OF SAFE
PRACTICE PART-15, 4TH EDITION AND RELEVANT HAZARDOUS
MATERIALS SCHEDULE.

3. FOR THE BASIS OF HAZARDOUS AREA RELEASE AND


TEMPERATURE CLASS REFERRELEVANT HAZARDOUS AREA
DETAIL 1: AREA CLASSIFICATION FOR ELEVATED STORAGE TANK OR PRESSURE VESSEL DETAIL 2: AREA CLASSIFICATION FOR PUMPS DETAIL 3: AREA CLASSIFICATION FOR TANK VENTS
000 CLASSIFICATION SCHEDULE.
0 = 2
=1 00 0 R2 4. THE POINT SOURCE OF RELEASE FOR SKID MOUNTED EQUIPMENT
R1 100 0
R1= 100 WILL BE CONSIDERED FROM THE EDGE OF THE EQUIPMENT.
R1= 00
TANK WITHIN BUND TANK IN OPEN AREA R1=10

2
R1
SOURCE 5. FLANGES AND VALVES ON FLAMMABLE PRODUCT LINES LOCATED

1000
RELIEF

P
ON PIPE RACK SHALL NOT BE CLOSER THAN 3000mm FROM

TY
R2 VALVE R2 GRADE

TY
VENT R2 ROADS.

R2
2
RELEASE WHERE H < 1000mm 6. ALL EQUIPMENT SHALL BE CE MARKED AND CODED WITH AN ATEX
CATEGORY IN RELATION TO THE DESIGN AND CONSTRUCTION OF

3000
0
100 EQUIPMENT INTENDED FOR USE IN POTENTIALLY EXPLOSIVE
R1=

H
H
VENT ATMOSPHERE.
SEE DETAIL-3

SOURCE 7. DETAIL 4 SHALL ALSO COVER SAMPLING POINTS BECAUSE ALL


SAMPLING POINTS ARE CLOSED CIRCUIT AND NO VENTING IS

H
1000
ALLOWED DURING SAMPLING AND THERE IS NO DISCHARGE OR
GRADE DISCHARGE DIRECTLY TO ATMOSPHERE OR GROUND. THIS ALL
R2 GRADE SAMPLING POINTS SHALL HAVE A ZONE 2 CLASSIFICATION SIMILAR
TO FLANGED CONNECTIONS.
RELEASE WHERE 1000mm<H<R1+1000mm
(A) PRIMARY GRADE RELEASE (B) SECONDARY GRADE RELEASE (C) VENT WITH DUAL REQUIREMENTS
RELEASE ABOVE 1000mm, BUT AT HEIGHTS BELOW
VENTS TO ATMOSPHERE: (TANK VENTS, PROCESS VENTS, INSTRUMENT VENTS AND PRESSURE RELIEF
THE HAZARD RADIUS R1+1000mm ARE INFLUENCED BY
VALVES)
THE GROUND IF THE RELEASE IS DIRECTED
DOWNWARD AND PASSES BELOW 1000mm. NOTES:

00 1. AREA CLASSIFICATION DETAIL PREPARED IN ACCORDANCE WITH CL. 3.6.2.2 OF IP-15, 4TH EDITION.
0
R 1=1 2. THE FIGURE WITH THE TABLE 3.1 OF IP-15 GIVE THE HAZARDOUS AREA AROUND THE VENT FROM THE
BUND STORAGE OF A TYPICAL CATEGORY 'C' LIQUID.
3. VENT PIPE OPENING SHOULD HAVE AT LEAST R1 MILLIMETERS OF FREE SPACE AROUND IT IN ALL
GRADE SOURCE DIRECTION TO ALLOW DISPERSAL OF VAPOR AND BE AWAY FROM OPEN WINDOWS, DOORS ETC.
4. HIGH LEVEL VENTS (E.G) FROM UNDERGROUND OR MOUNDED TANKAGE SHOULD BE REGARDED AS PRIMARY
GRADE RELEASE SOURCES WITH THE EXTENT OF ZONE-1 HAZARDOUS AREA DEPENDENT ON VAPOR

H
PIT OR DEPRESSION EMISSION RATE (OR FILING RATE) AS DESCRIBED IN 3.6.2 OF IP-15, 4TH EDITION.

1000
5. VENT RATE AND DIAMETER ARE INDICATED BY PROCESS.
GRADE 6. R1 AND R2 ARE AS DEFINED IN THE RELEVANT HAZARDOUS AREA SCHEDULE FOR THE SPECIFIC PIECE
NOTES:
OF EQUIPMENT. REFER RELEVANT HAZARDOUS AREA CLASSIFICATION SCHEDULE.
1. AREA CLASSIFICATION DETAIL PREPARED IN ACCORDANCE WITH CL. D3.2 & 3.4 OF IP-15, 4TH RELEASE WHERE H>R1+1000mm
7. 'H' DEPENDS ON THE TEMPERATURE OF RELEASE AND THE VOLATILITY OF THE MATERIAL RELEASED.
EDITION.

2. R1 AND R2 ARE AS DEFINED IN THE RELEVANT HAZARDOUS AREA SCHEDULE FOR THE SPECIFIC NOTES:
DETAIL 5: AREA CLASSIFICATION FOR PROCESS VENTS DETAIL 6: AREA CLASSIFICATION FOR PIT DEPRESSION
PIECE OF EQUIPMENT. REFER RELEVANT HAZARDOUS AREA CLASSIFICATION SCHEDULE. 1. AREA CLASSIFICATION DETAIL PREPARED IN
ACCORDANCE WITH CL. 3.7.1 OF IP-15, 4TH
0 0
DETAIL 4: AREA CLASSIFICATION FOR RELEASE HEAVIER THAN AIR FOR PIPING WITH VALVES,
EDITION. THE FLUID CATEGORY IS 'A' FOR LPG, =10 R1
'B' FOR C3-C10, 'C' FOR MIXED MATERIAL AND R1 =1
SCREWS, FITTINGS, FLANGES OR SIMILAR ACCESSORIES (REFER NOTE-7) 00
0
0
G(ii) FOR HYDROGEN, C1, C3. LEGEND:
00 2. POINT SOURCES ON PUMPS INCLUDE THEIR
SOURCE
1 =1 SEALS, VENTS, DRAINS, VALVES, SAMPLING GRADE
R ZONE 0 AREA
POINT, PIPING FLANGES AND FILTERS/STRAINERS.
BELOW GRADE LOCATION

H
3. WHERE A PUMP IS AT A HEIGHT IS LESS
SUCH AS A SUMP OR TRENCH THAN OR EQUAL TO 1000mm IS INFLUENCED BY ZONE 1 AREA

1000
THE GROUND AND HAVE A HAZARD RADIUS R2 NOTES:
1000

SOURCE GRADE
GRADE AS PER TABLE C4 IN ANNEX.C PART-1.
1.
AREA CLASSIFICATION DETAIL PREPARED IN ZONE 2 AREA
4. PUMPS HANDLING HAZARDOUS MATERIALS ARE
RELEASE WHERE H>R1+1000mm ACCORDANCE WITH CL. 3.6.4 OF IP-15, 4TH
R2 HIGH INTEGRITY PUMPS. AS PER CL. 3.7.1 OF
EDITION.
IP-15 TO ACHIEVE ZONE-2 CLASSIFICATION. NOTES: UNCLASSIFIED AREA
NOTES: 2. WHERE A PIT OR DEPRESSION EXISTS IN A
5. R1 AND R2 ARE DEFINED IN THE RELEVANT 1. AREA CLASSIFICATION DRAWING PREPARED IN HAZARDOUS AREA, WITHOUT ITSELF CONTAINING A
1. AREA CLASSIFICATION DETAIL PREPARED IN ACCORDANCE WITH CL. 3.7.3.1 OF IP-15, 4TH EDITION. HAZARDOUS AREA SCHEDULE FOR THE SPECIFIC ACCORDANCE WITH CL. 3.6.2.3 OF IP-15, 4TH EDITION. SOURCE OF RELEASE, IT SHOULD BE REGARDED AS
2. SHOWN FOR PIPING INSTALLED ABOVE GRADE. ALSO APPLIES TO BURIED PIPING WITH ABOVE GRADE VENTS, SUCH AS PIECE OF EQUIPMENT. REFER RELEVANT 2. THE ZONE CLASSIFICATION WILL DEPEND ON THE INADEQUATELY VENTILATED AND THEREFORE
MOTOR OPERATED VALVE BODY BURIED AND THE MOTOR OPERATOR ABOVE GRADE. HAZARDOUS AREA CLASSIFICATION SCHEDULE. GRADE OF RELEASE. TO AVOID GROUND EFFECTS (R2) CLASSIFIED AS ZONE-1.
3. R1 & R2 ARE AS DEFINED IN THE RELEVANT HAZARDOUS AREA SCHEDULE FOR THE SPECIFIC PIECE OF EQUIPMENT.
AND EFFECTS ON PERSONNEL, IT IS RECOMMENDED
REFER RELEVANT HAZARDOUS AREA CLASSIFICATION SCHEDULE.
THAT PROCESS VENTS DETAIL 10: AREA CLASSIFICATION FOR SUMPS
DISCHARGE AT A HEIGHT GREATER THAN R1+2000mm
FROM GROUND OR THE NEAREST WORKING LEVEL.
3. FOR SPECIFIC VENT CONDITIONS NOT GIVEN IN THE
DETAIL 7: AREA CLASSIFICATION FOR TOP LOADING TANKERS (DIESEL) DETAIL 8: AREA CLASSIFICATION FOR TOP LOADING TANKERS (PROPANE)

H
TABLE 3.2 OF IP-15, 4TH EDITION. ACTUAL HAZARD
GRADE
RADII MAY EITHER BE CALCULATED OR FOR A
CONSERVATIVE HAZARD RADIUS, THE HAZARD RADIUS (SEE
LIQUID LEVEL
FOR THE NEXT GREATER VENT SIZE MAY BE USED. FOLLOWING
4

00 NOTE 3)
0

15 4. AVERAGE MOLECULAR WEIGHT AND VENT RATE ARE


0

R1 0
0

=1
50 50 GENERALLY INDICATED BY PROCESS. 15000 L R1
=1
0 R1 5. R1 IS AS DEFINED IN THE RELEVANT HAZARDOUS
AREA SCHEDULE FOR THE SPECIFIC PIECE OF
HAZARDOUS AREA FROM LIQUID POOL
EQUIPMENT. REFER RELEVANT HAZARDOUS AREA
HAZARD
CLASSIFICATION SCHEDULE. EQUIVALENT DIAMETER
RADIUS
OF POOL, L (MM)
R1 (MM)

DETAIL 9: AREA CLASSIFICATION FOR SURFACE WATER


DRAINAGE (AOC DRAINAGE) IN NON ENCLOSED
ADEQUATELY VENTILATED AREA
GRADE

1000mm MIN. NOTES:


GRADE 3000mm MAX. 1. AREA CLASSIFICATION DETAIL PREPARED IN
ACCORDANCE WITH CL. 3.8.2 OF IP-15, 4TH

1500
4000 4000 GRADE EDITION.
2. THE ZONE-2 IS APPLICABLE WHERE THERE IS A
0 POSSIBILITY OF A SECONDARY GRADE RELEASE
R1
=15 150
= AND THE HAZARD RADIUS R1 FOR THE PRIMARY
00 R1 FLAMMABLE
LIQUID GRADE RELEASE IS LESS THAN 15000mm.
3. FOR THE PURPOSES OF THIS MODEL CODE A
4000

SUMP WIDTH SUMP MEANS A VESSEL OR PIT, OPEN OR VENTED


1500 TO ATMOSPHERE, USED TO COLLECT FLAMMABLE
LIQUID, USUALLY AS A RESULT OF DELIBERATE
NOTES: DRAINING. OTHER LIQUIDS, e.g. WATER, MAY ENTER
1. AREA CLASSIFICATION DETAIL PREPARED IN THE SUMP BUT THE FLAMMABLE LIQUID IS
ACCORDANCE WITH CL. 3.6.5 OF IP-15, 4TH EDITION. NORMALLY AN APPRECIABLE PART OF THE TOTAL
2. NORMAL OPEN SURFACE LIQUID DRAIN CHANNELS, LIQUID ENTERING. A SUMP IS USUALLY BELOW
1000

TYPICALLY NOT MORE THAN 500mm WIDE, HANDLING GROUND LEVEL.


FLAMMABLE MATERIALS SHALL HAVE A NOMINAL 4. SUMPS AND VESSELS COVERED WITH e.g. NTS
HAZARDOUS AREA OF 1000mm HORIZONTAL RADIUS VENTILATED CONCRETE SLABS OR METAL GRILLS
R2 L SEE NOTE 3 & 4 R2 4000 L SEE NOTE 3 & 4 4000 EACH SIDE AND 1000mm RADIUS VERTICALLY ABOVE SHOULD NOT BE REGARDED AS SEALED VESSELS
THEM. THE POSSIBILITY OF VAPOR RELEASE SHOULD BUT SHOULD BE TREATED AS OPEN SUMPS.
ALWAYS BE CONSIDERED WHEN ACCESS CHAMBER 5. WHERE THERE IS A POSSIBILITY THAT A HOT D
COVERS ARE LIFTED OR TEMPORARILY REMOVED. MATERIAL (e.g. CATEGORY C FLUID ABOVE 50°C OR
NOTES: 3. WHERE THERE IS A POSSIBILITY THAT A HOT
STEAM CONDENSATE) COULD ENTER THE SUMP IN 25-00053-0007-407
MATERIAL (e.g. CATEGORY C FLUID ABOVE 50°C OR
1. AREA CLASSIFICATION DRAWING PREPARED IN ACCORDANCE WITH CL. D2.1, D2.2, D3.3.2 AND D3.3.3 OF IP-15, 4TH EDITION. SUFFICIENT QUANTITY TO PRODUCE AN
STEAM CONDENSATE) COULD ENTER THE DRAIN IN
2. IN ADDITION TO THE ZONE 1 AREAS DURING THE LOADING OPERATION, TRANSIENT ZONE 2 HAZARDOUS AREAS SHOULD BE RECORDED WHERE SPILLAGE OF CLASS I, II(2) OR APPRECIABLE FLAMMABLE VAPOR, OR CATEGORY A X
SUFFICIENT QUANTITIES TO PRODUCE AN APPRECIABLE
III(2) MATERIALS COULD OCCUR. SPILLAGES IN THE LOADING AREA SHOULD BE CONSIDERED SECONDARY GRADE RELEASES. OR B FLUIDS COULD INADVERTENTLY ENTER, A
FLAMMABLE VAPOR, OR THAT CATEGORY A OR B KK/PY CG
3. THE EXTENT OF A SPILLAGE SHOULD BE ASSESSED ACCORDING TO THE EXPECTED DURATION OF RELEASE AND WITH DUE REGARD TO THE EXPECTED DURATION OF HAZARD RADIUS (R1) OF AT LEAST 15m SHOULD
MATERIALS COULD INADVERTENTLY ENTER, THESE 04/20/20 04/20/20
RELEASE, SURFACE GRADING AND DRAINAGE SYSTEMS. OVERFILLING A TANKER COMPARTMENT IS LIKELY TO RESULT IN THE FORMATION OF THE LARGEST WETTED AREA OR BE USED WITH AN INCREASED VERTICAL DISTANCE
DISTANCES SHOULD BE EXTENDED TO 3m.
POOL. DETAILS OF THE SURFACE AREA DRAINAGE (i.e. THE GRADING OF THE PAVED AREA & POSITION OF THE COLLECTING POINTS, DUCTS & CHANNELS) WILL DETERMINE OF 3m.
4. THE VAPORIZATION RATE FROM ANY VENTS ON DRAIN D 04/20/20 ISSUED FOR APPROVAL
THE SIZE OF POOL LIKELY TO BE FORMED FOR A GIVEN COMBINATION OF SPILLAGE RATE AND DURATION. 6. H DEPENDS ON THE TEMPERATURE OF RELEASE
SYSTEMS SHOULD BE LOW AND A ZONE-1 HAZARDOUS
4. R2 IS DEFINED IN THE RELEVANT HAZARDOUS AREA SCHEDULE FOR THE SPECIFIC PIECE OF EQUIPMENT. REFER RELEVANT HAZARDOUS AREA CLASSIFICATION SCHEDULE. AND THE VOLATILITY OF THE MATERIAL RELEASED.
AREA SHOULD BE DRAWN IN ACCORDANCE WITH TABLE
5. IF WEATHER ROOFING IS PROVIDED FOR THE LOADING AREA, THEN ALL SPACE ABOVE THE ZONE1 AREA WILL BE ZONE 2 UP TO THE ROOF. 7. THE ABOVE DRAWING IS FOR A PRIMARY GRADE 25-00053-0007
3.2 ASSUMING A VENT RATE OF NOT MORE THAN
6. ZONE 0 INSIDE COMPARTMENT APPLIES FOR ALL CLASSES OF FLAMMABLE FLUIDS. RELEASE FOR A SECONDARY GRADE RELEASE. THE
10Cu.M/HR, AT AMBIENT CONDITIONS, OTHERWISE IT
AREAS SHOWN AS ZONES 0 AND 1 ON THE ABOVE
SHALL BE BASED ON DISPERSION CALCULATION.
DRAWING SHALL BE RECLASSIFIED TO ZONE 1 AND HAZARDOUS AREA CLASSIFICATION
2 RESPECTIVELY.
HAZ
TYPICAL LAYOUT DETAILS
RIGS, PLATFORM AND UTILITIES
RAS AL KHAIR

D000 964 B RA-616190 001 D


CAD