Professional Documents
Culture Documents
Section 35 - Air Conditioning and Mechanic Ventilation System
Section 35 - Air Conditioning and Mechanic Ventilation System
35.1 General
1. This section includes the general requirement for materials, workmanship,
design and other items in respect of the Air Conditioning provisions in the
Contract.
2 The Contractor shall be responsible for the due performance of the works
in compliance with these requirements and the Contract.
1. Scope
2. Casings
(a) The casing shall consist of ¼" angle iron framework, to which are
fixed 18 gauge panels.
(c) The unit shall be completely insulated with ½" to 1" thick
odourless, fireproof, permanent glass fibre material having a
density of at least 2 lb/cu ft.
3. Compressor
(c) To reduce noise the hot gas discharge line shall incorporate a hot
gas muffler.
4. Cooling Coils
(a) The Cooling Coils shall be direct expansion type. The coils shall
be constructed of seamless copper tubing, with either aluminium
or copper fins, mechanically bonded to the tubes.
(b) Cooling Coil shall have two or more rows depending on size of the
unit.
(c) Cooling Coils shall have one refrigerant circuit for units up to and
inclusive of 7½ tons capacity and shall have one expansion valve
only. Larger capacity units have two or more refrigerant circuits,
and each circuit shall have its own expansion valve and solenoid
valve to achieve the required capacity modulation.
(a) The water cooled condenser shall be of shell and finned tube
design.
(b) It shall also incorporate a removable cast iron water header(s) and
the tubes shall be cleanable.
(c) The condenser shall be factory tested to at least 300 psi and shall
be provided with a spring-loaded pressure relief valve set and
sealed to relieve at 300 psi.
2. Casing
3. Condenser Coil
7. Fans
1. Evaporator Fan
2. Condenser Fan
(b) The fan(s) shall be direct driven and shall be statically and
dynamically balanced.
3. Discharge Plenum
(a) The discharge section from the fan shall be suitable for
either ducting or free discharge as shown on the drawings.
8. Controls
(a) All units shall incorporate high and low pressure cut-outs oil
pressure switch, non-recycling control relay.
9. Filters
(b) The face velocity across the filter shall not exceed 500 cfm.
All units shall incorporate a suitable size drain pan, with outlet connection.
The drain pan shall also be insulated with minimum 1" thick fireproof,
permanent insulation.
(b) The system used is Low/Medium pressure duct system and all
workmanship shall be suitable for this type of installation.
2. Materials
(a) The ducts shall be fabricated from best quality galvanised steel
sheets. Sheets on which the galvanising peels off on bending will
be rejected.
(c) Transverse reinforcing shall be applied on all four sides and tied
together at each corner by reveting, bolting or welding.
(d) All ducts shall be machine bent, free from sharp internal edges
and ensure tightness of seams and corners to minimise leakage.
(e) All ducts sizes shown are clear internal sizes and the dimensions
given in the drawing are 'plane of drawing' first and vertical
dimensions second.
(f) All transitions due to changes in duct size shall be done gradually
and a slope of 1" in 7" is to be used for all transitions.
3. Duct Supports
31 to 40 20 Drive, 1" Pocket or 1" Bar Slips 1" x 1" x 1/8" angles
on 7'10" centres 4" from joint
Table 35.2
(a) Elbows shall in general be long radius type and changes and
reduction in noise and turbulence.
(b) The connection shall be made such that, the renewal of the
canvas connection can be made without dismantling the ductwork.
(c) Where a fire hazard exists, the material used shall conform to the
requirements of the Local Fire or other Authority having
jurisdiction.
6. Dampers
2. Splitter Dampers
3. Butterfly Dampers
4. Louvre Dampers
5. Fire Dampers
ii) The fire damper shall be operated by a Fusible link set for
the maximum temperature allowed in the particular area.
iii) The Fire Dampers shall lock shut positively and shall be
opened manually. The damper shut or open position shall
be indicated by means of an external indicator.
7. The diffusers, registers and grilles shall be given one coat of rust
preventive primer and given one coat of flat grey enamel. The
final colour shall be enamel to Architect's selection. All the
diffusers, registers and grilles shall be painted matt black, behind
and internally.
8. The linear diffuser for VAV system shall have factory catalogue
performance ratings which conform to CFM, total pressure drop,
throw and drop as designated.
11. The linear diffuser shall be suitable for flush mountings in ceiling
with concealed fixing. Exposed screw heads will not be permitted.
8. Flexible Ducts
4. Flexible duct shall be insulated with 2" thick fibre glass similar in
manner to that for rectangular ducts.
9. Insulation Of Ductworks
a) Cork
The insulation shall be 2" thick and the density shall not
exceed 7.7 lb/cu ft. The thermal conductivity shall be 0.24
Btuh/in/sq ft/hr/F at 70oF mean temperature.
b) Onazote or Embonite
This shall be 2" thick with the density being 6 to 8 lb/cu ft.
The thermal conductivity shall be 0.23 Btu/in/sq.ft/hr/F at
70oF mean temperature. The installation shall be as per
recommendations of the manufactures. To obtain a
continuous vapour seal, all joints shall be sealed with low
temperature adhesive or mastic. The insulation shall be
finished with coats of aluminium bitumastic paint.
2. Balancing Procedure
ii) The capacity of the fan shall then be measured. This could
be measured by means of a rotating vane anemometer
vi) The fan capacity shall be re-checked and the fan speed or
main trunk damper shall be adjusted to make the fan
capacity equal to the design capacity.
Insect screens of the corrosion resistant type shall be provided and fixed
behind all intakes and discharge louvres, grilles and openings where
these occur on the outside of the building. The screens shall be fixed for
easy removal for periodic cleaning and shall be of minimum gauge 22.
All external supply and discharge air louvres shall be of the sizes
indicated on the Drawings and shall be supplied and fixed by the
CONTRACTOR. They shall be suitable for removal and be complete with
suitable corrosion resistant insect screens and shall be constructed of
steel or of aluminium.
1. General
2. Capacity
3. Compressors
Evaporator and condenser fans shall be direct driven. The evaporator fan
shall be the centrifugal type and the condenser fan shall be the propeller type
with provisions to eliminate condensate dripping.
Evaporator coils shall have copper tubing as the primary surface and
aluminium fins for the secondary surface. Condenser coils shall have copper
tubing as the primary surface and copper fins or hydrophilic fins or equivalent
for the secondary surface. They shall be factory tested for leaks. A suitable
metering device shall be provided for the refrigeration system.
6. Filters
Air filters shall be of the reusable type and be efficient for its purpose. They
shall be located so that they can be checked, cleaned and replaced easily.
1. General
Fans for the air-confitioning and ventilation shall be capable of giving the
specified performance when tested in accordance with B.S.848 and shall
be to UBBL requirements and local authorities approval. Although
estimated values of the resistance to air-flow of items of equipment may
be indicated, this does not relieve the CONTRACTOR of the responsibility
for providing fans capable of delivering the required air volume through
the system.
2. Propeller Fans
The fans shall be window mounted or wall mounted to suit the particular
installations. Wall mounted fans shall be supplied with wall boxes and
wall plates suitable for removal for cleaning or built in the wall where
shown on the Drawings. The fan shall be completed with weatherproof,
flush fitting grilles, draught preventing iris or similar shutters, wire guards,
etc. as specified.
3. Axial Fans
The fans shall be the tubeaxial, direct driven with aerofoil blades and
manufactured from heavy gauge metal or other approved materials. Fan
motors shall be non overloading over the characteristic curve at the
required rpm to deliver the specified airflows. Fans shall be the bifurcated
type where so specified.
The casings shall be longer than the length of the fan and motor. The
casings shall be of steel, shall have flanged ends and shall incorporate an
inspection door. The fans shall be complete with resilient mountings,
mounting feet or plates, connection spigots, wire guards and dampers.
Silencers shall be included if required to comply with restrictions on noise
levels.
Fans shall be suitable for their particular service, position of fitting and
chosen with respect to corrosion, inflamability or other hazardous
applications and shall not exceed any specified noise levels. Extended
lubricators shall be provided with a suitable size access panel for fans
fitted in a run of ductwork.
Fan speeds shall not exceed 1450 rpm unless specified otherwise. The
fans shall be directly coupled to totally enclosed squirrel-cage induction
motors suitable for either single-phase or three-phase, 50-Hz supply.
1. General
2. Material of Pipeworks
The refrigerant pipes shall be copper tubes complying with BS 2871 Part
2 1972.
Jointing of copper pipes for air conditioning units of 6 Hp and below shall
not be permitted.
4. Insulation of Refrigerant Pipes
The refrigerant pipes shall be insulated with 15mm thick flexible, close cell
light weight elastometric material. Liquid line and suction line refrigerant
pipe shall not be insulated together.
5. Pipe Supports
1. General
The horizontal run of the pipework shall be installed with a gradient of not
less than 1/100.
The spacing of supports for condensate drain pipes shall not be more
than 2.0m.
Spring diameters and hanger box lower hole sizes shall be large enough
to permit the hanger rod to swing thru a 30 o arc before contacting the
hole and short circuiting the spring. Springs shall have a minimum
additional travel to solid equal to 50% of the rated deflection. Submittals
shall include a scale drawing of the hanger showing the 30o capacity.
Hangers shall be type 30N as manufactured by Mason Industries, Inc.
1. Description
2. Performance
At the specified volume flow rate, sound attenuators shall not exceed the
maximum pressure loss stated on the Drawings.
b) The splitter shape for all attenuators, e.g. shape of nose cone and
taper of tail (if any).
3. Construction
The casing and cells shall have a smooth finish with all edges neatly
butted. Raw edges, fixing straps or screws shall not protrude into the air
stream.
Sound absorbent side panels, splitters and pods shall have acoustic infill
of mineral Rockwool or Fiberglass. The acoustic infill shall be covered by
perforated galvanised sheet steel not less than 1.0mm thick, and between
10% and 40% open area. All splitters shall have a sheet metal nose cone.
4. Installation
Sound attenuators should ideally be installed two duct diameters from any
obstacles such as bends, dampers etc. Where this is not possible,
splitters of rectangular sound attenuators shall be orientated in the same
plane as the bend.
1. General
The CONTRACTOR shall obtain, fill in and lodge all notices required by
any local authority, public or private, having jurisdiction over the
installation and shall obtain all consent necessary for the various work to
be executed and shall pay all fees in connection herewith.
2. Switchboards
All incoming and outgoing circuits and wirings shall be brought to the
contactors, starters, relays and controllers via insulated terminal strips
mounted within the cubicle. All wirings between terminal strips and
electrical equipment inside the control panels shall be neatly run and
taped in accordance with the requirements of the TNB.
Each switchboard panel shall be arranged such that the busbars run
horizontally through each sectionalized length, rigidly mounted on non-
hygroscopic insulators with connections from the busbars to the circuit
breakers and switches effected by means of copper bar or rod securely
clamped to the bars and identified by means of painting or coloured
plastic sleeving to indicate the phase colours.
3. Electrical Wirings
All wirings shall be carried out with PVC cables in fabricated conduits or
mineral insulated copper sheathed (MICS) cables and shall be run strictly
in accordance with the requirements of the TNB. All cables in which links
or abrasions occur shall be rejected and shall be replaced by the
CONTRACTOR at his own expense.
MICS cables shall be used where specified for wiring to motors and
equipment. Cables shall be neatly run on cable trays in the space under
floor ducts if provided or overhead exposed in the plant rooms or in
suitable trunking whichever is applicable.
Bending radius of cables shall be not less than eight times the overall
cable diameter. The cables shall be terminated at a brass junction box
near the motor or equipment terminal blocks and at earthbar inside the
switchboards. The connection between junction boxes and equipment or
motors shall be made by PVC cables and PVC heavy duty flexible
conduits fitted with approved brass screw type flexible conduit couplings.
Cable from above 6.5 sq.mm. shall be terminated with lug type or grip
cable sockets of approved manufacture.
4. Electric Motors
All motors shall be in accordance with B.S. 5000 Part 99 and B.S. 2757
with Class 'E' insulation to B.S. 2757. Motors shall be continuously rated
(C.M.R. category of B.S. 5000 Part 99) and shall have torque
characteristics as required by their respective duties. Motor enclosures
shall be IP44 unless otherwise specified.
Motor starters shall be in accordance with B.S. 587 and equipped with
overload, single-phasing and under-voltage protection. Where remote
control is required, starters shall be the contactor type with coils wound for
240V 50-Hz supply.
The rating of motors shall be such that they will not be over loaded at any
points within the range of operation of the equipment connected and shall
be of adequate rating and starting characteristic to allow equipment to be
brought up to speed on starting in a reasonable time.
All moulded case circuit breakers shall comply with the requirements of
BS EN60947-2:1992 and shall be of the current limited type. Unless
otherwise stated, the AC rated short-circuit capacity shall be:
The MCCB shall incorporate a time delay device to ensure that it will
tolerate harmless transient overload unless this is well in excess of 25%
of its rated value for a sustained period.
The MCCB shall be able to isolate the fault instantaneously for short
circuit current of the order of six to ten times the normal load current.
Incoming and outgoing circuits to the unit shall be protected for by fuses.
7. Earthings
8. Commissioning Tests
The complete installation or any part thereof shall be tested, both before
and after being connected up.
The CONTRACTOR shall be responsible for all electrical tests at the Site
and shall be represented by a capable and qualified personnel during the
whole of the period required for the tests.
Test certificates of each test and four copies of schedules of the results
shall be submitted by the CONTRACTOR to the E.R.
The following work associated with the electrical services to the air
conditioning and ventilation systems shall be carried out by the
CONTRACTOR.
o Conduit cable trays, cablings and control wirings between the air
conditioning switchboards and the various items of air conditioning
and ventilation equipment.
Only the best quality primers and paints shall be used on all equipment,
pipings, fittings, valves, hangers, conduits, framework, duckwork, insulation,
diffusers, grilles, switchboards, etc. and all work exposed to view.
The paint system for steel fabricated items and pipework shall consist of a
lead oxide or zinc chromate primer coat, a undercoat and two finish coats of
gloss paint of an approved colour .
The paint system for galvanised surfaces shall consist of a etching primer, a
zinc chromate primer coat and two finish coats of gloss paint of an approved
colour .
All unprotected concealed metal work shall be painted with two coats of
bituminous paint.
2. Colour Scheme
The colour of painting required for various items are as listed below:-
Colours
3. Labels
Directional arrows shall be in black on all visible sides of ducting and pipings
at 2.5m centres and on two visible sides of all pipings at each valve, fitting.
The size of arrows shall be 80mm long on pipes up to and including 50mm
diameter and 150mm long on pipes over 50mm diameter.
The position of all dampers, that is open, normal and shut shall be clearly
labelled.
Ventilation fans and all duplicated equipment shall be numbered and labelled
in 30mm high stencilled letters.
1. Testing Equipment
The following calibrated testing equipment shall be made available for the
testing and commissioning of the air conditioning and ventilation system.
2. Schedule of Tests
The air conditioning units shall be tested and fine tuned before the
following data are recorded to verify the performance of each equipment.
Also to be recorded are the observations made on the air conditioning unit
as detailed below:-
The quantity of air for ventilation system shall be set within +5% of the
figures given in the Drawings and final setting of air quantities shall be
recorded.
Test procedures and data sheets shall be submitted for approval by the
E.R two weeks before commencement of tests.
All tests and inspection shall be conducted in the presence of the E.R who
shall endorse all test records.
1. General
2. Scope of Work
Check the suction and discharge pressure of all split systems, and if
abnormal situation occurs, trace the faults and rectify as necessary.
Check carbon brushes and slip rings of all motors, and clean as
necessary. Renew carbon brushes as necessary.
Check safety devices fitted to all motors, and clean, adjust and
lubricate as necessary.
Clean, adjust and lubricate all bearings, pivots and other moving
parts as necessary.
3. Consumable Materials
1. General
Two (2) copies of the draft O&M Manual complete with as-built drawings
shall be submitted to the E.R. for approval 2 weeks before handing over
of the installations to the E.R. Upon approval by E.R., four (4) copies of
the hard cover bound O&M Manual shall be submitted to the E.R.
Technical catalogues
1. General description
The Compressor shall be air cooled, oil injected, single stage, positive
displacement rotary screw type, delivering 1500 ltrs/min of free air at 10
bar pressure at the outlet of the compressor. The air flow specification
shall be based on CAGI/Pneurop PN2 CPT C2 air flow measurement
conditions and methodology. The compressor shall be capable of
continuous full flow operation 24 hours/day at rated specified capacities
and pressure. All components are to be mounted on a rigid enclosure with
hinge doors for easy access safety interlocks and vibration isolation pads
for installation on any flat surface capable of supporting the eight of the
compressor shall also be provided .There shall be one point of electrical
input and one point for air discharge for ease of installation.
2. Airend
3. Bearings
All airend shall come with cylindrical and angular contact bearing capable
of operation up to pressure of 14.0 bar at outlet of compressor.
4. Motor
The motor shall be of the Totally Enclosed Fan Cooled (TEFC), IP54
enclosure type induction motor with a class F insulation and a service
factor of at least 1.5. The motor is to be operated by a 415 volt, three
phase, 50 Hz power source. The motor shall be applied such that only the
rated power is utilised at the specified compressor outlet pressure at full
load.
5. Starter
6. Controls
The compressor shall include all necessary control for the starting,
capacity control, operating control, and safety control of the unit. The
compressor should come standard with energy efficient DUAL control with
automatic shutdown of the motor on extended idling and automatic restart
after power failure. Optionally, it should be able to support modulation
control, quadro control and RS232/RS485 interface to other external
sequencing and control systems.
Over temperature
Main/Fan motor overloading
Wrong rotation of motors or wrong phasing on incoming supply
7. Drive Assembly
The motor and compressor airend shall be coupled via belt and pulley
system with integrated automatic belt tensioning device. The drive system
shall be capable of trouble free operation for a minimum of 10000 hours.
The entire assembly shall be vibration isolated from the package.
8. Enclosure
The unit shall come standard totally enclosed in a sound proofed steel
casing with a powder coat finish and hinged doors for easy maintenance
access. All doors should have a mechanical lock and safety interlock to
prevent unauthorised opening while in operation. Compressors should
come with 10 micro filter mats to ensure extended life and sufficient
cooling. The sound level shall not be more than 70 dBA at one meter.
9. Coolant/Lubrication System
The air cooler shall be efficient enough to provide a compressed air outlet
temperature of below 10oC above ambient conditions.
10. Piping
The compressor shall utilize rigid steel piping capable of safe operation up
to an outlet pressure of 14.0 bars and shall come with Aeroquip leak free
pipe connections for maintenance purposes. Each compressor system,
after manufacturing and assembly, will be 100% inspected and tested to
provide a piping system free of leaks and maintenance.
The receiver tank shall a capacity of 1000 liters and shall be designed and
manufactured according to ASME Section VIII Division 1 Boiler and
Pressure Vessel Code. The tank shall have a design/working pressure of
at least 150 psi 910.35 bar) and a test pressure of 300 psi (20.7 bar). The
tank shall be tested and approved by JKKP before delivery and
installation.
1. General Description
2. General Description
The dryer shall include precooling and reheating air circuits. The
precooling portion of this air circuit shall lower than inlet air temperature to
the compressed air, thus reducing the required refrigeration wattage. The
reheater portion of the air circuit shall reheat the cool dry air so as to
prevent condensation on the down stream piping. The precooler/reheater
shall be of the tube design that give continued efficiency and minimal
pressure drop.
3. Refrigeration System
5. Packaging
1. General Description
The system shall come with 1 unit of electronic level sensing condensate
drains for the receiver tank. The condensate drain shall be capable of
handling the condensate flow through the receiver tank. The operating
voltage shall be 230 V, 50Hz., single phase AC supply. The condensate
drains shall come with a alarm led and be equipped with a test feature.
1. General Description
The filter shall have the capability to remove the particle size down to 1
micron and remaining oil contents to 0.5 mg/m3 @ 20oC. The filter
medium shall be manufactured from borosilicate or its equivalent and is
binder free. The maximum working temperature shall be 40oC. The filter
shall be designed to withstand a maximum differential pressure of 5 bar
and provide a sufficiently large surface area to allow high flowrates.
1. General Description
Any pipework which in the opinion of the E.R shows signs of corrosion,
scale or deterioration of any form shall be remind from site whether
stoned or fixed and shall be replaced without cost to the E.R.
Pipework shall be clean and free from internal obstructions. All butted and
cut ends of tubes provide full unrestricted bone throughout. Any blockage
occury in the pipework system after installation shall be rectified without
any cost to the E.R.
2. Fittings
The fittings for pipes to BS 1387 shall be of malleable iron galvanised type
confirming to BS 143 with BS 21 Standard taper threads.
3. Joints
All cuts ends of pipes shall be at 90 degree to the axis of the tube and
filed smooth and reamed out to their original diameter.
All screwed joints cut onto the ends of tube shall be made with the use of
dies to suit the threads being used. The lengths and depths of thread cut
shall strictly comply with the requirement of the relevant standard to BS
21.
All joints shall be made with P.T.F.E. tape wrapped clockwise round the
male thread of the joint. Other forms of jointing material will only be
accepted with the written approval from the E.R.
All excess jointing material shall be removed after erection and the
exposed threads painted with zinc chromate paint, any damaged area of
the galvanised pipework during erection shall be filled smooth and
painted.
It should be noted that the “approved for construction” drawings may not
necessary indicate the location of all flanges and unions as defined by the
previous paragraph. Therefore it is deemed to be the CONTRACTOR’s
responsibility to provide and install such flanges and
The flanges table shall suit the system working and test pressure and any
items of fixed equipment. Bolting shall be high tensile steel with corrosion
protection finish, and sizes to suit the flange table being used.
Flange joints shall be made with CAF gaskets minimum 1.5mm thick.
When using BS1387 pipe, all union shall be of galvanised malleable iron
type confirming to BS143 with BS21 taper thread connections with bronze
seatings commonly referred to as the “Navy Pattern”.
5. Valves
Valves shall be provided at all places for the proper working and
regulation of the systems and are to be suitable for the working and test
pressure for the system on which they are installed.
a) Isolation Valve
6. Pressure Gauges
7. Expansion
All pipework shall be installed in such a manner that all expansion is taken
by changes to direction.
All pipework shall be installed with due consideration for expansion and
contraction such that these effects will not damage the pipework and
accessories nor will they put undue strain on the same.
8. Pipe Sleeves
Pipe sleeves shall be supplied and fixed on all pipes passing through
walls, ceiling and floors including all vertical ducts and be of the same
material as the pipe in which they are installed. They shall finish flush with
plaster and/or other finishes.
The sleeves are to be correctly positioned and pipes shall not, after fixing,
be built in solid with masonry material.
All pipe sleeves shall be packed with mineral wool insulation and caulked
with a non-hard setting compound. On external walls only mastic sealant
of at least 12mm shall be applied to totally vapour seal the gap.
Sleeves through floors and walls shall be of sufficient size to allow for
lateral expansion.
9. Supports
The design of supports and hangers shall be approved by the E.R prior to
fabrication, and they shall allow for the free movement of pipes at all
points with the exception of anchors.
All pipework supports, hangers etc. shall be fixed prior to the actual
pipework installation, temporary supports, fixing or other trades work is
satisfactory and shall not be permitted. The setting out of pipe runs and
hole positions SHALL be approved by the E.R prior to drilling or cutting.
20 mm 2500 mm 2500 mm
25 mm 2500 mm 2500 mm
40 mm 3000 mm 3000 mm
50 mm 3000 mm 3600 mm
80 mm 3600 mm 3600 mm
15 mm to 40 mm 9.5 mm
50 mm to 80 mm 12 mm
100 mm 16 mm
150 mm 22 mm